background image

20

checKInG Gas Input

With this heater in operation, determine whether it is receiving the 

full rated input of gas. This may be done by timing the gas meter 

and measuring gas pressure with a gauge or manometer. When the 

heater is operating at full capacity (full gas input) it should consume 

approximately 1 cubic foot of gas in the time shown in Table 5.

taBle 5. Input checK tIMe requIred 

to consuMe 1 cu. ft. of Gas

type of Gas

Btu per cu. ft.

approx. time required to 

consume 1 cu. ft. of Gas

Natural Propane

1050 2500

50.3 sec. 119.8 sec.

Use  this  formula  to  “clock”  the  meter.    Be  sure  that  other  gas 

consuming appliances are not operating during this interval.

 

3,600

  X  H  =  Btu/Hr

 

   T

 

T  =  Time in seconds needed to burn one cubic foot of gas.

 

H  =  Heating value of gas in Btu’s per cubic foot of gas.

 

Btu/Hr  =  Actual heater input rate.

 

Example:

 

T  =  50.3 seconds/ft

3

 

H  =  1,050 Btu/ft

3

 (natural gas)

 

Btu/Hr  =  ?

 

3,600

  X  1,050  =  75,100 Btu/Hr (22.0 kW)

 50.3

Compare the actual input rate to that given on the heater’s rating 

plate. In the example, the full input rate should be 75,100 Btu/Hr 

for natural gas.
Because  of  the  suddenness  and  amount  of  water,  condensation 

water may be diagnosed as a “tank leak”. After the water in the tank 

warms up (about 1-2 hours), the condition should disappear.
Do  not  assume  the  water  heater  is  leaking  until  there  has  been 

enough time for the water in the tank to warm up.
An undersized water heater will cause more condensation. The water 

heater must be sized properly to meet the family’s demands for hot 

water including dishwashers, washing machines and shower heads.
Excessive condensation may be noticed during the winter and early 

spring months when incoming water temperatures are at their lowest.
Good venting is essential for a gas fired water heater to operate properly 

as well as to carry away products of combustion and water vapor.

sMoKe/odor

It is not uncommon to experience a small amount of smoke and odor 

during the initial start-up. This is due to burning off of oil from metal 

parts, and will disappear in a short while.

stranGe sounds

Possible noises due to expansion and contraction of some metal 

parts during periods of heat-up and cool-down do not necessarily 

represent harmful or dangerous conditions.
Condensation causes sizzling and popping within the burner area 

during heating and cooling periods and should be considered normal.  

See “Condensation” in this section.

operatIonal condItIons

sMellY water

In each water heater there is installed at least one anode rod (see 

parts  section)  for  corrosion  protection  of  the  tank.  Certain  water 

conditions  will  cause  a  reaction  between  this  rod  and  the  water. 

The most common complaint associated with the anode rod is one 

of a “rotten egg smell” in the hot water. This odor is derived from 

hydrogen sulfide gas dissolved in the water. The smell is the result 

of four factors which must all be present for the odor to develop:
a.  A concentration of sulfate in the supply water.
b.  Little or no dissolved oxygen in the water.
c.  A sulfate reducing bacteria which has accumulated within the 

water heater (this harmless bacteria is nontoxic to humans).

d.  An excess of active hydrogen in the tank.  This is caused by the 

corrosion protective action of the anode.

Smelly water may be eliminated or reduced in some water heater 

models by replacing the anode(s) with one of less active material, 

and  then  chlorinating  the  water  heater  tank  and  all  hot  water 

lines. Contact the local water heater supplier or service agency 

for further information concerning an Anode Replacement Kit and 

this chlorination treatment.
If the smelly water persists after the anode replacement and chlorination 

treatment, we can only suggest that chlorination or aeration of the water 

supply be considered to eliminate the water problem.

do not remove the anode leaving the tank unprotected.  By doing 

so, all warranty on the water heater tank is voided.

“aIr” In hot water faucets

HYDROGEN  GAS:  Hydrogen  gas  can  be  produced  in  a  hot 

water system that has not been used for a long period of time 

(generally  two  weeks  or  more).  Hydrogen  gas  is  extremely 

flammable  and  explosive.  To  prevent  the  possibility  of  injury 

under  these  conditions,  we  recommend  the  hot  water  faucet, 

located  farthest  away,  be  opened  for  several  minutes  before 

any electrical appliances which are connected to the hot water 

system are used (such as a dishwasher or washing machine). If 

hydrogen gas is present, there will probably be an unusual sound 

similar to air escaping through the pipe as the hot water faucet 

is opened. There must be no smoking or open flame near the 

faucet at the time it is open.

hIGh water teMperature shut off sYsteM

This water heater is equipped with an automatic gas Shut-off 

system. This system works when high water temperatures are 

present.  The  high  temperature  Shut-off  is  built  into  the  gas 

control valve.  It is non-resettable. If the high temperature Shut-

off activates, the gas control valve must be replaced. Contact 

your gas supplier or service agency. Turn “OFF” the entire gas 

supply to the water heater.  

Summary of Contents for SBL 100 76N

Page 1: ... safety messages could result in death or serious injury This manual must remain with the water heater Low Lead Content WARNING If the information in these instructions is not followed exactly a fire or explosion may result causing property damage personal injury or death Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF...

Page 2: ... for Confined Spaces 13 Outdoor Air Through Two Openings 13 Outdoor Air Through One Opening 13 Outdoor Air Through Two Horizontal Ducts 14 Outdoor Air Through Two Vertical Ducts 14 Air From Other Indoor Spaces 14 Venting 14 Gas Piping 16 Sediment Traps 17 LIGHTING OPERATING INSTRUCTIONS 18 TEMPERATURE REGULATION 19 FOR YOUR INFORMATION 19 Start Up Conditions 19 Operational Conditions 20 PERIODIC M...

Page 3: ...fornia to cause cancer birth defects or other reproductive harm and requires businesses to warn of potential exposure to such substances WARNING This product contains a chemical known to the State of California to cause cancer birth defects or other reproductive harm This appliance can cause low level exposure to some of the substances listed in the Act DANGER WARNING CAUTION CAUTION DANGER indica...

Page 4: ...4 general safety INFORMATION ...

Page 5: ...u don t follow the safety rules the water heater will not operate properly It could cause DEATH SERIOUS BODILY INJURY AND OR PROPERTY DAMAGE This manual contains instructions for the installation operation and maintenance of the gas fired water heater It also contains warnings throughout the manual that you must read and be aware of All warnings and all instructions are essential to the proper ope...

Page 6: ...in US Gallons hr or Liters hr at Indicated Temperature Rise in Fahrenheit or Celsius 75 100 BTU H F 30 40 50 60 70 80 90 100 110 120 130 140 GPH 246 184 148 123 105 92 82 74 67 62 57 53 22 KW C 17 22 28 33 39 44 50 56 61 67 72 78 LPH 927 695 557 462 397 347 309 278 252 233 214 198 Recovery ratings based on 81 thermal efficiency Units A B C D E F G H J K L M Inches CM 70 1 2 179 07 66 1 2 168 9 30 ...

Page 7: ...icing and proper operation of the water heater Installation of water heater must be accomplished in such a manner that if the tank or any connections should leak flow will not cause damage to the structure For this reason it is not advisable to install water heater in an attic or upper floor When such locations cannot be avoided a suitable metal drain pan should be installed under the water heater...

Page 8: ...esult in improper and inefficient operation of the water heater producing carbon monoxide gas in excess of the safe limits This could result in serious injury or death Contact your local gas supplier for any specific changes that may be required in your area Clearances Minimum clearances between the water heater and combustible construction are 0 inch at the sides and rear 4 102 mm at the front an...

Page 9: ...tain it does not sag thereby obstructing the combustion air flow Hard Water Where hard water conditions exist water softening or the threshold type of water treatment is recommended This will protect the dishwashers coffee urns water heaters water piping and other equipment See the Maintenance Section in this manual for sediment and lime scale removal procedures Circulation Pumps A circulating pum...

Page 10: ...anufacturer s specifications If a positive lock up regulator is required follow these instructions 1 Positive lock up gas pressure regulators must be rated at or above the input Btu hr rating of the water heater they supply 2 Positive lock up gas pressure regulator s should be installed no closer than 3 feet 1 meter and no farther than 8 feet 2 4 meters of equivalent length from the water heater s...

Page 11: ...ef of thermal expansion A properly sized thermal expansion tank must be installed on all closed systems to control the harmful effects of thermal expansion Contact a local plumbing service agency to have a thermal expansion tank installed FIGURE 7 NOTE To protect against untimely corrosion of hot and cold water fittings it is strongly recommended that di electric unions or couplings be installed o...

