Specifications 

Steffes | 3050 Highway 22 North | Dickinson, North Dakota 58601-9413 | 701-483-5400 

Rev 3

 

Model 9150

53kW Storage Module

Model 9180 

80kW Storage Module

Input Voltage

277/480

347/600

277/480

347/600

Phase

3

3

3

3

Number of Wires

4

4

4

4

Charging Input (kW)

50.4

53.3

75.6

80.0

Elements - Quantity

Elements - Watts Each

12

4,200

12

4,444

18

4,200

18

4,444

Amps - Core Charging

60.65

51.23

90.97

76.84

Max. Pump & Blower Load (AMPS) 

Tentative

2.3

1.9

2.3

1.9

Minimum Circuit Ampacity

78.69

66.41

116.59

98.43

Blowers/System Control Voltage

*

240V/208V

Storage Capacity - kWh

***

Storage Capacity - BTU

290

989,480

440

1,501,280

Pipe Size (Inlet/Outlet)

1 ½” 

Required Primary Loop

Minimum of 12’ of 1 ½” pipe required in primary loop plumbing

Output Water Temperature 

(selection range)

50

o

F to 185

o

F

Maximum Working Pressure

20 PSIG requires 30 PSI Pressure Relief Valve  

60 PSIG requires 75 PSI Pressure Relief Valve (Standard) 

125 PSIG requires 150 PSI Pressure Relief Valve 

Flow Rate (Primary Loop)

1 GPM per 10,000 BTU of required output at 20

o

F Temperature Rise 

(Not to exceed 30 GPM)

Internal Pressure Drop

  (assuming 50% glycol mix)

.7 ft @ 15 GPM     1.8 ft @ 25 GPM

1.2 ft @ 20 GPM      2.5 ft @ 30 GPM

Approximate Heater Module Weight 

(lbs)

900

970

Approximate Insulation 

Block/Elements/Other Weight (lbs)

330

400

Approximate Brick Weight (lbs)

3,440

5,160

Number of Brick

192

288

Approximate Installed Weight (lbs)

**

4,670

6,530

*

 Supply via step-down transformer - field installation.

**

 Add approximately 500 lbs to arrive at shipping weight. 

*** 

Storage capacity is based on a maximum core temperature of 1,400 degrees Fahrenheit. 