background image

Page 3

The Power supply rating will be indicated on the top of the instrument, 

ENSURE IT IS CORRECT FOR THE

APPLICATION.

THE MAINS SUPPLY TO THE EQUIPMENT MUST BE PROTECTED BY AN EXTERNAL 1 A FUSE AND A
SUITABLE SWITCH OR CIRCUIT BREAKER WHICH SHOULD BE NEAR THE EQUIPMENT.

NOTE: USE 600 VRMS CABLE (0.5 TO 1.5) mm

²

.

Wires are retained by screws.  Ensure that the exposed section of the wire is fully inserted and that no
loose strands are exposed.

All sensor connections are made via the five way "fast wiring" socket at the rear of the unit (wire size
(0.5 to 1.5) mm²).

NOTE: THERMOCOUPLE, RTD AND VOLTAGE INPUT A SCREENED CABLE IS RECOMMENDED FOR RUNS
GREATER THAN 10 m.

To make a connection: Insert small screwdriver blade into tension clamp orifice 

(1),

push and twist to

deflect clamp into open position. Do not lever screwdriver thus forcing connector body sideways. Insert
conductor tail sufficiently into 

(2)

then release screwdriver.  Ensure no loose wire strands protrude.

Page 4

Power must be removed from unit before adding/removing a pod. Slot 1 (alarm 1A and 1B) should be 
positioned on the left side of the unit looking from the front to correspond to front panel alarm indicator,
Slot 2 (alarm 2A and 2B) is positioned on the right.

To install an Option Pod, slide back the cover to its next engaging position and push the pod connection
within the mating connector. To remove an Option Pod, disengage the supporting latch situated beneath
the pod by pushing the back cover forward, the pod can then be lifted away from the instrument connector.

The relay pod has two "change over"relays with a common wiper.

NOTE: USE 600 VRMS CABLE (0.5 TO 1.5) mm

²

NOTE: ANY CIRCUIT WITH AN AC POTENTIAL GREATER THAN 33 VRMS AND 46.7 V PEAK MUST BE 
PROTECTED WITH A 5 A(T) FUSE WHEN CONNECTED TO THIS POD.

3.3 POWER SUPPLY

3.4 SENSOR CONNECTIONS

4.0 OPTION PODS

(+) L N (-)

1
2

1

2

3

4

5

NO

NC

WIPE

R

NO

NC

4.1 INSTALLING PODS

4.2 DUAL RELAY POD. POD-3000/02000000

Summary of Contents for DM3600U

Page 1: ...RESETTING THE DEVICE 13 12 0 INPUT MENU STRUCTURE 14 17 13 0 OUTPUT MENU STRUCTURE 18 20 14 0 SYSTEM MENU STRUCTURE 21 22 15 0 FAULT FINDING 23 Status Instruments Ltd Status Business Park Tewkesbury Glos GL20 8FD Tel 44 0 1684 296818 Fax 44 0 1684 293746 Email sales status co uk Web www status co uk 52 314 2367 02 Issue Web 4 DM3600U INDEX Single Channel Universal Input 6 Digit Indicator Important...

Page 2: ...ion to an installation over voltage Category II supply pollution degree 2 The supply voltage and frequency must remain within the limits stated on the product label The mains supply to the unit must be protected by an external 1 A fuse and a suitable switch or circuit breaker must be located close to the equipment in order to isolate the supply SIGNAL INPUT OUTPUTS All signal input and communicati...

Page 3: ...rt conductor tail sufficiently into 2 then release screwdriver Ensure no loose wire strands protrude Page 4 Power must be removed from unit before adding removing a pod Slot 1 alarm 1A and 1B should be positioned on the left side of the unit looking from the front to correspond to front panel alarm indicator Slot 2 alarm 2A and 2B is positioned on the right To install an Option Pod slide back the ...

Page 4: ...lease contact your supplier When fitted this option provides the user with either 4 or 2 wire RS485 serial communications together two digital inputs Connections are made via a RJ45 connector A 0 5 m interface is supplied with this Page 5 Page 6 Material ABS PC Flammability IEC707 FV0 UL 94VO Weight 230 g Panel cut out 92 x 45 mm 1 2 3 4 5 R Load 1 2 3 4 5 V R Load Max RLoad 1 K 4 3 ISOLATED 4 TO ...

