REARMING / STATUS INDICATOR INSTRUCTIONS
SECUMATIC 3001S
(1) Hold the mechanism as shown in the picture
above. Remove used Cylinder by twisting it in a
counter-clockwise direction. Throw used Cylinder in
garbage.
(2) Carefully lift lever marked with the
CAUTION
symbol until you hear it “click”. Be careful not to let
it snap down on your fingers.
(3) Carefully insert the Pill into the Pill holder.
(4) Close the Jerk Cord lever so it points toward the
Cylinder holder. The only part of the lever you
should be able to see is where it is attached to the
cord.
(5) Insert Green Pin into the hole that is surrounded
by red. Make sure the pin passes through the Jerk
Cord lever also.
(6) Check CO
2
cylinder. If the cap has a hole or is
scratched, throw it away and get a new one that is
not damaged.
(7) Install the inspected cylinder, twisting it in a
clockwise direction. Twist until the window under the
cylinder (indicated by C in the illustration) turns
green.
(8) Close the lever marked with the
CAUTION
symbol. Be careful not to let it snap down on your
fingers.
(9) Review the Indicator Check instructions below.
Make sure indicators at locations A, B, and C are
GREEN. If you see any RED areas, try to rearm
the mechanism again – a step has been missed or
done incorrectly.
Use RE P L ACE M E NT K IT No . 0 9 2 0 a nd 0 9 2 3