Sterlco 30RAN010-055 AquaSnap Installation Instructions Manual Download Page 17

17

Table 6 — Maximum Loop Volume Limits 

NOTE: Max loop volume is based on typical system of 12 psi and
30 psi of min/max pressures, and 100 F mean temperature. If the
volume in the system is greater than the limits listed, then extra
expansion tank volume must be added to the system.

 

Pump Modification/Trimming — Since the pumps are
constant speed, the only way to obtain greater flow with a
given pump/impeller is to decrease system head. This will
allow the pump to “ride” its curve to the right, resulting in
increased flow. If greater flow is necessary, look at opening the
balance valve. Also, verify that the strainer is clean, and that no
unnecessary system resistance is present, such as partially
closed isolation valves.

Increasing system resistance by closing the balancing valve

will force the pump to “ride” its curve to the left, resulting in
less flow. Although this does reduce power consumption
slightly, it may not be the desirable method of reducing the
flow, especially if a rather large reduction is needed.

The other method for reducing flow on a constant speed

pump is impeller trimming. The impellers in the pumps provid-
ed in the 30RA hydronic kit are easily removable for this pur-
pose. Refer to the ITT literature packet supplied with the
hydronic package information on Seal Replacement in the
Service Section, and follow its instructions for impeller remov-
al. Trimming should only be done by a qualified machine shop

that has experience in this operation. Contact your local Sterling
representative for a recommended machine shop. After trim-
ming, the impeller MUST be balanced. Failure to balance
trimmed impellers can result in excessive vibration, noise, and
premature bearing failure.

 Impeller trimming has the added benefit of maximum BHP

savings. It is very possible for power savings to pay for the
trimming cost very quickly.
Freeze Protection — The 30RA units are provided with a
water strainer and a flow switch to protect against freezing situ-
ations that occur from no water flow. While the flow switch
(paddle-type) is helpful in preventing freezing during no-flow
situations, it does not protect the chiller in case of power fail-
ure, or in other cases where water temperature falls below the
freezing mark. Appropriate concentrations of inhibited ethyl-
ene glycol or other suitable inhibited antifreeze solution should
be considered for chiller protection where ambient tempera-
tures are expected to fall below 32 F. Consult local water treat-
ment specialist on characteristics of the system water and add a
recommended inhibitor to the chilled water.

1. If the pump will be subjected to freezing temperatures,

steps must be taken to prevent freeze damage. If the
pump will not be used during this time, it is recommend-
ed to drain the pump and hydronic package and these
components back-flushed with inhibited glycol. Other-
wise, a glycol-water solution should be considered as the
heat transfer fluid. Drains are located on the balancing
valves for units with hydronic kits. Units without hydron-
ic kits have a drain mounted on the piping leaving the
heat exchanger. Drain knockouts are located on the sheet
metal base of all units.

NOTE: Do not use automobile anti-freeze, or any other fluid
that is not approved for heat exchanger duty. Only use appro-
priately inhibited glycols, concentrated to provide adequate
protection for the temperature considered.

2. Use an electric tape heater for the internal piping (exclud-

ing those within the pump box) if unit will be exposed to
freezing temperature.

3. Ensure that power is available to the chiller at all times,

even during the off-season, so that the pump and cooler
heaters have power. Also make sure that the piping tape
heaters also have power.

4. On units with pump packages, a heater is supplied in the

pump box that will protect this section from freezing in
outdoor-air temperatures down to –20 F, except in case of
a power failure. Sterling warranty does not cover damage
due to freezing.

5. Cooler heaters that will protect down to –20 F can be

installed as a factory option. Again, it should be noted
that these heaters will not protect the cooler from freezing
in the event of a power failure.

Preparation for Winter Shutdown — Do not shut off power
disconnect during off-season shutdown. At the end of the cool-
ing season:

1. Drain water from system.
2. Replace drain plug(s) and add sufficient inhibited ethyl-

ene glycol (or other suitable inhibited antifreeze) to
cooler, pump and piping to prevent freezing of residual
water.

3. At the beginning of the next cooling season, refill cooler

and add recommended inhibitor.

MAX LOOP VOLUME IN GALLONS (LITERS)

% Ethylene Glycol

30RA010-030

 30RA032-055

0 (Pure Water)

310 (1173)

725 (2744)

10

180 (681)

425 (1609)

20

175 (662)

410 (1552)

30

155 (587)

370 (1400)

40

150 (568)

350 (1325)

50

145 (549)

340 (1287)

% Propylene Glycol

30RA010-030

 30RA032-055

10

175 (662)

410 (1552)

20

150 (568)

350 (1325)

30

128 (484)

300 (1136)

40

118 (447)

275 (1041)

BAD

BAD

GOOD

GOOD

Fig. 17 — Tank Baffling

Summary of Contents for 30RAN010-055 AquaSnap

Page 1: ...ture and on tags stickers and labels attached to the equipment Follow all safety codes Wear safety glasses and work gloves Keep quenching cloth and fire extinguisher nearby when brazing Use care in handling rigging and setting bulky equipment See Tables 1A 1D for Physical Data Refer to Fig 2 for unit weights INSTALLATION Step 1 Rig and Place the Unit RIGGING Preferred method is with spreader bars ...

Page 2: ...48 018 110 146 203 194 653 018 117 161 218 215 711 022 174 237 198 186 795 022 187 268 215 211 881 025 181 241 204 198 824 025 194 272 221 224 911 030 193 268 210 207 878 030 208 308 224 241 981 035 374 320 302 425 1421 035 422 356 341 474 1593 040 381 325 307 440 1453 040 429 361 346 490 1626 045 425 351 368 447 1591 045 473 387 408 496 1764 050 432 356 380 466 1634 050 479 394 421 514 1808 055 4...

Page 3: ...ti freeze in cooler to prevent freezing of residual water 4 At the beginning of the next cooling season refill cooler and add recommended inhibitor Fig 3 Unit Rigging Label Detail C Copper Finned Condenser Coil UNIT MAX SHIP WT W O PACKAGING MAX SHIP WT W PACKAGING LIFTING HOLES CENTER OF GRAVITY Lb Kg Lb Kg in mm in mm in mm in mm 30RA032 2791 1266 2965 1345 105 44 2678 87 00 2210 43 87 1114 46 0...

Page 4: ...a sq ft 23 23 23 32 32 40 55 55 64 64 80 HYDRONIC MODULE Optional Pump s Strainer W Blowdown Valve Expansion Tank Pressure Gages Drain and Vent Plugs Flow Switch and Balance Valve Pump Single or Dual Close Coupled Centrifugal Pump s 3500 Rpm Expansion Tank Volume gal 4 4 10 3 UNIT 30RA 010 015 018 022 025 032 035 042 045 REFRIGERANT TYPE R 22 TXV Controlled System Refrigerant Charge lb Ckt A Ckt B...

Page 5: ... 2 97 2 97 3 72 5 11 5 11 5 95 5 95 7 43 HYDRONIC MODULE Optional Pump s Strainer W Blowdown Valve Expansion Tank Pressure Gages Drain and Vent Plugs Flow Switch and Balance Valve Pump Single or Dual Close Coupled Centrifugal Pump s 58 3 r s Expansion Tank Volume L 16 5 39 UNIT 30RA 010 015 018 022 025 032 035 042 045 REFRIGERANT TYPE R 22 TXV Controlled System Refrigerant Charge kg Ckt A Ckt B 8 ...

Page 6: ...solid surface side Ends 3 ft 914 mm from solid surface for service access 2 Coil side clearance with accessory hail guard installed is 3 ft 914 mm to outside edge of hail guard top panel 3 Coil side clearance for multiple chiller installation is 6 ft 1981 mm 4 Flow switch is factory installed in leaving fluid piping Strainer is factory installed for entering fluid piping ...

Page 7: ...lid surface side Ends 3 ft 914 mm from solid surface for service access 2 Coil side clearance with accessory hail guard installed is 3 ft 914 mm to outside edge of hail guard top panel 3 Coil side clearance for multiple chiller installation is 6 ft 1981 mm 4 Flow switch is factory installed in leaving fluid piping Strainer is factory installed for entering fluid piping ...

Page 8: ...d surface side Ends 3 ft 914 mm from solid surface for service access 2 Coil side clearance with accessory hail guard installed is 3 ft 914 mm to out side edge of hail guard top panel 3 Coil side clearance for multiple chiller installation is 6 ft 1981 mm 4 Flow switch is factory installed in leaving fluid piping Strainer is factory installed for entering fluid piping ...

Page 9: ...lid surface side Ends 3 ft 914 mm from solid surface for service access 2 Coil side clearance with accessory hail guard installed is 3 ft 914 mm to outside edge of hail guard top panel 3 Coil side clearance for multiple chiller installation is 6 ft 1981 mm 4 Flow switch is factory installed in leaving fluid piping Strainer is factory installed for entering fluid piping ...

Page 10: ...olid surface side Ends 3 ft 914 mm from solid surface for service access 2 Coil side clearance with accessory hail guard installed is 3 ft 914 mm to outside edge of hail guard top panel 3 Coil side clearance for multiple chiller installation is 6 ft 1981 mm 4 Flow switch is factory installed in leaving fluid piping Strainer is factory installed for entering fluid piping ...

Page 11: ...id surface side Ends 3 ft 914 mm from solid surface for service access 2 Coil side clearance with accessory hail guard installed is 3 ft 914 mm to outside edge of hail guard top panel 3 Coil side clearance for multiple chiller installation is 6 ft 1981 mm 4 Flow switch is factory installed in leaving fluid piping Strainer is factory installed for entering fluid piping ...

Page 12: ...should follow sound engineer ing practice as well as applicable local and industry standards Improperly designed or installed systems may cause unsatis factory operation and or system failure Consult a water treat ment specialist or appropriate literature for information regard ing filtration water treatment and control devices Figure 10 shows a typical installation with components that might be i...

Page 13: ...tall a temporary bypass around the chiller to avoid cir culating dirty water and particulates into the pump pack age and chiller during the flush Use a temporary circulat ing pump during the cleaning process Also be sure that there is capability to fully drain the system after cleaning See Fig 13 2 Be sure to use a cleaning agent that is compatible with all system materials Be especially careful i...

Page 14: ...a pressure drop between the tank and the pump must be accounted for NOTE If the system requires a pre charge greater than 40 psig increase pressure as described below Expansion Tank Pre Charge To pre charge the expansion tank do the following steps 1 Check the tank air pressure at the pre charge connection with an accurate pressure gage Adjust as needed 2 If additional pressure is required charge ...

Page 15: ...on of the city water system should be consulted and followed to prevent contamination of the public water supply This is especially important when anti freeze is used in the system Set Water Flow Rate Once the system is cleaned pressur ized and filled the flow rate through the chiller needs to be established On units with the hydronic package this can best be done using the balancing valve In orde...

Page 16: ...s available from the factory as an accessory These tanks are designed to physically fit beneath the corresponding 30RA unit taking up the same footprint Available volumes are as follows 30RA010 018 110 gallons 30RA022 030 152 gallons 30RA032 055 305 gallons Maximum Loop Volume Since the minimum size of the expansion tank is dependent upon loop volume units with the integrated hydronic kit must not...

Page 17: ...tion where ambient tempera tures are expected to fall below 32 F Consult local water treat ment specialist on characteristics of the system water and add a recommended inhibitor to the chilled water 1 If the pump will be subjected to freezing temperatures steps must be taken to prevent freeze damage If the pump will not be used during this time it is recommend ed to drain the pump and hydronic pac...

Page 18: ... Management Module Used for any of the following types of temperature reset demand limit and ice features 4 to 20 mA leaving fluid temperature reset requires field supplied 4 to 20 mA generator 4 to 20 mA cooling set point reset requires field supplied 4 to 20 mA generator Discrete inputs for 2 step demand limit requires field supplied dry contacts 4 to 20 mA demand limit requires field supplied 4...

Page 19: ...92 2 125 311 3 110 96 2 125 110 97 4 125 110 97 4 125 110 99 6 125 110 208 230 60 187 253 1 102 4 125 316 4 125 106 8 125 125 108 2 125 125 108 2 125 125 110 6 150 125 460 60 414 506 1 50 3 70 160 0 60 52 3 70 80 52 9 70 80 52 9 70 80 54 0 70 80 575 60 518 633 1 41 2 50 140 4 50 42 8 50 50 43 3 50 50 43 3 50 50 44 2 60 50 380 60 342 418 1 65 2 90 202 2 80 67 6 90 80 68 4 90 80 68 5 90 80 69 7 90 8...

Page 20: ...60 2 1 9 1 3 0 380 60 2 2 9 1 4 6 042 380 415 50 2 2 3 2 2 3 230 50 2 3 8 2 3 8 045 230 60 2 4 8 2 4 8 208 230 60 2 5 3 2 5 3 460 60 2 2 4 2 2 4 575 60 2 1 9 2 1 9 380 60 2 2 9 2 2 9 380 415 50 2 2 3 2 2 3 230 50 2 3 8 2 3 8 050 230 60 2 4 8 2 4 8 208 230 60 2 5 3 2 5 3 460 60 2 2 4 2 2 4 575 60 2 1 9 2 1 9 380 60 2 2 9 2 2 9 055 230 60 2 4 8 2 4 8 208 230 60 2 5 3 2 5 3 460 60 2 2 4 2 2 4 575 60 ...

Page 21: ...2 205 34 1 225 41 6 310 035 230 60 29 4 265 36 7 265 43 8 380 208 230 60 32 7 265 40 8 265 48 7 380 460 60 14 6 120 20 2 135 23 8 175 575 60 12 2 80 16 6 120 18 9 140 380 60 18 9 155 26 4 170 30 1 235 380 415 50 24 2 175 24 2 175 24 2 175 230 50 41 6 310 41 6 310 41 6 310 040 230 60 36 7 265 36 7 265 43 8 380 208 230 60 40 8 265 40 8 265 48 7 380 460 60 20 2 135 20 2 135 23 8 175 575 60 16 6 120 1...

Page 22: ...emove the orange harness wire from TB5 1 and wire contacts in series as shown The contacts must be rated for dry circuit application capable of handling a 24 vac load up to 50 mA 5 Terminals 11 and 13 of TB5 are for control of Chilled Water Pump 1 CWP1 starter Terminals 13 and 15 of TB5 are for control of Chilled Water Pump 2 CWP2 starter The maximum load allowed for the chilled water pump relay i...

Page 23: ...ange harness wire from TB5 1 and wire contacts in series as shown The contacts must be rated for dry cir cuit application capable of handling a 24 vac load up to 50 mA 5 Terminals 11 and 13 of TB5 are for control of Chilled Water Pump 1 CWP1 starter Termi nals 13 and 15 of TB5 are for control of Chilled Water Pump 2 CWP2 starter The maximum load allowed for the chilled water pump relay is 75 va se...

Page 24: ...ns 6 and 7 for details Do not use compressor to evacuate system REFRIGERANT CHARGE Refer to Tables 1A 1D Immediately ahead of filter drier in each circuit is a factory installed liquid line service valve Each valve has a 1 4 in Schrader connection for charging liquid refrigerant If unit is equipped with a Motormaster V control the pres sure transducer has to be removed from the liquid line Schrade...

Page 25: ... PUMP UNITS 30RA032 055 PRESSURE DROP SINGLE PUMP UNITS 30RA010 030 PRESSURE DROP SINGLE PUMP UNITS 30RA010 030 LEGEND 1 30RA010 3 30RA018 5 30RA025 7 30RA032 30RA035 9 30RA042 30RA045 11 30RA055 2 30RA015 4 30RA022 6 30RA030 8 30RA040 10 30RA050 Use the following formula to convert Feet of water to psi Ft of water 4335 psi Use the following formula to convert psi to Feet of water Psi 2 306 Ft of ...

Page 26: ... DUAL PUMP UNITS SIZES 30RA032 055 PRESSURE DROP SINGLE PUMP UNITS 30RA032 055 PRESSURE DROP SINGLE PUMP UNITS 30RA032 055 LEGEND 1 30RA010 3 30RA018 5 30RA025 7 30RA032 30RA035 9 30RA042 30RA045 11 30RA055 2 30RA015 4 30RA022 6 30RA030 8 30RA040 10 30RA050 Use the following formula to convert Feet of water to psi Ft of water 4335 psi Use the following formula to convert psi to Feet of water Psi 2...

Page 27: ... Accessory Storage Tanks 1 ACCESSORY TANK FLOW RATE gpm PRESSURE DROP ft wg 30RA 900 010 30RA 900 001 009 100 0 10 0 1 0 0 1 10 100 1000 0 1 1 0 10 0 1 0 10 0 ACCESSORY TANK FLOW RATE L s PRESSURE DROP kPa 30RA 900 010 30RA 900 001 009 100 0 ...

Page 28: ...continue or change at any time specifications or designs without notice and without incurring obligations PC 903 Catalog No 533 00045 Printed in U S A Form 30RA 12SI Pg 28 7 02 Replaces 30RA 1SI Book 2 Tab 5c Copyright 2002 Sterling Sterlco ...

Reviews: