background image

Page 9

Page 10

REMOTE DIGITALS OPTION

Two isolated digital inputs are available to reset latched alarms, clear peak/valley readings, or for 
customised use with TFML.

Simple plug in pre-calibrated units, no dismantling or re-calibration.

POD-3000/02 DUAL RELAY ALARM 

Two independent mains rated relay outputs 

Contacts

2 x changeover relays with common wiper

Ratings

AC, DC

Maximum Load

5 A @ 250 V, 5 A @ 30 V

Min Load

100 mA

Maximum Power

1250 VA, 150 W

Maximum Switching 

253 V, 125 V

Electrical Life

1 M operations at rated load

Mechanical Life

50 M operations

Termination       Standard

5 way tension clamp connector

Optional Screw 

terminals 

Pulse Mode

Pulse period 100 ms

POD-3000/03  ISOLATED RE-TRANSMISSION 

Ranges

(0 to 10) mA (Active or Passive)
(0 to 20) mA (Active or Passive)
(4 to 20) mA (Active or Passive)

Minimum Current Output

0 mA

Maximum Current Output

23 mA

Accuracy

0.07 % F.S.

Resolution

1 part in 30 000

Max. Output load 

See Section 4.3

Max. Ext. Supply Voltage

30 V (Passive mode)

Voltage Effect

0.2 µA/V

Ripple Current

< 3 µA

Isolation

500 VAC

Stability

1 µA/°C

Termination        Standard 

5 way tension clamp connector

Optional

Screw terminals

Voltage Outputs

Voltage Outputs may be obtained by connecting a external resistor and 
selecting the appropriate current range, as shown in the table below.

7.1 PLUG AND PLAY OPTION PODS

RS485 MODBUS Communications 

DM3600 is available with RS485 serial communications using MODBUS RTU protocol, and can be used with
Status’ own M-Config software.

Physical Layer

4 wire or 2 wire half duplex RS485

Protocol

MODBUS RTU format

Breakdown Isolation

500 VAC

Maximum Fan out

32 units (can be increased with repeaters) 

Termination Standard  

RS485

The DM3600 is configured using the three keys on the front panel. The unit has two modes of operation:

The first is ‘Run’ mode. This will automatically be entered 5 s after power up. This is the principle mode
of operation. There are 6 possible key press combinations, as shown in the ‘Key Press Definitions’ diagram
below. The ‘Run Mode Options’ diagram shows the key presses required to access various states from the
run mode. (See diagram in Section 8.2 overleaf).

The other principle mode of operation is ‘Menu Mode’. The menu navigation method is shown diagrammatically
in the ‘General Menu Structure’ (see Section 9.1).

Once the menu mode has been accessed, the user can use the large ‘Menu Map’ (see Section 10.0) to 
navigate through the menu structure. 

All programming is done using the three front panel keys, A, B and C.

ESCAPE (A & B), ENTER (B & C) and CLEAR (A & C) are obtained by simultaneously pressing the two keys.

CYCLE (A), SHIFT (B) and INC (C) keys are pressed singularly. 

7.2 COMMUNICATIONS OPTION

RESISTOR

CURRENT RANGE

OUTPUT

1 K

(0 to 10) mA

(0 to 10) V

500 

(0 to 20) mA

(0 to 10) V

250 

(4 to 20) mA

(1 to 5) V

8.0 INSTRUMENT CONFIGURATION

8.1 KEY PRESS DEFINITIONS

CYCLE

SHIFT

INC

ESCAPE

ENTER

CLEAR

B

C

A

B

B

C

A

C

A

CONNECTIONS

Input
Comms + Digitals

5 way tension clamp connector (2 part)
8 way RJ45 (Supplied with matching plug and 1 m cable)

Communications option fitted

Summary of Contents for DM3600U

Page 1: ...RESETTING THE DEVICE 13 12 0 INPUT MENU STRUCTURE 14 17 13 0 OUTPUT MENU STRUCTURE 18 20 14 0 SYSTEM MENU STRUCTURE 21 22 15 0 FAULT FINDING 23 Status Instruments Ltd Status Business Park Tewkesbury Glos GL20 8FD Tel 44 0 1684 296818 Fax 44 0 1684 293746 Email sales status co uk Web www status co uk 52 314 2367 02 Issue Web 4 DM3600U INDEX Single Channel Universal Input 6 Digit Indicator Important...

Page 2: ...ion to an installation over voltage Category II supply pollution degree 2 The supply voltage and frequency must remain within the limits stated on the product label The mains supply to the unit must be protected by an external 1 A fuse and a suitable switch or circuit breaker must be located close to the equipment in order to isolate the supply SIGNAL INPUT OUTPUTS All signal input and communicati...

