
Fire Control Panel FS4000
−
System fault - indicator
(System fault) is illuminated in yellow light;
−
Fault in fire alarm line – separate indicator for fault condition flashes in yellow to indicate:
♦
Short circuit - 1Hz frequency /slow flashing light/;
♦
Break in a line - 4Hz frequency /quick flashing light/;
♦
Removed fire detector - 4Hz frequency, 1 second pause /interrupted, quick flashing
light/.
−
Fault condition in controllable output - indicator
Out of order / Disabled controllable
output) flashes in yellow light;
−
Fault in backup batteries - indicator
(Backup battery fault) is illuminated in yellow light;
−
Fault in power supply to external devices - indicator
(Fault in internal power supply) is
illuminated in yellow light;
−
Short circuit or leakage to ground wire - indicator
(Fault in grounds) is illuminated in
yellow light.
−
Fault in the local network or in the transmitting device
the right indicator is illuminated
in continuous yellow light.
The local sounder is activated and produces discontinuous signal. If the sound indication has been
suppressed by button
(Alarm), the LED indicator
is illuminated in continuous red light.
9.3. Using the buttons
No buttons are active in System fault.
In all other fault conditions button
(Alarm) is active only. Press the button to:
−
Switch off the local sounder if it responded for Fire condition or Fault condition;
−
Activate the local sounder if the Fire control panel is in Fire condition or Fault condition
and the local sounder is previously suppressed by the same button.
The LED indicator
is illuminated, if the local sounder is switched off for Fire condition or
Fault condition.
The button does not affect nor is its action cancelled by the following events:
−
When new line enters Fire condition, the local sounder will be activated;
−
When new fault condition is registered, the local sounder will be activated.
Access to the button is allowed at Access level 1, 2, 3.
10. Disabled component mode
10.1. Description
The fire control panel enters Disabled component mode after a component has been manually
disabled – a fire alarm line or a controllable output. The condition is set through microswitchers for
each line separately, and also for outputs for fire condition – controllable and relay outputs.
The disabled line is switched off (the power supply is cut off) and is not monitored for activated
fire detector and faults. The disabled outputs are switched off (the executive device can not operate)
and the controllable output is not monitored for faults.
10.2. Disable/Enable a line:
Instruction manual
Page 14
Revision 4/02.11
of 24