Page 12: ...rature Pressure Relief Valve discharge line and 2 the water manually discharged will not cause any bodily injury or property damage because the water may be extremely hot If after manually operating the valve it fails to completely reset and continues to release water immediately close the cold water inlet to the water heater follow the draining instructions in this manual and replace the Temperat...

Page 13: ...heater and the risk of fire or explosion may result It can also create a risk of asphyxiation Louvers and Grilles Thefreeareasofthefreshairopeningsintheinstructionsthatfollowdonot takeintoaccountthepresenceoflouvers grillesorscreensintheopenings The required size of openings for combustion ventilation and dilution air shall be based on the net free area of each opening Where the free area through ...

Page 14: ...be provided with two permanent vertical ducts one commencing within 12 inches 300 mm of the top and one commencing within 12 inches 300 mm of the bottom of the enclosure The vertical ducts shall communicate directly with the outdoors See Figure 11 Each duct opening shall have a minimum free area of 1 square inch per 4 000 Btu hr 550 mm2 per kW of the aggregate input rating of all appliances instal...

Page 15: ...ter heater unless it is vented to the outdoors and has adequate air supply to avoid risks of improper operation explosion or asphyxiation Align the legs of the draft hood with the slots provided Insert the legs and secure the draft hood to the water heater s top with the four screws provided as shown in Figure 13 Do not alter the draft hood in any way If you are replacing an existing water heater ...

Page 16: ... IN INCHES MAXIMUM CAPACITY OF PIPE IN CUBIC FEET PER HOUR LENGTH IN FEET NOMINAL IRON PIPE SIZES INCHES INPUT IN THOUSANDS BTU HR 1 2 3 4 1 1 1 4 1 1 2 2 2 1 2 3 4 10 175 360 680 1400 2100 3960 6300 11000 23000 20 120 250 465 950 1460 2750 4360 7700 15800 30 97 200 375 770 1180 2200 3520 6250 12800 40 82 170 320 660 990 1900 3000 5300 10900 50 73 151 285 580 900 1680 2650 4750 9700 60 66 138 260 ...

Page 17: ...tallation shown in the Figures 15 and 16 Contaminants in the gas lines may cause improper operation of the gas control valve that may result in fire or explosion Before attaching the gas line be sure that all gas pipe is clean on the inside To trap any dirt or foreign material in the gas supply line a sediment trap must be incorporated in the piping The sediment trap must be readily accessible Ins...

Page 18: ...fter several tries turn the gas control knob clockwise to OFF and call your service technician or gas supplier SEE FIGURE A DANGER Hotter water increases the risk of scald injury Consult the instruction manual before changing temperature At arm s length away turn gas control knob counterclockwise to ON SEE FIGURE C Set thermostat to desired setting Remove the outer door located below the gas contr...

Page 19: ...or at the water heater Mixing valves are available at plumbing supply or hardware stores see Figure 2 Follow manufacturer s instructions for installation of the valves Before changing the factory setting on the thermostat read the Temperature Regulation section in this manual see Figures 17 and 18 TEMPERATURE REGULATION FOR YOUR INFORMATION appear to be leaking when in fact the water is condensati...

Page 20: ...elly Water In each water heater there is installed at least one anode rod see parts section for corrosion protection of the tank Certain water conditions will cause a reaction between this rod and the water The most common complaint associated with the anode rod is one of a rotten egg smell in the hot water This odor is derived from hydrogen sulfide gas dissolved in the water The smell is the resu...

Page 21: ...eplaced At least once a year a visual inspection should be made of the main burner and pilot burner see Figure 19 Inspect burner fl ames through viewport Flames should be very small with a blue haze and small amounts of yellow or orange at the edges After several minutes of operation the burner screen may glow red You should check for sooting Soot is not normal and will impair proper combustion So...

Page 22: ... life of the equipment but also reduces efficiency of the heater and increases fuel consumption The usage of water softening equipment greatly reduces the hardness of the water However this equipment does not always INSTALLED IN SUITABLE AREA To insure sufficient ventilation and combustion air supply proper clearances from the water heater must be maintained See Locating the New Water Heater secti...

Page 23: ...Remove lime scale or sediment using care not to damage the glass lining 7 Inspect cleanout plate gasket if new gasket is required replace with part no 9004099215 8 Install cleanout plate Be sure to draw plate up tight by tightening screws securely 9 Replace outer jacket cover plate In some water areas the sediment might not be removed by this method and may result in the water heater making rumbli...

Page 24: ...ack on the container and slide 3 4 hose over end of male adapter and fasten in place using hose clamp provided Delime using Flo Jug Method 5 Slide the hose clamp over end of hose and slide hose over the male adapter in the water heater drain opening and secure in place using hose clamp 6 Lift container to the Pour Position see Figure 29 being careful to keep the vent in the handle above the liquid...

Page 25: ...first Then before checking the water heater make sure the gas supply has been turned OFF and never turn the gas ON before the tank is completely full of water Never use this water heater unless it is completely filled with water To prevent damage to the tank the tank must be filled with water Water must flow from the hot water faucet before turning ON gas to the water heater LEAKAGE CHECKPOINTS A ...

Page 26: ...embly and or thermocouple Defective Gas Control Replace Gas Control PILOT OUTAGE Dirty pilot burner Clean pilot assembly Thermocouple malfunction Replace pilot assembly and or thermocouple Defective Gas Control Replace Gas Control Thermocouple tip is not in contact with pilot flame Insert thermocouple correctly NOTENOUGH HOT WATER Heater not lit or thermostat not on Refer to LIGHTING INSTRUCTIONS ...

Page 27: ... govern their usage SINGLE FLUE 1 UNIT LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE TEMPERATURE GAGE WATER FLOW SWITCH CHECK VALVE WARNING THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION AND OTHER DEVICES CHECK WITH LOCAL CODES AND ORDINANCES FOR ADDITIONAL REQUIREMENTS FINISHED FLOOR HO C T OLD COLD EXPANSION...

Page 28: ...rmostat should be set 5 degrees F higher than the Tank Temperature Control SINGLE FLUE 1 UNIT WITH VERTICAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE TEMPERATURE GAGE WATER FLOW SWITCH CHECK VALVE WARNING THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION AND OTHER DEVICES CHECK WITH LOCAL CODES A...

Page 29: ...hermostat should be set 5 degrees F higher than the Tank Temperature Control SINGLE FLUE 1 UNIT WITH HORIZONTAL STORAGE TANK LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE TEMPERATURE GAGE WATER FLOW SWITCH CHECK VALVE WARNING THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION AND OTHER DEVICES CHECK WITH LOCAL COD...

Page 30: ... set 5 degrees F higher than the Tank Temperature Control SINGLE FLUE 1 UNIT WITH MIXING VALVE TWO TEMPERATURE LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE TEMPERATURE GAGE WATER FLOW SWITCH CHECK VALVE WARNING THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION AND OTHER DEVICES CHECK WITH LOCAL CODES AND ORDINAN...

Page 31: ...ter s and the storage tank s SINGLE FLUE 2 UNITS LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE TEMPERATURE GAGE WATER FLOW SWITCH CHECK VALVE WARNING THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION AND OTHER DEVICES CHECK WITH LOCAL CODES AND ORDINANCES FOR ADDITIONAL REQUIREMENTS FINISHED FLOOR HOT WATER TO FI...

Page 32: ...TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP TANK TEMPERATURE CONTROL DRAIN FULL PORT BALL VALVE TEMPERATURE GAGE WATER FLOW SWITCH CHECK VALVE WARNING THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION AND OTHER DEVICES CHECK WITH LOCAL CODES AND ORDINANCES FOR ADDITIONAL REQUIREMENTS FINISHED FLOOR HOT WATER TO FIXTURES HOT WATER RETURN HOT HOT COLD HIGH TEMPERATURE RE...

Page 33: ...33 NOTES ...

Page 34: ...34 NOTES ...

Page 35: ...effective method of controlling thermal expansion is also installed at the heater s and operational at all times The relief valve installed on the heater is not an acceptable method 4 SERVICE AND REPAIR EXPENSES Under the limited warranty the warrantor will provide only a replacement water heater or part thereof The owner is responsible for all other costs Such costs may include but are not limite...

Page 36: ...36 500 Tennessee Waltz Parkway Ashland City TN 37015 Phone 800 365 0024 Parts 800 433 2545 Fax 800 644 9306 www statewaterheaters com Copyright 2012 State Water Heaters All rights reserved ...

Reviews: