Ensure mains at the power panel are turned off before connecting power to the controller. Apply any necessary 

protection to assure that mains are not accidently turned on during the installation. 
 

1)  Caution use marked areas on the inside of the 

enclosure for safe drilling locations. To prevent 
cracking, ensure that holes are not close to each 
other. 
 

3)  Make sure the controller is designed for the line 

voltage and intended load. Check labels, circuit 
breakers and fuse sizes before installing. 
 

4)  Make sure all the circuit breakers in the 

controller are turned off. 

 

5)  Remove the 2 screws that secure the inner door. 

This compartment should be opened by a 
qualified electrician only! 
 

6)  Connect the door switch to the two terminals on 

TB1 marked “DOOR”. The door switch is class 2 
low voltage. 

 

TB1 
AGW 

16-24 

 
 

7)  Connect BMS. BMS includes Door, Emitters and 

Watchdog. 
 

8)  Connect Bank-1 and Bank-2 Loads. Ensure that 

both banks carry relatively equal load for proper 

watchdog operation. Ensure proper circuit 
breaker and grounding wire torque 
 

9)  Connect Mains. Ensure proper circuit breaker 

and grounding wire torque 
 

10) Torque the circuit breakers CB1, CB2 & CB3. 

CB1, CB2 & CB3 - Torque 
AGW 

In. Lb. 

3 to 12 

13 to 17.5 

 

11) Torque ground bar TB2. 

TB2 

– Torque 

AGW 

In. Lb. 

4 to 6 

45 

40 

10 to 14 

35 

 

12) Close inner door and secure the screws. 

 

13) Turn on the mains at the power panel on. 

 

14) Turn on the mains in the UVC Controller. 

 

15) The RED stop light should be illuminated. 

 

16) Turn on the Bank1 and Bank2 circuit breakers. 

 

17) Close and latch the Simple Controller front door. 

 

18) Press the Green Start Button. 

 

19) The emitters should be illuminated. 

 

The current loop has an isolated 12VDC power source, no need for an external power supply. Line resistance can vary 
from 0 to 200 ohms. Isolation is rated at 1.5KV. The 4-20ma current loop output represents 0-50A.  
Calculate Amps to current loop: (Amps/3.125) + 4 = ma 
Calculate Current loop to Amps: (ma 

– 4) x 3.125 = Amps 

Example using 40A: (40A/3.125) + 4 = 16.8ma 
 
 
 
 
All solid state relays are normally opened, 60v AC/DC Max, 150Ma Max, 16 ohms Max closed, 1.5KV isolation. If the UVC 
Controller loses power, contacts default to closed (alarm condition).

I

NSTALLATION

 

BMS

 

4-20

MA 

C

URRENT 

L

OOP

 

BMS

 

S

OLID 

S

TATE 

C

ONTACTS 

(D

OOR 

O

PEN

,

 

E

MITTERS 

O

FF

,

 

F

AULT

2)  This enclosure meets type 4 approval and IP6

criteria for water resistance. Use fittings that are 
consistent with the environmental rating of the 
enclosure. Use proper torque values on fittings. 
 

Summary of Contents for UVC Controller II

Page 1: ...e ensure unit is unplugged Electrical shock can cause death CAUTIONS Never expose eyes or skin to UVC light Wear gloves face shield glasses per ANSI Z87 1 and cover all exposed skin Do not touch EmitterTM glass without gloves Damage to Emitter may result Oil from fingerprints will permanently etch glass of Emitter and weaken structure Clean Emitter using a Steril Aire cleaning kit included Isoprop...

Page 2: ...he circuit breakers CB1 CB2 CB3 CB1 CB2 CB3 Torque AGW In Lb 3 to 12 13 to 17 5 11 Torque ground bar TB2 TB2 Torque AGW In Lb 4 to 6 45 8 40 10 to 14 35 12 Close inner door and secure the screws 13 Turn on the mains at the power panel on 14 Turn on the mains in the UVC Controller 15 The RED stop light should be illuminated 16 Turn on the Bank1 and Bank2 circuit breakers 17 Close and latch the Simp...

Page 3: ...mponent Locations Menu Select Button Display Menus Status QR Barcode Link to Watchdog Manual F1 F2 0 5A 600V PN 80004125 500 TB2 Neutral Ground F3 1 25A 250V 80004127 Circuit Breakers Remote Control BMS Connections ...

Page 4: ...Press and hold button to clear counts Timer Menu Emitter end of life count down and total run hours Yellow indicates Emitters need to be ordered 672 hours or 4 weeks remaining Red indicates Emitters have expired replace emitters After replacing Emitters Press and hold button to clear 9K count Order Menu The order menu will popup when there is 672 hours of Emitter life remaining Yellow indicates Em...

Page 5: ...20A Q 25A Phase 1 SINGLE 2 DOUBLE Volts 3 100 4 120 5 208 6 240 7 277 Options 0 Legacy Watchdog 2 UVC Controller II 3 UVC Controller III NOTE Circuit breakers need to be rated 125 of its expected load If your load is 16 7A then your circuit breaker needs to handle 22A A 20A circuit breaker is to small you will need a 30A circuit breaker Formula Load amps x 1 25 minimum circuit breaker size 16 7A x...