Page 3: ...rt conductor tail sufficiently into 2 then release screwdriver Ensure no loose wire strands protrude Page 4 Power must be removed from unit before adding removing a pod Slot 1 alarm 1A and 1B should be positioned on the left side of the unit looking from the front to correspond to front panel alarm indicator Slot 2 alarm 2A and 2B is positioned on the right To install an Option Pod slide back the ...

Page 4: ...lease contact your supplier When fitted this option provides the user with either 4 or 2 wire RS485 serial communications together two digital inputs Connections are made via a RJ45 connector A 0 5 m interface is supplied with this Page 5 Page 6 Material ABS PC Flammability IEC707 FV0 UL 94VO Weight 230 g Panel cut out 92 x 45 mm 1 2 3 4 5 R Load 1 2 3 4 5 V R Load Max RLoad 1 K 4 3 ISOLATED 4 TO ...

Page 5: ...tom 999 to 9999 Accuracy Linearisation Cold Junction Error Cold Junction Tracking Cold Junction Range 0 04 FS 0 04 reading or 0 5 C whichever is greater BS 4937 IEC 584 3 Custom 0 5 C 0 05 C C 20 to 60 C Thermal Drift Zero 4 uV C Span 0 02 C VOLTAGE INPUT Basic Accuracy 0 04 FS 0 04 of reading Thermal Drift 0 01 C Input Impedance 1 MΩ Linearity Linear X X 3 2 X 5 2 Custom Range 100 mV 1 V 5 V 10 V...

Page 6: ...ODBUS RTU protocol and can be used with Status own M Config software Physical Layer 4 wire or 2 wire half duplex RS485 Protocol MODBUS RTU format Breakdown Isolation 500 VAC Maximum Fan out 32 units can be increased with repeaters Termination Standard RS485 The DM3600 is configured using the three keys on the front panel The unit has two modes of operation The first is Run mode This will automatic...

Page 7: ...If enabled this gives access to the relevant alarm setpoints To revert to Run mode press these keys up to 4 times Show electrical value e g 4 to 20 mA input Shows secondary value i e total or rate If enabled this will clear total and or latched alarms Perform clear function Show upper 6 digits of Total RUN MODE RATE OR TOTAL DISPLAYED Edit setpoints menu shortcut Followed by Enter menu mode 8 2 RU...

Page 8: ...nge 10 10 V 1 1 V 5 5 V 1 5 1 to 5 V 4 2 20 4 to 20 mA 20 0 to 20 mA 10 0 to 10 mA 0 1 100 mV Displayed if VOLTAGE input is selected Displayed if CURRENT input is selected Lin Linearisation type nOnE None Linear S9rOOt Square root rOOt32 Power 3 2 rOOt52 Power 5 2 USEr User defined Pt100 Pt100 European Ni 120 Ni120 CA K Current Voltage JISC Pt100 USA Japanese USEr User defined RTD J J t T r R S S ...

Page 9: ...the input to the relevant input_lo and input_hi values see table overleaf for input_lo hi values The PV_lo PV_hi values shown overleaf equate to the En9LO and En9Hi entries Scaling is subsequently applied according to the graph overleaf The straight line illustrated overleaf will change if a non linear linearity type is selected If the user requires strict control over out of range limits user lin...

Page 10: ...RTD input type is chosen 13 0 OUTPUT MENU STRUCTURE Page 17 Page 18 DELAyA Alarm delay dEUA Deviation Enter value Enter value Enter value in seconds Enter value HI High dEUIAt Deviation tESt Test dISAbL Disable nonInU Non inverting InUErt Inverting RELAY OUTPUT MENU OUt 1 Output 1 OUt 2 Output 2 off Off lo Low enable Enable SEtPA Setpoint RE TRANSMISSION mA OUTPUT MENU rEtrAn mA Output scaled to r...

Page 11: ...OINT A The setpoint value defines the engineering value associated with an alarm For example if an alarm is required when the flow exceeds 10 000 kg h the setpoint will be set to 10 000 ALARM ACTION This defines the behaviour of the alarm when the setpoint is reached HYSTERISIS The hysterisis value is the difference between the points at which the alarm triggers and releases expressed in the relev...

Page 12: ...MENU ACCESS PASSCODE When accessing the menus from Run mode the user is prompted for this passcode If it is zero default then there is no prompt and the password function is disabled If the password is forgotten please contact your supplier USER OFFSET This value is used to offset the scaled process variable by a fixed amount MENU TIME OUT This sets the amount of time after which the display will ...

Page 13: ...HOWS DISPLAY SHOWS DP Err IS DISPLAYED OP CAL IS DISPLAYED IP CAL IS DISPLAYED POSSIBLE CAUSE No power Input is out of range above maximum Input is out of range below minimum The displayed value excluding total is greater than 6 digits i e 999999 The output pod has been corrupted The input calibrated data has been corrupted ACTION Check power supply connections Check that the engineering high valu...

Reviews: