Fire Control Panel FS4000
8. Fire condition
8.1. Description
The Fire Control Panel enters Fire condition upon double activation of a fire detector in any fire
alarm line, for a period not longer than 60 seconds. After the first activation the control panel resets
the fire alarm line for 3 seconds, and expects second activation in the next 60 sec. If activation occurs
in this period, the Fire Control Panel enters Fire Condition. The Fire Control Panel can enter Fire
condition in one fire alarm line or in a number of fire alarm lines.
To exit Fire condition, press button
at Access level 2.
8.2. LED and sound indication
In this condition are illuminated :
- common indicator
with red interrupted light if Fire condition 1
st
stage and red continuous
light if Fire condition is 2
nd
stage;
- local indicators from all lines of which the Fire Control Panel has indicated Fire condition;
- If the local sounder is suppressed by button
, the indicator built-in the button is illuminated
with red light ;
- if the outputs are suppressed by button
, then the button indicator is illuminated with red
light;
Local sounder is activated.
If the Control Panel is connected with local network by Remote Control Panel for indication
, the indicator is illuminated in red light when receiving a confirmed signal for Fire condition
from the Remote Panel FS5200E.
8.3. Using the buttons
8.3.1.
Button
(Alarm)
Press the button to:
−
Switch off the local sounder if it is activated due to Fire condition or Fault condition;
−
Activate the local sounder if the fire control panel is in Fire condition or Fault condition and the
local sounder is previously deactivated by the same button.
Instruction manual
Page 12
Revision 4/02.11
of 24