background image

9

8

GB

9�  Technical specifications

Malfunction

Cause

Remedy

No power at the sensor

 

Fuse has tripped, not switched 

ON, break in DALI wiring

 

Short circuit

 

Activate, change fuse, turn ON 

mains switch, check DALI wiring 

with voltage tester

 

Check connections

Light level not being 

communicated

 

Break in wiring

 

DALI power supply faulty

 

Check cable

Sensor sending motion 

detection signal when it 

should not

 

There is interference,  

e.g. fan, air-conditioning system 

or other source of heat,  

in the detection zone

 

Animals moving in detection zone

 

Wind is moving paper or plants in 

the detection zone

 

Sunlight is shining on the lens

 

Sudden temperature change  

due to air expelled from fans, 

open windows, air-conditioning 

systems or other sources of heat

 

Sensor near Wi-Fi or other wire-

less communication source

 

Adjust detection zone or fit  

shrouds, increase distance

 

Adjust zone or fit shrouds

 

Change detection zone

 

Mount sensor in a protected  

place or change zone

 

Adjust detection zone or install  

in a different place

 

Install at least 2 m away from the 

wireless communication source

10� Troubleshooting

Dimensions (H x W x D)

US 360 

120 × 120 × 68 mm

Single US  

120 × 120 × 73 mm

DualTech 

120 × 120 × 68 mm

Dual US  

120 × 120 × 73 mm

Power consumption

US 360

 

17.9 mA 9 users

Single US

 

15 mA 8 users

DualTech

 

17.5 mA 9 users

Dual US 

18 mA 9 users

DALI interface

DALI control line (multi-master capability for communication with the 

DALI Application Controller), DALI start-up time < 1 s

Detection zone

US 360 / DualTech 

   tangential/presence:  max. Ø 6 m min. (28 m

2

)

 

 

min. Ø 2 m (12 m

2

 

radial: 

reach up to Ø 10 m

Reaches

Single US / Dual US

   max. 3 × 10 m / 3 × 20 m (30 / 60 m²)

 

min. 3 × 2.5 m / 3 × 5 m (7.5 / 15 m²) 

Mounting height

2.5 - 3.5 m

Sensor system

DualTech

 

PIR (passive infrared), single pyro sensor,  

 

11 detection zones, 520 switching zones.  

 

Ultrasonic 40 kHz

US 360 / Single US /  

DualTech  

Ultrasonic 40 kHz

IP rating

IP20

Temperature range

-25°C to +55°C

Summary of Contents for Control PRO Series

Page 1: ... Änderungen vorbehalten Subject to technical modification without notice 2 US 360 Single US DualTech Dual US 000000000 09 2013 Technical changes subject to no prior notification US 360 DALI 2 Input Device Single US DALI 2 Input Device DualTech DALI 2 Input Device Dual US DALI 2 Input Device Information RUS CN BG LV LT EST HR SLO RO PL SK CZ H TR GR N FIN DK S P E I NL F GB D ...

Page 2: ... DualTech 3 2 Single US Dual US 3 3 US 360 DualTech D 8 GB 9 Textteil beachten Textteil beachten 3 3 4 Single US Dual US 4 4 1 4 2 3 4 Single US Dual US 4 4 1 4 2 2 3 3 US 360 DualTech GB 6 Follow written instructions ...

Page 3: ...4 5 4 4 3 4 4 5 4 5 Single US Dual US 4 6 4 7 DA DA 4 8 5 ...

Page 4: ...3 Part 303 and Part 304 The motion detection values and light levels measured by the sensor can be requested from the DALI Application Controller Automatic or time based cyclical transmission can also be selected You will find detailed information in the interface description on the Internet at www DALI 2 steinel de LED function Blue LED Initialisation LED flashes once every 2 seconds Normal mode ...

Page 5: ...se distance Adjust zone or fit shrouds Change detection zone Mount sensor in a protected place or change zone Adjust detection zone or install in a different place Install at least 2 m away from the wireless communication source 10 Troubleshooting Dimensions H x W x D US 360 120 120 68 mm Single US 120 120 73 mm DualTech 120 120 68 mm Dual US 120 120 73 mm Power consumption US 360 17 9 mA 9 users ...