Page 5: ...tom 999 to 9999 Accuracy Linearisation Cold Junction Error Cold Junction Tracking Cold Junction Range 0 04 FS 0 04 reading or 0 5 C whichever is greater BS 4937 IEC 584 3 Custom 0 5 C 0 05 C C 20 to 60 C Thermal Drift Zero 4 uV C Span 0 02 C VOLTAGE INPUT Basic Accuracy 0 04 FS 0 04 of reading Thermal Drift 0 01 C Input Impedance 1 MΩ Linearity Linear X X 3 2 X 5 2 Custom Range 100 mV 1 V 5 V 10 V...

Page 6: ...ODBUS RTU protocol and can be used with Status own M Config software Physical Layer 4 wire or 2 wire half duplex RS485 Protocol MODBUS RTU format Breakdown Isolation 500 VAC Maximum Fan out 32 units can be increased with repeaters Termination Standard RS485 The DM3600 is configured using the three keys on the front panel The unit has two modes of operation The first is Run mode This will automatic...

Page 7: ...If enabled this gives access to the relevant alarm setpoints To revert to Run mode press these keys up to 4 times Show electrical value e g 4 to 20 mA input Shows secondary value i e total or rate If enabled this will clear total and or latched alarms Perform clear function Show upper 6 digits of Total RUN MODE RATE OR TOTAL DISPLAYED Edit setpoints menu shortcut Followed by Enter menu mode 8 2 RU...

Page 8: ...nge 10 10 V 1 1 V 5 5 V 1 5 1 to 5 V 4 2 20 4 to 20 mA 20 0 to 20 mA 10 0 to 10 mA 0 1 100 mV Displayed if VOLTAGE input is selected Displayed if CURRENT input is selected Lin Linearisation type nOnE None Linear S9rOOt Square root rOOt32 Power 3 2 rOOt52 Power 5 2 USEr User defined Pt100 Pt100 European Ni 120 Ni120 CA K Current Voltage JISC Pt100 USA Japanese USEr User defined RTD J J t T r R S S ...

Page 9: ...the input to the relevant input_lo and input_hi values see table overleaf for input_lo hi values The PV_lo PV_hi values shown overleaf equate to the En9LO and En9Hi entries Scaling is subsequently applied according to the graph overleaf The straight line illustrated overleaf will change if a non linear linearity type is selected If the user requires strict control over out of range limits user lin...

Page 10: ...RTD input type is chosen 13 0 OUTPUT MENU STRUCTURE Page 17 Page 18 DELAyA Alarm delay dEUA Deviation Enter value Enter value Enter value in seconds Enter value HI High dEUIAt Deviation tESt Test dISAbL Disable nonInU Non inverting InUErt Inverting RELAY OUTPUT MENU OUt 1 Output 1 OUt 2 Output 2 off Off lo Low enable Enable SEtPA Setpoint RE TRANSMISSION mA OUTPUT MENU rEtrAn mA Output scaled to r...

Page 11: ...OINT A The setpoint value defines the engineering value associated with an alarm For example if an alarm is required when the flow exceeds 10 000 kg h the setpoint will be set to 10 000 ALARM ACTION This defines the behaviour of the alarm when the setpoint is reached HYSTERISIS The hysterisis value is the difference between the points at which the alarm triggers and releases expressed in the relev...

Page 12: ...MENU ACCESS PASSCODE When accessing the menus from Run mode the user is prompted for this passcode If it is zero default then there is no prompt and the password function is disabled If the password is forgotten please contact your supplier USER OFFSET This value is used to offset the scaled process variable by a fixed amount MENU TIME OUT This sets the amount of time after which the display will ...

Page 13: ...HOWS DISPLAY SHOWS DP Err IS DISPLAYED OP CAL IS DISPLAYED IP CAL IS DISPLAYED POSSIBLE CAUSE No power Input is out of range above maximum Input is out of range below minimum The displayed value excluding total is greater than 6 digits i e 999999 The output pod has been corrupted The input calibrated data has been corrupted ACTION Check power supply connections Check that the engineering high valu...

Reviews: