background image

12

distance below the structural 

fl

 oor.  Be certain that no contact is 

made with any live electrical part.  The discharge opening must 
not be blocked or reduced in size under any circumstances.  
Excessive length, over 30 ft. (9.14m), or use of more than four 
elbows can cause restriction and reduce the discharge capacity 
of the valve, see Figures 5 or 10.

No valve or other obstruction is to be placed between the relief 
valve and the tank.  Do not connect tubing directly to discharge 
drain unless a 6 in. (152mm) air gap is provided.  To prevent 
bodily injury, hazard to life, or property damage, the relief valve 
must be allowed to discharge water in quantities should circum-
stances demand.  If the discharge pipe is not connected to a 
drain or other suitable means, the water 

fl

 ow may cause property 

damage.

The Discharge Pipe:
•  Shall not be smaller in size than the outlet pipe size of the 

valve, or have any reducing couplings or other restrictions.

•  Shall not be plugged or blocked.
•  Shall be of material listed for hot water distribution.
•  Shall be installed so as to allow complete drainage of both 

the temperature-pressure relief valve, and the discharge 
pipe.

•  Shall terminate at an adequate drain.
•  Shall not have any valve between the relief valve and tank.

The temperature-pressure relief valve must be manually oper-
ated at least once a year.  Caution should be taken to ensure that 
(1) no one is in front of or around the outlet of the temperature-
pressure relief valve discharge line, and (2) the water manually 
discharged will not cause any bodily injury or property damage 
because the water may be extremely hot.

If after manually operating the valve, it fails to completely reset 
and continues to release water, immediately close the cold water 
inlet to the water heater, follow the draining instructions, and re-
place the temperature-pressure relief valve with a new one.

WATER (POTABLE) HEATING AND SPACE HEATING

1.  All piping components connected to this unit for space heating 

applications shall be suitable for use with potable water.

2. Toxic chemicals, such as those used for boiler treatment, 

shall NEVER be introduced into this system.

3.  This unit may NEVER be connected to any existing heating 

system or component(s) previously used with a non-potable 
water heating appliance.

4. When the system requires water for space heating at 

temperatures higher than required for domestic water 
purposes, a tempering valve must be installed, see Figure 7 
for suggested piping arrangement.

FIGURE 7

CLOSED WATER SYSTEM

A closed system will exist if a back-

fl

 ow preventer (check valve), 

pressure reducing valve, or other similar device is installed in 
the cold water line between the water heater and the street main 
(or well).  Excessive pressure may develop due to the thermal 
expansion of heated water causing premature tank failure or 
intermittent relief valve operation.  This type of failure is not 
covered by the limited warranty.  An expansion tank may be 
necessary in the cold water supply to alleviate this situation, see 
Figure 1.  Contact the local plumbing authority.
If the temperature and pressure relief valve on the appliance 
discharges periodically, this may be due to thermal expansion 
in a closed water supply system.  Contact the water supplier or 
local plumbing inspector on how to correct this situation.  DO 
NOT PLUG THE TEMPERATURE AND PRESSURE RELIEF 
VALVE.

GAS PIPING

Make sure the gas supplied is the same type listed on the model 
rating plate.  The inlet gas pressure must not exceed 14 inch  
water column (3.5 kPa) for natural and propane gas (L.P.).  The 

Summary of Contents for 186589-001

Page 1: ...N ODORANT IS ADDED TO THE GAS USED BY THIS WATER HEATER GAMA certification applies to all residential gas water heat ers with capacities of 20 to 100 gallons with input rating of 75 000 BTU Hr or less A Brand of State Industries Inc Ashland City TN 37015 www statewaterheaters com ALL TECHNICAL AND WARRANTY QUESTIONS SHOULD BE DIRECTED TO THE LOCAL DEALER FROM WHOM THE WATER HEATER WAS PURCHASED IF...

Page 2: ...NT DEFINITIONS Qualified Installer A qualified installer must have ability equivalent to a licensed tradesman in the fields of plumbing air supply venting and gas supply including a thorough understanding of the requirements of the National Fuel Gas Code as it relates to the installation of gas fired water heaters The qualified installer must also be familiar with the design features and use of fl...

Page 3: ...3 GENERAL SAFETY ...

Page 4: ...Mechanical Engineers GAMA Gas Appliance Manufacturer s Association UL Underwriters Laboratories Inc This gas fired water heater is design certified by Underwriters Laboratories Inc under American National Standard CSA Stan dard for Gas Water Heaters ANSI Z21 10 1 CSA 4 1 current edition PREPARING FOR THE INSTALLATION 1 Read the General Safety section page 3 of this manual first and then the entire...

Page 5: ...ntally vented gas fueled heating appli ance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS INSPECTION The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless upon inspection the inspector observes carbon monoxide detectors and si...

Page 6: ...LOCAL CODES THERMAL EXPANSION TANK INSTALLTHERMALEXPANSION TANK IF WATER HEATER IS INSTALLED IN A CLOSED SYSTEM GAS CONTROL TYPICAL INSTALLATION FLUE BAFFLE GAS SUPPLY LINE MAIN MANUAL GAS SHUTOFF VALVE GROUND JOINT UNION DIRT LEG ANODE HOT WATER OUTLET PIPE UNION INLET DIP TUBE TEMPERATURE AND PRESSURE RELIEF VALVE DISCHARGE PIPE DO NOT CAP OR PLUG WATER TEMPERATURE ADJUSTING DIAL DRAIN VALVE DRA...

Page 7: ...the hot water tap then you must take special precautions In addition to using the lowest possible temperature setting that satisfies your hot water needs a means such as a Mixing Valve should be used at the hot water taps used by these people or at the water heater Mix ing valves are available at plumbing supply or hardware stores Consult a Qualified Installer or Service Agency Follow mixing valve...

Page 8: ...Water heater life depends upon water quality water pressure and the environment in which the water heater is installed Water heaters are sometimes installed in locations where leakage may result in property damage even with the use of a drain pan piped to a drain However unanticipated damage can be reduced or prevented by a leak detector or water shut off device used in conjunction with a piped dr...

Page 9: ...ATION FOR APPLIANCES LOCATED IN CONFINED SPACES FIGURE 3 Confined Space is a space whose volume is less than 50 cubic feet per 1 000 Btu per hour 4 8 cm per kW of the aggregate input rating of all appliances installed in that space VENT TERMINATION Before installing water heater determine placement of vent ter mination Make certain to observe vent location limitation see Figures 3 4 12 Minimum cle...

Page 10: ... heating systems or component s used with a non potable water heating appli ance All piping components connected to this unit for space heating applications shall be suitable for use with potable water Toxic chemicals such as those used for boiler treatment shall not be introduced into this system When the system requires water for space heating at tem peratures higher than required for domestic w...

Page 11: ... TEMPERATURE PRESSURE RELIEF VALVE This heater is provided with a properly certified combination temperature pressure relief valve by the manufacturer The valve is certified by a nationally recognized testing labora tory that maintains periodic inspection of production of listed equipment of materials as meeting the requirements for Relief Valves for Hot Water Supply Systems ANSI Z21 22 CSA 4 4 an...

Page 12: ...and continues to release water immediately close the cold water inlet to the water heater follow the draining instructions and re place the temperature pressure relief valve with a new one WATER POTABLE HEATING AND SPACE HEATING 1 All piping components connected to this unit for space heating applications shall be suitable for use with potable water 2 Toxic chemicals such as those used for boiler ...

Page 13: ...y solution and wipe dry Wheninstalledatelevationsabove7 700feet 2 347meters input rating should be reduced at the rate of 4 percent for each 1 000 feet 305 meters above sea level which requires replacement of the burner orifice in accordance with National Fuel Gas Code ANSI Z223 1 NFPA 54 Contact your local gas supplier for further information Failure to replace the standard orifice with a high al...

Page 14: ... must be filled with water Water must flow from the hot water faucet before turning ON gas to the water heater To fill the water heater with water 1 Close the water heater drain valve by turning the handle clockwise The drain valve is on the lower front of the water heater 2 Open the cold water supply valve to the water heater NOTE The cold water supply valve must be left open when the water heate...

Page 15: ...bove if within 10 ft 3 m horizontally to a mechanical air supply inlet Minimum 12 in 30 cm from sides above or below a permanently closed window or door Minimum 7 ft 2 3 m above public sidewalk or paved driveway see footnote 2 Minimum 9 in 23 cm for appliances with 10 000 btuh 3 Kw to 50 000 btuh 15 Kw inputs and 12 in 30 cm for appliances greater than 50 000 btuh 15 Kw to a non mechanical air sup...

Page 16: ... gal Hi Input and 75 gal models as measured from the hole center to bottom of water heater The maximum height recommended is 80 in 2 03m or in compliance with Figure 16 Where the wall is combustible and the wall thickness is over 14 in 356mm 1 in 25mm clearance to combustible materials around the vent terminal is needed The first 14 in 356mm is zero clearance 7 in 178mm DIAMETER BOTTOM OF HEATER S...

Page 17: ...unction of the outer corrugated tube and the trim plate inside with suitable sealant SEALANT TRIM PLATE INSIDE TRIM PLATE OUTSIDE FIGURE 19 UNCOMPRESSING THE CORRUGATED TUBING 1 Pull the inner corrugated tube towards the water heater and leave some length over the water heater s center for bending 2 Pull the outer corrugated tube toward the water heater and leave it 1 in 25mm shorter than the inne...

Page 18: ... corrugated tube TOP VIEW 90 MAXIMUM BEND FIGURE 26 CONDITION 2 Where floor joists impede venting a rise or drop to complete the vent termination is possible All installations require 1 in 25mm clearance to combustibles Note A The maximum horizontal vent length of 80 in 2 03m minus wall thickness should be considered when installing an offset vent arrangement B Do not combine condition 1 Figure 26...

Page 19: ...y call your service technician or gas supplier If the pilot will not stay lit after several tries turn the gas control knob clockwise to OFF and call your service technician or gas supplier SEE FIGURE A 11 Once the pilot flame is established replace the outer burner door 12 At arm s length away turn gas control knob counterclockwise to ON SEE FIGURE C 13 Set thermostat to desired setting DANGER Ho...

Page 20: ... by small hot water uses can cause temperatures at the point of use to exceed the thermostat setting by up to 30 F 17 C If you experience this type of use you should consider using lower temperature settings to reduce scald hazards Valves for reducing point of use temperature by mixing cold and hot water are available see Figures 2 7 Also available are inexpensive devices that attach to faucets to...

Page 21: ...e effects of water hammer among others have installed devices such as pressure reducing valves check valves back flow preventers etc to control these types of problems When these devices are not equipped with an internal by pass and no other measures are taken the devices cause the water system to be closed As water is heated it expands thermal expansion and closed systems do not allow for the exp...

Page 22: ...ossibility of injury under these conditions we recommend the hot water faucet located farthest away be opened for several minutes before any electri cal appliances which are connected to the hot water system are used such as a dishwasher or washing machine If hydrogen gas is present there will probably be an unusual sound similar to air escaping through the pipe as the hot water faucet is opened T...

Page 23: ...ter heater will create dangerous conditions which can cause DEATH SERIOUS BODILY INJURY OR PROPERTY DAM AGE Contact a qualified installer or service agency to replace a flooded water heater Do not attempt to repair the unit It must be replaced At least once a year a visual inspection should be made of the main burner and the pilot assembly for proper flame characteris tics This can be done by remo...

Page 24: ...water to run until it flows clean This will help prevent sediment build up in the tank It is normal for lime and scale deposits to form within the tank Such deposits will not be removed by periodic draining It is necessary to chemically delime the affected parts in water areas where such deposits are encountered Contact your dealer or plumber for deliming information CATHODIC PROTECTION ANODE The ...

Page 25: ...ter heater 2 Follow Draining instructions 3 Turning counterclockwise remove the hex cap below the screw handle 4 Remove the washer and put the new one in place 5 Screw the handle and cap assembly back into the drain valve and retighten using a wrench DO NOT OVER TIGHT EN 6 Follow instructions in the Filling The Water Heater section 7 Check for leaks 8 Follow the lighting instructions in the Lighti...

Page 26: ...g may be leaking anode is located under the Blower Assembly D Small amounts of water from temperature pressure relief valve may be due to thermal expansion or high water pres sure in your area E The temperature pressure relief valve may be leaking at the tank fitting F Water from a drain valve may be due to the valve being slightly opened G The drain valve may be leaking at the tank fitting H Comb...

Page 27: ...h gas utility company 3 Notify utility install dirt trap in gas line 4 Clean locate source and correct 5 Finger tighten then 1 4 turn with wrench 6 Replace thermocouple 7 Locate source and correct 8 Replace gas control thermostat 9 Call a qualified service technician 10 Replace igniter or pilot assembly 11 Replace water heater eliminate flammable vapors source Call a qualified service tech nician ...

Page 28: ...d 3 Heater installed in a confined area 1 Provide ventilation to water heater Check flue way flue baffle burner 2 Clean locate source and correct 3 Provide fresh air ventilation SMOKING AND CARBON FORMATION SOOTING 1 Insufficient secondary air 2 Low gas pressure 3 Flue clogged 4 Defective gas control thermostat 5 Heater installed in a confined area 6 Burner flame yellow lazy 1 Provide ventilation ...

Page 29: ...29 NOTES ...

Page 30: ... the working pres sure shown on the heater filled with potable water free to circulate at all times and with the tank free of damaging water sediment or scale deposits used in a non corrosive and non contaminated atmo sphere used with factory approved anode s installed in its original installation location in the United States its territories or possessions and Canada sized in accordance with prop...

Page 31: ...tz Parkway Ashland City TN 37015 phone 1 800 821 2017 The warrantor will only honor replacement with identical or similar water heater or parts thereof which are manufactured or distributed by the warrantor Dealer replacements are made subject to in warranty valida tion by warrantor PROOF OF PURCHASE AND PROOF OF INSTALLATION DATE ARE REQUIRED TO SUPPORT WARRANTY CLAIM FROM ORIGINAL OWNER THIS FOR...

Page 32: ...32 500 TENNESSEE WALTZ PARKWAY ASHLAND CITY TN 37015 PHONE 800 821 2017 FAX 800 644 9306 www statewaterheaters com ...

Reviews: