5
INSSEFECMI0513
Note that this product must be connected by a qualified electrician according to the electrical and building codes effective in your
region. for 240 vac connection, you can use copper or aluminum wire (75°c (165°f)), except for 27 kw and 30 kw models where only
copper wire is allowed.
This furnace must be connected to a 240/208 VAC power source. For 240V power supply, either copper or aluminum wires can be used, except
for 27 and 30kW models where only copper wire can be used (see the power connection illustration below). If you want to energize the furnace at
208 VAC, you must change a connection on the 24 V terminal board of the transformer (see the illustration below). Refer to the local and national
electrical codes to know which wire size, fuses and circuit breakers are required.
A 1-pole power supply is installed in the electrical compartment of the furnace. It is used to connect a neutral line conductor at the entrance. Some
auxiliary devices, like a dehumidifier, are supplied by a 120 VAC power source. The neutral conector allows to supply auxiliary devices with a 120
VAC power source from the furnace.
electrical connections of the furnace
Power ConneCTion DrAwings (meChAniCAL)
TRANSFORMER PRIMARY VOLTAGE SELECTION
The transformer primary is connected in factory to operate on 240 VAC (black and red wires)
Summary of Contents for SEFECM Series