III. Unit Start-Up (cont)
COMPONENT TEST
USE ESCAPE/ARROW KEYS TO ILLUMINATE CONFIGURATION LED. PRESS ENTER TO DISPLAY ‘DISP’.
PRESS ENTER AGAIN TO DISPLAY ‘TEST’ FOLLOWED BY ‘OFF’. PRESS ENTER TO STOP DISPLAY AT
‘OFF’ AND ENTER AGAIN SO ‘OFF’ DISPLAY FLASHES. ‘PASS’ AND ‘WORD’ WILL FLASH IF PASSWORD
NEEDS TO BE ENTERED. PRESS ENTER TO DISPLAY PASSWORD FIELD AND USE THE ENTER KEY FOR
EACH OF THE FOUR PASSWORD DIGITS. USE ARROW KEYS IF PASSWORD IS OTHER THAN STANDARD.
AT FLASHING ‘OFF’ DISPLAY, PRESS THE UP ARROW KEY TO DISPLAY ‘ON’ AND PRESS ENTER. ALL LED
SEGMENTS AND MODE LEDS WILL LIGHT UP. PRESS ESCAPE TO STOP THE TEST. PRESS ESCAPE TO
RETURN TO THE ‘DISP’ DISPLAY. PRESS THE ESCAPE KEY AGAIN AND USE THE ARROW KEYS TO ILLU-
MINATE THE SERVICE TEST LED. PRESS ENTER TO DISPLAY ‘TEST’. PRESS ENTER TO STOP DISPLAY
AT ‘OFF’ AND ENTER AGAIN SO ‘OFF’ FLASHES. PRESS THE UP ARROW KEY AND ENTER TO ENABLE
THE MANUAL MODE. PRESS ESCAPE AND DISPLAY NOW SAYS ‘TEST’ ‘ON’. REFER TO THE TABLE
BELOW.
Service Test Mode and Sub-Mode Directory
NOTE: If the unit has a single circuit, the Circuit B items will not appear in the display, except the ability to configure circuit B will be displayed.
SUB-MODE
KEYPAD
ENTRY
ITEM DISPLAY
ITEM
EXPANSION
COMMENT
Completed
(Yes/No)
TEST
ON/OFF
SERVICE TEST MODE
To Enable Service Test Mode,
move Enable/Off/Remote
Contact switch to OFF. Change
TEST to ON. Move switch to
ENABLE.
OUTS
OUTPUTS AND PUMPS
FAN1
ON/OFF
FAN 1 RELAY
SIZES 010-018,
Condenser fan at low speed
SIZES 022-030
Condenser fan A1 energized
SIZES 032-055,
Condenser fan A2 energized
FAN2
ON/OFF
FAN 2 RELAY
SIZES 022-030,
Condenser fan A2 energized
SIZES 032-040,
Condenser fan B1 at high speed
SIZES 042-055,
Condenser fan B2 energized
CLP.1
ON/OFF
COOLER PUMP 1 RELAY
CLP.2
ON/OFF
COOLER PUMP 2 RELAY
CL.HT
ON/OFF
COOLER/PUMP HEATER
RMT.A
ON/OFF
REMOTE ALARM RELAY
CMPA
CIRCUIT A COMPRESSOR TEST
CC.A1
ON/OFF
COMPRESSOR A1 RELAY
CC.A2
ON/OFF
COMPRESSOR A2 RELAY
MLV
ON/OFF
MINIMUM LOAD VALVE RELAY
CMPB
CIRCUIT B COMPRESSOR TEST
CC.B1
ON/OFF
COMPRESSOR B1 RELAY
See Note
CC.B2
ON/OFF
COMPRESSOR B2 RELAY
See Note
MLV
ON/OFF
MINIMUM LOAD VALVE RELAY
See Note
ENTER
ENTER
ENTER
ENTER
Summary of Contents for AquaSnap 30RA010
Page 6: ...6 Fig 1 Typical Control Box for 30RA010 030 022 030 Shown ...
Page 7: ...7 Fig 2 Typical Control Box for 30RA032 055 042 055 Shown ...
Page 8: ...8 Fig 3 Wiring Schematic 30RA010 018 30RA010 018 AQUA SNAP ...
Page 10: ...10 Fig 4 Wiring Schematic 30RA022 030 30RA022 030 AQUA SNAP ...
Page 11: ...11 Fig 4 Wiring Schematic 30RA022 030 cont AQUA SNAP LOW VOLTAGE CONTROL SCHEMATIC 022 030 ...
Page 12: ...12 Fig 5 Wiring Schematic 30RA032 040 30RA032 040 AQUA SNAP ...
Page 13: ...13 Fig 5 Wiring Schematic 30RA032 040 cont AQUA SNAP LOW VOLTAGE CONTROL SCHEMATIC 032 040 ...
Page 14: ...14 Fig 6 Wiring Schematic 30RA042 055 30RA042 055 AQUA SNAP ...
Page 15: ...15 Fig 6 Wiring Schematic 30RA042 055 cont AQUA SNAP LOW VOLTAGE CONTROL SCHEMATIC 042 055 ...