background image

0

IMPORTANT

The vent system must terminate so that proper clearances are maintained 

as cited in local codes or the current editions of the National Fuel Gas Code, 

ANSI Z223.1/NFPA 54 or the Natural Gas and Propane Installation Code, 
CAN/CSA-B149.1.

Do not terminate the exhaust vent terminal over public area where condensate 

or vapor can cause nuisance or hazard.

Plan the vent system layout so that proper clearances are maintained from 

plumbing and wiring.

Vent pipes serving power vented appliances are classified by building codes 

as "vent connectors". Required clearances from combustible materials must 

be provided in accordance with information in this manual under LOCATION 

OF HEATER and CLEARANCES, and with National Fuel Gas Code and 

local Codes.

IMPORTANT

Plan the layout of the vent system backwards from the vent termination to 

the appliance. 

 WARNING

USE  ONLY  THE  VENT  TERMINALS  SUPPLIED  WITH  THIS  UNIT. 

TERMINATION  OF A  VENT  SYSTEM  WITH A  DEVICE  OTHER THAN 

THE  SUPPLIED  VENT  TERMINATIONS  WILL  AFFECT  SYSTEM 

PERFORMANCE AND RESULT IN A SAFETY HAZARD.

DIRECT  VENTING

The air intake provided on the unit contains a mesh screen (see Figure 7) 

to prevent large particles from entering the unit.

FIGURE  7.

 WARNING

WHEN THE  UNIT  IS TO  BE  SETUP AS A  DIRECT  VENT, THE  MESH 

SCREEN  MUST BE REMOVED. THE INLET VENT PIPE MAY THEN BE 

GLUED TO THE AIR INTAKE (see Figure 8) PROVIDED ON THE UNIT.

DIRECT VENT TERMINAL INSTALLATION

IMPORTANT

THIS UNIT CONSISTS OF TWO VENT TERMINALS - AN INTAKE VENT 

TERMINAL AND AN  EXHAUST  VENT TERMINAL. THE  INTAKE  VENT 

TERMINAL IS A 3" 45° PVC ELBOW WITH A DOME MESH WIRE SCREEN 

AND THE EXHAUST VENT TERMINAL IS A 3"  45°PVC ELBOW WITH A 

MESH WIRE SCREEN.

NOTE: TO PREVENT EXHAUSTING PRODUCTS FROM CIRCULATING TO 

THE AIR INTAKE IN WINDY/COLD AREAS, THE MAXIMUM PRACTICAL 

DISTANCE BETWEEN THESE TWO TERMINALS IS RECOMMENDED

FIGURE  8.

IMPORTANT

WHEN LOCATING THE TERMINALS ON A SIDEWALL, THE FOLLOWING 

SPECIFICATIONS  PERTAINING TO TERMINAL  LOCATION  MUST  BE 
FOLLOWED.

1.  The intake vent terminal and the exhaust vent terminal must terminate on 

the same exterior wall and must be located at a minimum of 24" (61cm) 

from the vertical centerline of the exhaust vent terminal (see Figure 9).  In 

colder climates increasing the 24" (61cm) minimum will reduce possibility 

of frost over from side winds blowing exhaust vapors to the air intake of 

the direct vent.  

2.  The horizontal centerline of the intake vent terminal may not be located 

lower  than  the  horizontal  centerline  of  the  exhaust  vent  terminal 

 

(see Figure 9).

INSTALLATION SEQUENCE

For installations in the City of Los Angeles, California Category IV PVC Pipe 
such as that manufactured by Brownline Pipe Company, must be used as 
vent pipe material

 CAUTION

Vent terminals supplied with the heater must be used.

NOTE:  BEFORE BEGINNING INSTALLATION OF ANY VENT PIPE READ 

THE VENT PIPE MANUFACTURER'S INSTALLATION INSTRUCTIONS.

1.  After the points of termination have been determined, use the cover plates 

as templates to mark the holes for the vent pipes to be inserted through 

the wall.  BEWARE OF CONCEALED WIRING AND PIPING INSIDE OF 

WALL.

2.  If the vent terminals are being installed on the outside of a finished wall, it 

may be easier to mark both the inside and outside wall. Align the holes by 

drilling a hole through the center of the template from the inside through 

to the outside. The template can now be positioned on the outside wall 

using the drilled holes as a centering point for the template.

3.  A) MASONRY SIDE WALLS

  Chisel an opening approximately 1/2" (1.3 cm) larger than the marked 

circle.

  B) WOODEN SIDE WALLS

  Drill a pilot hole approximately one quarter inch outside of the marked 

circle. This pilot hole is used as a starting point for a saws-all or sabre saw 

blade. Cut around the marked circle staying approximately one quarter 

inch outside of the line. (This will allow the vent pipe to easily slide through 

the opening. The resulting gap will be covered by the vent terminal cover 

plates.) Repeat this step on the inside wall if necessary.

4.  Cut a length of 3" PVC pipe about 3.5" (8.9 cm) longer than the wall

 

thickness at the opening.

FOR ALL 

MODELS

Summary of Contents for SUF 120

Page 1: ...ERVICE MAINTENANCE LIMITED WARRANTY WARNING If the information in these instructions is not followed exactly a fire or explosion may result causing property damage personal injury or death Do not stor...

Page 2: ...Natural Gas and Propane Installation Code and CSA C22 1 the Canadian Electrical Code All documents are available from the Canadian Standards Association 8501 East Pleasant Valley Road Cleveland OH 441...

Page 3: ...RATURE CONTROL TABLE OF CONTENTS ROUGH IN DIMENSIONS 2 FOREWORD 2 FEATURES 3 4 Water Temperature Control 3 High Limit Switch E C O 4 Dishwashing Machine Requirement 4 Circulating Pump 5 INSTALLATION I...

Page 4: ...w pressures above 25 pounds per square inch 173 Kpa or below 15 pounds per square inch 103 Kpa will result in improperly sanitized dishes Where pressures are high a water pressure reducing or flow reg...

Page 5: ...sometimes installed in locations where leakage may result in property damage even with the use of a drain pan piped to a drain However unanticipated damage can be reduced or prevented by a leak detect...

Page 6: ...BER ISOLATION PIPE HANGERS ARE USED THIS PREVENTS ANY VIBRATIONS FROM BEING TRANSMITTED INTO THE LIVING SPACES HARD WATER Where hard water conditions exist water softening or the threshold type of wat...

Page 7: ...tally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS INSPECTION The st...

Page 8: ...S POWER VENT CANADIAN POWER VENT FIGURE 5b CAUTION TO PREVENT EXHAUSTING PRODUCTS FROM CIRCULATING TO THE AIR INTAKE IN WINDY COLD AREAS THE MAXIMUM PRACTICAL DISTANCE BETWEEN THESE TWO TERMINALS IS...

Page 9: ...S DIRECT VENT CANADIAN DIRECT VENT FIGURE 6b CAUTION TO PREVENT EXHAUSTING PRODUCTS FROM CIRCULATING TO THE AIR INTAKE IN WINDY COLD AREAS THE MAXIMUM PRACTICAL DISTANCE BETWEEN THESE TWO TERMINALS IS...

Page 10: ...LOCATION MUST BE FOLLOWED 1 The intake vent terminal and the exhaust vent terminal must terminate on the same exterior wall and must be located at a minimum of 24 61cm from the vertical centerline of...

Page 11: ...the same side of roof 4 The center line of the intake vent termination and the center line of the exhaust vent termination must be no closer than 24 61cm 5 The intake vent terminal and the exhaust ve...

Page 12: ...or ABS cement to join PVC or CPVC pipe and fittings SAFETY PRECAUTION PRIMERS AND CEMENTS ARE EXTREMELY FLAMMABLE AND MUST NOT BE STORED OR USED NEAR HEAT OR OPEN FLAME ALSO USE ONLY IN A WELL VENTILA...

Page 13: ...s that the electrical contacts on this air flow switch be open before it will allow the blower to come on BLOCKED OUTLET PROVER SWITCH SEE FIGURE 12 The Blocked Outlet Prover Switch is set up to shut...

Page 14: ...NGCONDITIONS INSTALLINACCORDANCE WITH RECOMMENDATIONS OF SERVING GAS SUPPLIERS REFER TO THE NATIONAL FUEL GAS CODE FIGURE 13 CONNECTION OF GAS PIPE 1 When connecting gas pipe to unit apply wrench to f...

Page 15: ...VE This heater is equipped with an approved temperature and pressure relief valve ASME ratings cover pressure relief CSA ratings cover release rate with temperature actuation FOR SAFE OPERATION OF THE...

Page 16: ...upply Voltage is reversed the controller will not sense flame Verify polarity before connecting the unit 3 This unit may never be connected to any existing heating system or component s previously use...

Page 17: ...y the desktop screen if there are no active faults or warnings An example of this screen is shown to the right The first temperature on this screen is the temperature of the water inside the tank The...

Page 18: ...u DISPLAY ACTION From the Main Menu press Select to enter the Temperatures screen DISPLAY 2 Operating States In the main desktop screen there are some specific Operating States that are indicated on t...

Page 19: ...an occur during operation These are Warnings and Faults Warnings This is a non safety related condition that the control has detected that may cause the water heater to operate in a less than optimal...

Page 20: ...tion about the water heater and the current status of specific conditions can be found INSTALLATION OR SERVICE OF THIS WATER HEATER REQUIRES ABILITY EQUIVALENT TO THAT OF A LICENSED TRADESMAN IN THE F...

Page 21: ...let pressures confirmed simply turn the switch on and observe operation Cycle the unit off and on several times to ensure proper operation OPERATING INSTRUCTIONS IMPORTANT IT IS RECOMMENDED THAT A QUA...

Page 22: ...able is factory set to cutout at 202 F 94 C The controller must be manually reset by depressing the reset button on front of the control when water temperature drops to below 160 F 71 C TABLE 4 HIGH A...

Page 23: ...23 FOR YOUR SAFETY READ BEFORE OPERATING WARNING If you do not follow these instructions exactly a fire or explosion may result causing property damage personal injury or loss of life 120 MODELS ONLY...

Page 24: ...BEFORE OPERATING WARNING If you do not follow these instructions exactly a fire or explosion may result causing property damage personal injury or loss of life 150 MODELS ONLY OPERATING INSTRUCTIONS T...

Page 25: ...OFF GAS TO APPLIANCE FOR YOUR SAFETY READ BEFORE OPERATING WARNING If you do not follow these instructions exactly a fire or explosion may result causing property damage personal injury or loss of lif...

Page 26: ...rn off the heater electrical disconnect switch 2 Close the cold water inlet valve to heater 3 Open a nearby hot water faucet to vent the system 4 Open the heater drain valve 5 If the heater is being d...

Page 27: ...sly it may be due to thermal expansion of water in a closed water supply system or it may be due to a faulty relief valve Thermal expansion is the normal response of water when it is heated In a close...

Page 28: ...OF WATER IN THE HOT WATER SYSTEM MUST BE PROVIDED NOTE CONNECT RETURN LINE FROM HOT WATER CIRCULATING LOOP IF USED TO COLD WATER INLET LINE PIPE TO OPEN DRAIN INSTALL IN ACCORDANCE WITH LOCAL CODES I...

Page 29: ...PAGE 4 IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT ADD AN ANTI SCALD VALVE FOR HOT WATER SUPPLIED TO FIXTURES CAUTION IF BUILDING COLD WATER SUPPLY HAS A BACK FLOW P...

Page 30: ...TEMPERATURE SETTING SHOULD NOT EXCEED SAFE TEMPERATURE AT FIXTURES SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 4 IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT ADD AN...

Page 31: ...TH LOCAL CODES TWO TEMPERATURE TWO HEATERS ONE PRE HEATER ONE BOOSTER HEATER WITH OR WITHOUT BUILDING RECIRCULATION DANGER TEMPERATURE SETTING SHOULD NOT EXCEED SAFE TEMPERATURE AT FIXTURES SEE WATER...

Page 32: ...HOULD NOT EXCEED SAFE TEMPERATURE AT FIXTURES SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 5 IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT ADD AN ANTI SCALD VALVE FOR...

Page 33: ...nits with the higher water flow may have a shortened life Dimensions shown are for minimum space occupied by the water heaters assemblies Space for the venting system and unit servicing must be added...

Page 34: ...is tightly closed Also check the cleanout opening for leakage 2 The apparent leakage may be condensation which forms on cool surfaces of the heater and piping 3 If the outlet of the relief valve is le...

Page 35: ...g the prepurge portion of the ignition cycle due to the location of the gas orifice MOTOR RUNS BURNER LIGHTS MOMENTARILY THEN LOCKS OUT 1 Reset the appliance two more times to ensure that all of the a...

Page 36: ...heater is or is attempted to be modified or altered in any way including but not limited to by attaching non company approved appliances or equipment 4 SERVICE AND REPAIR EXPENSES Under the limited wa...

Page 37: ...37 NOTES...

Page 38: ...38 NOTES...

Page 39: ...39 NOTES...

Page 40: ...40 500 TENNESSEE WALTZ PARKWAY ASHLAND CITY TN 37015 PHONE 1 800 365 0024 www statewaterheaters com...

Reviews: