Emitters need to be replaced every 9000 hours. Use Genuine Steril-Aire Emitters to maintain design output. If a Steril-Aire
UVC Radiometer Kit is used, the Emitters should be replaced when the output falls below 50% of initial output.
Always use Genuine Steril-Aire replacement parts. Parts in this device were certified by one or more safety
originations such as UL, CE... Replacement parts not intended for this device may cause equipment failure or damage.
Replacement Fuses:
Fuse
Description
Part#
F1 & F2
FUSE 0.5A 600VAC Type CC, For Line Input
80004125-500
F3
FUSE GLASS 1.25A 250VAC 5X20MM, For 24VAC
80004127-1250
M
AINTENANCE
S
PARE OR
R
EPLACEMENT
P
ARTS
Controller Part Number Options
810WPVAB
Full Amps
0 = 4A
1 = 6A
3 = 10A
O = 16A
5 = 20A
6 = 30A
S = 32A
7 = 40A
U = 50A
Branch Amps
E = 2A
F = 3A
2 = 5A
J = 8A
3 = 10A
4 = 15A
O = 16A
5 = 20A
Q = 25A
Phase
1 = SINGLE
2 = DOUBLE
Volts
3 = 100
4 = 120
5 = 208
6 = 240
7 = 277
Options
0 = Legacy Watchdog
2 = UVC Controller II
3 = UVC Controller III
NOTE: Circuit breakers need to be rated 125% of its expected load. If your load is 16.7A, then your circuit breaker needs to handle
22A. A 20A circuit breaker is to small, you will need a 30A circuit breaker.
Formula: Load amps x 1.25 = minimum circuit breaker size. 16.7A x 1.25 = 22A
___________________________________________________________________________________________________________
Thank you for choosing Steril-
Aire, #1 “UVC for HVAC” solution provider worldwide. Please contact your local supplier or Steril-Aire
directly if we can provide any further information or service. Call
1-8
18-565-1128
or visit
. Your satisfaction is
very important to us.
The health aspects associated with the use of this product and its ability to aid in disinfection of environment air have not been
investigated by UL.
© 20
19 Steril-Aire, Inc. All rights reserved.
Part #:
114
6A