Sterlco 30RAN010-055 AquaSnap Installation Instructions Manual Download Page 18

18

Step 5 — Make Electrical Connections

POWER SUPPLY — Electrical  characteristics  of  available
power supply must agree with unit nameplate rating. Field wir-
ing size and supply voltage must be within limits shown in
Tables 7 and 8. See Tables 9-11 for component electrical data. 

POWER WIRING  — All  power  wiring  must  comply  with
applicable local and national codes. Install field-supplied
branch circuit fused disconnect per NEC (National Electric
Code, U.S.A.) of a type can be locked OFF or ON. Disconnect
must be within sight from and readily accessible from unit in
compliance with NEC Article 440-14. 
General Wiring Notes 

1. The control circuit does NOT require a separate power

source. Control circuit power is obtained by a step-down
transformer from the main three-phase power supply. Up
to two terminal blocks are provided for field-wired
control devices. 

2. Cooler and pump heaters (if factory installed) are wired

in the control circuit so they are operable as long as the
main power supply to the unit is ON. A factory-installed
and set overload device protects them.

NOTE: The field-supplied disconnect should never be off
except when unit is being serviced or is to be down for a pro-
longed period, in which case cooler should be drained.

3. Power entry is at one end only.
4. Maximum field wire sizes allowed by lugs on terminal

block/non-fused disconnect are listed in Table 7.

5. Terminals for field power supply are suitable for

copper conductors. Insulation must be rated 167 F (75 C)
minimum.

Table 7 — Recommended Field Wiring Sizes

FIELD CONNECTIONS
Main Power — Bring wires from the fused disconnect switch
through hole in bottom of left front corner post (010-030 sizes)
or through hole in bottom center panel (032-055 sizes) of unit
to bottom of control box and connect to terminals on terminal

block or non-fused disconnect. A field neutral is required for
380/415-3-50 units only. To comply with NEC Article 440-14,
the disconnect must be located within sight from and readily
accessible from unit. Refer to Fig. 18 and 19.

Control Power — Control power is obtained from the main
power supply and does NOT require a separate source. A
toggle switch (marked Emergency On-Off on the unit label
diagram and by the switch) allows the control circuit to be
manually disconnected when necessary. Cooler and pump
heaters (if installed) are in an operable state when this switch is
in the Off position. 

Step 6 — Install Accessories

ELECTRICAL — A number of electrical accessories are
available to provide the following optional features (for details,
refer to the Controls, Start-Up, Operation, Service, and
Troubleshooting book):
Energy Management Module (Used for any of the following
types of temperature reset, demand limit and ice features):
• 4 to 20 mA leaving fluid temperature reset (requires

field-supplied 4 to 20 mA generator)

• 4 to 20 mA cooling set point reset (requires field-

supplied 4 to 20 mA generator)

• Discrete inputs for 2-step demand limit (requires field-

supplied dry contacts)

• 4 to 20 mA demand limit (requires field-supplied 4 to

20 mA generator)

• Discrete input for Ice Done switch (requires field-

supplied dry contacts)

Navigator Display — Provides hand-held, mobile capability
using easy to read   4-line display. Keypad function is the same
as the Scrolling Marquee module. Features magnet for ‘hands
free’ service of components.
Low Ambient Operation — If outdoor ambient operating
temperatures below 45 F (7.2 C) for 30RA010-018 units and
32 F (0.0° C) for 30RA022-055 units are expected, refer to sep-
arate installation instructions for low-ambient operation using
accessory Motormaster® V control.
Minimum Load Accessory — If minimum load accessory is
required, refer to unit Price Pages or contact your local Sterling
representative for more details. For installation details, refer to
separate installation instructions supplied with the accessory
package.
Miscellaneous Accessories — For applications requiring spe-
cial accessories, the following packages are available: Coil hail
guard, external vibration, enhanced display, temperature reset,
condenser coil grilles, storage tank and remote cooler. For
installation details, refer to separate installation instructions
supplied with these accessory packages.

ELECTRIC SHOCK HAZARD.
To avoid the possibility of electrical shock,
open and tag all disconnects before installing
this equipment.

IMPORTANT: Operating unit on improper supply voltage
or with excessive phase imbalance constitutes abuse and
may affect Sterling warranty.

CONNECTION

TYPE

MAX WIRE

SIZE

UNIT SIZE AND VOLTAGE

TERMINAL

BLOCK

#2/0 AWG

30RA010-030 (all voltages)

350 kcmil

30RA035-055 (all voltages)

60/100 AMP 

NON-FUSED

DISCONNECT

#1 AWG

30RA010-055 (575-3-60)
30RA010-030 
(380-3-60, 460-3-60)
30RA010-025 (380/415-3-50)
30RA010-018 (230-3-50, 230-3-60, 
208/230-3-60)

250 AMP

NON-FUSED

DISCONNECT

350 kcmil

30RA035-055 (380-3-60, 460-3-60)
30RA032-045 (380/415-3-50)
30RA022-045 (230-3-50)
30RA022-055 (230-3-60, 208/230-
3-60)

AWG

American Wire Gage

IMPORTANT: To ensure power to the heaters, make sure
auxiliary power to unit is always on (except for servicing or
prolonged shutdown).

Proper rotation of condenser fan(s) MUST be verified
before pumps or compressors are started. Consult the Con-
trols, Start-Up and Operation manual provided with this
chiller for correct procedure. Improper pump rotation can
cause permanent damage to pump impeller and housing. If
pump(s) have been removed for trimming, verify that wir-
ing is reconnected in the original manner.

Summary of Contents for 30RAN010-055 AquaSnap

Page 1: ...ture and on tags stickers and labels attached to the equipment Follow all safety codes Wear safety glasses and work gloves Keep quenching cloth and fire extinguisher nearby when brazing Use care in handling rigging and setting bulky equipment See Tables 1A 1D for Physical Data Refer to Fig 2 for unit weights INSTALLATION Step 1 Rig and Place the Unit RIGGING Preferred method is with spreader bars ...

Page 2: ...48 018 110 146 203 194 653 018 117 161 218 215 711 022 174 237 198 186 795 022 187 268 215 211 881 025 181 241 204 198 824 025 194 272 221 224 911 030 193 268 210 207 878 030 208 308 224 241 981 035 374 320 302 425 1421 035 422 356 341 474 1593 040 381 325 307 440 1453 040 429 361 346 490 1626 045 425 351 368 447 1591 045 473 387 408 496 1764 050 432 356 380 466 1634 050 479 394 421 514 1808 055 4...

Page 3: ...ti freeze in cooler to prevent freezing of residual water 4 At the beginning of the next cooling season refill cooler and add recommended inhibitor Fig 3 Unit Rigging Label Detail C Copper Finned Condenser Coil UNIT MAX SHIP WT W O PACKAGING MAX SHIP WT W PACKAGING LIFTING HOLES CENTER OF GRAVITY Lb Kg Lb Kg in mm in mm in mm in mm 30RA032 2791 1266 2965 1345 105 44 2678 87 00 2210 43 87 1114 46 0...

Page 4: ...a sq ft 23 23 23 32 32 40 55 55 64 64 80 HYDRONIC MODULE Optional Pump s Strainer W Blowdown Valve Expansion Tank Pressure Gages Drain and Vent Plugs Flow Switch and Balance Valve Pump Single or Dual Close Coupled Centrifugal Pump s 3500 Rpm Expansion Tank Volume gal 4 4 10 3 UNIT 30RA 010 015 018 022 025 032 035 042 045 REFRIGERANT TYPE R 22 TXV Controlled System Refrigerant Charge lb Ckt A Ckt B...

Page 5: ... 2 97 2 97 3 72 5 11 5 11 5 95 5 95 7 43 HYDRONIC MODULE Optional Pump s Strainer W Blowdown Valve Expansion Tank Pressure Gages Drain and Vent Plugs Flow Switch and Balance Valve Pump Single or Dual Close Coupled Centrifugal Pump s 58 3 r s Expansion Tank Volume L 16 5 39 UNIT 30RA 010 015 018 022 025 032 035 042 045 REFRIGERANT TYPE R 22 TXV Controlled System Refrigerant Charge kg Ckt A Ckt B 8 ...

Page 6: ...solid surface side Ends 3 ft 914 mm from solid surface for service access 2 Coil side clearance with accessory hail guard installed is 3 ft 914 mm to outside edge of hail guard top panel 3 Coil side clearance for multiple chiller installation is 6 ft 1981 mm 4 Flow switch is factory installed in leaving fluid piping Strainer is factory installed for entering fluid piping ...

Page 7: ...lid surface side Ends 3 ft 914 mm from solid surface for service access 2 Coil side clearance with accessory hail guard installed is 3 ft 914 mm to outside edge of hail guard top panel 3 Coil side clearance for multiple chiller installation is 6 ft 1981 mm 4 Flow switch is factory installed in leaving fluid piping Strainer is factory installed for entering fluid piping ...

Page 8: ...d surface side Ends 3 ft 914 mm from solid surface for service access 2 Coil side clearance with accessory hail guard installed is 3 ft 914 mm to out side edge of hail guard top panel 3 Coil side clearance for multiple chiller installation is 6 ft 1981 mm 4 Flow switch is factory installed in leaving fluid piping Strainer is factory installed for entering fluid piping ...

Page 9: ...lid surface side Ends 3 ft 914 mm from solid surface for service access 2 Coil side clearance with accessory hail guard installed is 3 ft 914 mm to outside edge of hail guard top panel 3 Coil side clearance for multiple chiller installation is 6 ft 1981 mm 4 Flow switch is factory installed in leaving fluid piping Strainer is factory installed for entering fluid piping ...

Page 10: ...olid surface side Ends 3 ft 914 mm from solid surface for service access 2 Coil side clearance with accessory hail guard installed is 3 ft 914 mm to outside edge of hail guard top panel 3 Coil side clearance for multiple chiller installation is 6 ft 1981 mm 4 Flow switch is factory installed in leaving fluid piping Strainer is factory installed for entering fluid piping ...

Page 11: ...id surface side Ends 3 ft 914 mm from solid surface for service access 2 Coil side clearance with accessory hail guard installed is 3 ft 914 mm to outside edge of hail guard top panel 3 Coil side clearance for multiple chiller installation is 6 ft 1981 mm 4 Flow switch is factory installed in leaving fluid piping Strainer is factory installed for entering fluid piping ...

Page 12: ...should follow sound engineer ing practice as well as applicable local and industry standards Improperly designed or installed systems may cause unsatis factory operation and or system failure Consult a water treat ment specialist or appropriate literature for information regard ing filtration water treatment and control devices Figure 10 shows a typical installation with components that might be i...

Page 13: ...tall a temporary bypass around the chiller to avoid cir culating dirty water and particulates into the pump pack age and chiller during the flush Use a temporary circulat ing pump during the cleaning process Also be sure that there is capability to fully drain the system after cleaning See Fig 13 2 Be sure to use a cleaning agent that is compatible with all system materials Be especially careful i...

Page 14: ...a pressure drop between the tank and the pump must be accounted for NOTE If the system requires a pre charge greater than 40 psig increase pressure as described below Expansion Tank Pre Charge To pre charge the expansion tank do the following steps 1 Check the tank air pressure at the pre charge connection with an accurate pressure gage Adjust as needed 2 If additional pressure is required charge ...

Page 15: ...on of the city water system should be consulted and followed to prevent contamination of the public water supply This is especially important when anti freeze is used in the system Set Water Flow Rate Once the system is cleaned pressur ized and filled the flow rate through the chiller needs to be established On units with the hydronic package this can best be done using the balancing valve In orde...

Page 16: ...s available from the factory as an accessory These tanks are designed to physically fit beneath the corresponding 30RA unit taking up the same footprint Available volumes are as follows 30RA010 018 110 gallons 30RA022 030 152 gallons 30RA032 055 305 gallons Maximum Loop Volume Since the minimum size of the expansion tank is dependent upon loop volume units with the integrated hydronic kit must not...

Page 17: ...tion where ambient tempera tures are expected to fall below 32 F Consult local water treat ment specialist on characteristics of the system water and add a recommended inhibitor to the chilled water 1 If the pump will be subjected to freezing temperatures steps must be taken to prevent freeze damage If the pump will not be used during this time it is recommend ed to drain the pump and hydronic pac...

Page 18: ... Management Module Used for any of the following types of temperature reset demand limit and ice features 4 to 20 mA leaving fluid temperature reset requires field supplied 4 to 20 mA generator 4 to 20 mA cooling set point reset requires field supplied 4 to 20 mA generator Discrete inputs for 2 step demand limit requires field supplied dry contacts 4 to 20 mA demand limit requires field supplied 4...

Page 19: ...92 2 125 311 3 110 96 2 125 110 97 4 125 110 97 4 125 110 99 6 125 110 208 230 60 187 253 1 102 4 125 316 4 125 106 8 125 125 108 2 125 125 108 2 125 125 110 6 150 125 460 60 414 506 1 50 3 70 160 0 60 52 3 70 80 52 9 70 80 52 9 70 80 54 0 70 80 575 60 518 633 1 41 2 50 140 4 50 42 8 50 50 43 3 50 50 43 3 50 50 44 2 60 50 380 60 342 418 1 65 2 90 202 2 80 67 6 90 80 68 4 90 80 68 5 90 80 69 7 90 8...

Page 20: ...60 2 1 9 1 3 0 380 60 2 2 9 1 4 6 042 380 415 50 2 2 3 2 2 3 230 50 2 3 8 2 3 8 045 230 60 2 4 8 2 4 8 208 230 60 2 5 3 2 5 3 460 60 2 2 4 2 2 4 575 60 2 1 9 2 1 9 380 60 2 2 9 2 2 9 380 415 50 2 2 3 2 2 3 230 50 2 3 8 2 3 8 050 230 60 2 4 8 2 4 8 208 230 60 2 5 3 2 5 3 460 60 2 2 4 2 2 4 575 60 2 1 9 2 1 9 380 60 2 2 9 2 2 9 055 230 60 2 4 8 2 4 8 208 230 60 2 5 3 2 5 3 460 60 2 2 4 2 2 4 575 60 ...

Page 21: ...2 205 34 1 225 41 6 310 035 230 60 29 4 265 36 7 265 43 8 380 208 230 60 32 7 265 40 8 265 48 7 380 460 60 14 6 120 20 2 135 23 8 175 575 60 12 2 80 16 6 120 18 9 140 380 60 18 9 155 26 4 170 30 1 235 380 415 50 24 2 175 24 2 175 24 2 175 230 50 41 6 310 41 6 310 41 6 310 040 230 60 36 7 265 36 7 265 43 8 380 208 230 60 40 8 265 40 8 265 48 7 380 460 60 20 2 135 20 2 135 23 8 175 575 60 16 6 120 1...

Page 22: ...emove the orange harness wire from TB5 1 and wire contacts in series as shown The contacts must be rated for dry circuit application capable of handling a 24 vac load up to 50 mA 5 Terminals 11 and 13 of TB5 are for control of Chilled Water Pump 1 CWP1 starter Terminals 13 and 15 of TB5 are for control of Chilled Water Pump 2 CWP2 starter The maximum load allowed for the chilled water pump relay i...

Page 23: ...ange harness wire from TB5 1 and wire contacts in series as shown The contacts must be rated for dry cir cuit application capable of handling a 24 vac load up to 50 mA 5 Terminals 11 and 13 of TB5 are for control of Chilled Water Pump 1 CWP1 starter Termi nals 13 and 15 of TB5 are for control of Chilled Water Pump 2 CWP2 starter The maximum load allowed for the chilled water pump relay is 75 va se...

Page 24: ...ns 6 and 7 for details Do not use compressor to evacuate system REFRIGERANT CHARGE Refer to Tables 1A 1D Immediately ahead of filter drier in each circuit is a factory installed liquid line service valve Each valve has a 1 4 in Schrader connection for charging liquid refrigerant If unit is equipped with a Motormaster V control the pres sure transducer has to be removed from the liquid line Schrade...

Page 25: ... PUMP UNITS 30RA032 055 PRESSURE DROP SINGLE PUMP UNITS 30RA010 030 PRESSURE DROP SINGLE PUMP UNITS 30RA010 030 LEGEND 1 30RA010 3 30RA018 5 30RA025 7 30RA032 30RA035 9 30RA042 30RA045 11 30RA055 2 30RA015 4 30RA022 6 30RA030 8 30RA040 10 30RA050 Use the following formula to convert Feet of water to psi Ft of water 4335 psi Use the following formula to convert psi to Feet of water Psi 2 306 Ft of ...

Page 26: ... DUAL PUMP UNITS SIZES 30RA032 055 PRESSURE DROP SINGLE PUMP UNITS 30RA032 055 PRESSURE DROP SINGLE PUMP UNITS 30RA032 055 LEGEND 1 30RA010 3 30RA018 5 30RA025 7 30RA032 30RA035 9 30RA042 30RA045 11 30RA055 2 30RA015 4 30RA022 6 30RA030 8 30RA040 10 30RA050 Use the following formula to convert Feet of water to psi Ft of water 4335 psi Use the following formula to convert psi to Feet of water Psi 2...

Page 27: ... Accessory Storage Tanks 1 ACCESSORY TANK FLOW RATE gpm PRESSURE DROP ft wg 30RA 900 010 30RA 900 001 009 100 0 10 0 1 0 0 1 10 100 1000 0 1 1 0 10 0 1 0 10 0 ACCESSORY TANK FLOW RATE L s PRESSURE DROP kPa 30RA 900 010 30RA 900 001 009 100 0 ...

Page 28: ...continue or change at any time specifications or designs without notice and without incurring obligations PC 903 Catalog No 533 00045 Printed in U S A Form 30RA 12SI Pg 28 7 02 Replaces 30RA 1SI Book 2 Tab 5c Copyright 2002 Sterling Sterlco ...

Reviews: