background image

23

FOR YOUR INFORMATION

START UP CONDITIONS

CONDENSATE

Whenever the water heater is 

fi

 lled with cold water, some condensate 

will form while the burner is on. A water heater may appear to be leaking 
when in fact the water is condensate. This usually happens when:

a.  A new water heater is 

fi

 lled with cold water for the 

fi

 rst time.

b.  Burning gas produces water vapor in water heaters, particularly 

high ef

fi

 ciency models where 

fl

 ue temperatures are lower.

c.  Large amounts of hot water are used in a short time and the re

fi

 ll 

water in the tank is very cold.

Moisture from the products of combustion condense on the cooler 
tank surfaces and form drops of water which may fall onto the burner 
or other hot surfaces to produce a “sizzling” or “frying” noise.

Because of the suddenness and amount of water, condensate water 
may be diagnosed as a “tank leak”. After the water in the tank warms 
up (about 1-2 hours), the condition should disappear.

Do not assume the water heater is leaking until there has been enough 
time for the water in the tank to warm up.

An undersized water heater will cause more condensation. The water 
heater must be sized properly to meet the family’s demands for hot 
water including dishwashers, washing machines and shower heads.

Excessive condensate may be noticed during the winter and early 
spring months when incoming water temperatures are at their 
lowest.

Good venting is essential for a gas 

fi

 red water heater to operate 

properly as well as to carry away products of combustion and water 
vapor.

SMOKE/ODOR

It is not uncommon to experience a small amount of smoke and odor 
during the initial start-up. This is due to burning off of oil from metal 
parts, and will disappear in a short while.

THERMAL EXPANSION

CLOSED WATER SYSTEMS

Water supply systems may, because of code requirements or such 
conditions as high line pressure, among others, have installed devices 
such as pressure reducing valves, check valves, and back 

fl

 ow preventers. 

Devices such as these cause the water system to be a closed system.

THERMAL EXPANSION

As water is heated, it expands (thermal expansion). In a closed system 
the volume of water will grow. As the volume of water grows there will be 
a corresponding increase in water pressure due to thermal expansion. 
Thermal expansion can cause premature tank failure (leakage). This type 
of failure is not covered under the limited warranty. Thermal expansion 
can also cause intermittent temperature-pressure relief valve operation: 
water discharged from the valve due to excessive pressure build up. The 
temperature-pressure relief valve is not intended for the constant relief 
of thermal expansion. This condition is not covered under the limited 
warranty.

A properly sized thermal expansion tank should be installed on all 
closed systems to control the harmful effects of thermal expansion. 
Contact a local plumbing service agency to have a thermal expansion 
tank installed.

STRANGE SOUNDS

Possible noises due to expansion and contraction of some metal parts 
during periods of heat-up and cool-down do not necessarily represent 
harmful or dangerous conditions.

Condensation causes sizzling and popping within the burner area 
during heating and cooling periods and should be considered normal. 
See “Condensate” in this section.

OPERATIONAL CONDITIONS

SMELLY WATER

In each water heater there is installed at least one anode rod (see parts 
section) for corrosion protection of the tank. Certain water conditions 
will cause a reaction between this rod and the water. The most common 
complaint associated with the anode rod is one of a “rotten egg smell” 
in the hot water. The smell is a result of four factors which must all be 
present for the odor to develop:

a.  A concentration of sulfate in the supply water.
b.  Little or no dissolved oxygen in the water.
c.  A sulfate reducing bacteria which has accumulated within the water 

heater (this harmless bacteria is nontoxic to humans).

d.  An excess of active hydrogen in the tank. This is caused by the 

corrosion protective action of the anode.

Smelly water may be eliminated or reduced in some water heater 
models by replacing the anode(s) with one of less active material, 
and then chlorinating the water heater tank and all water lines. 
Contact the local water heater supplier or service agency for further 
information concerning an Anode Replacement Kit and this chlorination 
treatment.

If the smelly water persists after the anode replacement and chlorination 
treatment, we can only suggest that chlorination or aeration of the 
water supply be considered to eliminate the water problem.

Do not remove the anode leaving the tank unprotected. By doing 
so, all warranty on the water heater tank is voided.

“AIR” IN HOT WATER FAUCETS

HYDROGEN GAS: Hydrogen gas can be produced in a hot water 
system that has not been used for a long period of time (generally 
two weeks or more). Hydrogen gas is extremely 

fl

 ammable  and 

explosive. To prevent the possibility of injury under these conditions, we 
recommend the hot water faucet, located farthest away, be opened for 
several minutes before any electrical appliances which are connected 
to the hot water system are used (such as a dishwasher or washing 
machine). If hydrogen gas is present, there will probably be an unusual 
sound similar to air escaping through the pipe as the hot water faucet 
is opened. There must be no smoking or open 

fl

 ame near the faucet 

at the time it is open.

HIGH WATER TEMPERATURE SHUT OFF SYSTEM

This water heater is equipped with an automatic gas shut-off system. 
This system works when high water temperatures are present. Turn 
“OFF” the entire gas supply to the water heater. The high temperature 
shut-off is built into the gas control valve. It is non-resettable. If the 
high temperature shut-off activates, the gas control valve must be 
replaced. Contact your gas supplier or service agency.

Summary of Contents for 185244-004

Page 1: ...D BE DIRECTED TO THE LOCAL DEALER FROM WHOM THE WATER HEATER WAS PURCHASED IF YOU ARE UNSUCCESSFUL PLEASE WRITE TO THE COMPANY LISTED ON THE RATING PLATE ON THE WATER HEATER RESIDENTIAL GAS WATER HEATERS For Your Safety AN ODORANT IS ADDED TO THE GAS USED BY THIS WATER HEATER GAMA certification applies to all residential gas water heaters with capacities of 20 to 100 gallons with input rating of 7...

Page 2: ...NT DEFINITIONS Qualified Installer A qualified installer must have ability equivalent to a licensed tradesman in the fields of plumbing air supply venting and gas supply including a thorough understanding of the requirements of the National Fuel Gas Code as it relates to the installation of gas fired water heaters The qualified installer must also be familiar with the design features and use of fl...

Page 3: ...3 GENERAL SAFETY ...

Page 4: ...y rules the water heater will not operate properly It could cause DEATH SERIOUS BODILY INJURY AND OR PROPERTY DAMAGE This manual contains instructions for the installation operation and maintenance of the gas fired water heater It also contains warnings throughout the manual that you must read and be aware of All warnings and all instructions are essential to the proper operation of the water heat...

Page 5: ...ntally vented gas fueled heating appli ance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS INSPECTION The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless upon inspection the inspector observes carbon monoxide detectors and si...

Page 6: ...ain Valve X Gas Control Valve Y Drain Pan Z Air Intake Screen Base Pan AA Inner Door B B Outer Door CC HSI Burner Assembly D D Air Intake Screen Blower Assembly E E FV Sensor Bracket Assembly 40K 50K Models Only F F FV Sensor Bracket Assembly 55K 62 5K Models Only NATURAL HOT SURFACE IGNITER MAIN BURNER HOT SURFACE IGNITOR SENSOR PROPANE HOT SURFACE IGNITER MAIN BURNER HOT SURFACE IGNITOR SENSOR C...

Page 7: ... than others These include the elderly children the infirm or physically mentally handicapped If anyone using hot water in your home fits into one of these groups or if there is a local code or state law requiring a certain temperature water at the hot water tap then you must take special precautions In addition to using the lowest possible temperature setting that satisfies your hot water needs a...

Page 8: ...ger an alarm or turn off the incoming water to the water heater when leakage is detected Sensors mounted in the drain pan that turn off the water supply to the entire home when water is detected in the drain pan Water supply shut off devices that activate based on the water pressure differential between the cold water and hot water pipes connected to the water heater Devices that will turn off the...

Page 9: ...exceeds the National Appliance Energy Conversation Act standards with respect to insulation and standby loss requirements making an insulation blanket unnecessary Should you choose to apply an insulation blanket to this heater you should follow these instructions For identification of components mentioned below see Figure 1 Failure to follow these instructions can restrict the air flow required fo...

Page 10: ...oors through vertical ducts each opening shall have a minimum free area of 1 square inch per 4 000 Btu per hour 5 5 cm2 kW of total input rating of all equipment in the enclosure see Figure 8 3 When communicating with the outdoors through horizontal ducts each opening shall have a minimum free area of 1 square inch per 2 000 Btu per hour 11 cm2 kW of total input rating of all equipment in the encl...

Page 11: ...e people are more likely to be permanently injured by hot water than others These include the elderly children the infirm or physically mentally handicapped If anyone using hot water in your home fits into one of these groups or if there is a local code or state law requiring a certain temperature water at the hot water tap then you must take special precautions In addition to using the lowest pos...

Page 12: ...ectly into the fitting of the water heater designed for the relief valve Position the valve downward and provide tubing so that any discharge will exit only within 6 inches 15 2 cm above or at any distance below the structural floor Be certain that no contact is made with any live electrical part The discharge opening must not be blocked or reduced in size under any circumstances Excessive length ...

Page 13: ...ter heater Use a soapy water solution not a match or open flame Rinse off soapy solution and wipe dry When installed at elevations above 7 700 feet 2 347 meters input rating should be reduced at the rate of 4 percent for each 1 000 feet 305 meters above sea level which requires replacement of the burner orifice in accordance with National Fuel Gas CodeANSI Z223 1 NFPA 54 Contact your local gas sup...

Page 14: ...mbly is still mounted securely and the air intake screen of the blower assembly is installed in the dilution air opening Also make sure the drain port of the rubber boot vent adapter is capped off Lastly make sure there is no damage to the blower 3 Make sure there is no packing material in the discharge of the blower or the intake of the dilution air restrictor see Figure 15 4 Make sure that the p...

Page 15: ... this water heater to an existing vent or chimney It must be vented separately from all other appliances Nonmetallic vent may be used if it has Heat Deflection Temperature HDT 66 psi or 455 kPa of at least 157 F or 69 C Typical nonmetallic vent materials meeting this requirement are PVC Schedule 40 ASTM D 1785 Coex Cellular Core Schedule 40 ASTM F 441 CPVC Schedule 40 ASTM D 2846 ABS Schedule 40 A...

Page 16: ...allations will have water condensate in the vent piping If this occurs then adequate means of draining and disposing of the condensate needs to be made by the installer CONDENSATE Condensate formation does not occur in all installations of power vented water heaters but should be protected against on installations where it can form in the venting system Condensation in the venting system of power ...

Page 17: ... building The manufacturer also recommends that the vent termination should not be installed closer than 18 45 7 cm from an inside corner of an L shaped structure and not be less than 1 foot 0 31 m above grade The vent shall terminate a minimum of 12 30 5 cm above expected snowfall level to prevent blockage of vent termination see Figure 16 4 In cold climates it is recommended that vent terminatio...

Page 18: ...plied for decorative purposes only and is not a requirement for the vent termination if not needed by the installer VERTICAL VENT THROUGH ROOF This unit is approved for venting through the roof with the type vent terminal that is included with the unit A proper flashing or BOOT should be used to seal the pipe where it exits the roof The total vent system should not exceed that which is specified s...

Page 19: ...s 15 2 cm and above PRIMER It is recommended that Tetrahydrofuran THF be used to prepare the surfaces of pipe and fittings for solvent welding Do not use water rags gasoline or any other substitutes for cleaning PVC or CPVC surfaces A chemical cleaner such as MEK may be used CEMENT The cement should be a bodied cement of approximately 500 to 1600 centipoise viscosity containing 10 20 by weight vir...

Page 20: ...the distance and make a second mark as the primer and cement will most likely destroy your first one Apply primer to the surface of the pipe and fitting socket with a natural bristle brush This process softens and prepares the PVC or CPVC for the solvent cementing step Move quickly and without hesitation to the cementing procedure while the surfaces are still wet with primer E Application of solve...

Page 21: ...21 ...

Page 22: ...s If a suitable area is not available a cover should be installed over the thermostat to prevent tampering The water temperature setting was factory set at the lowest temperature Pressing the COOLER button decreases temperature and pressing the HOTTER button increases the temperature Setting the water heater temperature at 120 F 49 C Approx mark on temperature setting of the gas control valve will...

Page 23: ... expansion Contact a local plumbing service agency to have a thermal expansion tank installed STRANGE SOUNDS Possible noises due to expansion and contraction of some metal parts during periods of heat up and cool down do not necessarily represent harmful or dangerous conditions Condensation causes sizzling and popping within the burner area during heating and cooling periods and should be consider...

Page 24: ... Viewport on the Inner Door see Figure 1 The main burner should provide complete combustion of gas ignite rapidly give reasonably quiet operation and cause no excessive flame lifting from the burner ports If the proper flame characteristics are not evident see Figure 20 make sure that the flow of combustion and ventilation air is not blocked on the Air Intake Screen at the base of the water heater...

Page 25: ...ails to completely reset and continues to release water immediately close the cold water inlet to the water heater follow the draining instructions and replace the temperature pressure relief valve with a new one If the temperature pressure relief valve on the appliance weeps or discharges periodically this may be due to thermal expansion You may have a check valve installed in the water line or a...

Page 26: ...the tank Droplets form and drip onto the burner or run on the floor This is common at the time of start up after installation and when incoming water is cold I Water in the water heater bottom or on the floor may be from condensation loose connections or the relief valve DO NOT replace the water heater until a full inspection of all possible water sources is made and necessary corrective steps tak...

Page 27: ...models only 26B FV Sensor Bracket 55K 62 5K models only 27 Nipple with Heat Trap 28 Secondary Anode with Heat Trap Not Shown Optional Now that you have purchased this water heater should a need ever exist for repair parts or service simply contact the company it was purchased from or direct from the manufacturer listed on the rating plate on the water heater Be sure to provide all pertinent facts ...

Page 28: ...LINES TROUBLESHOOTING GUIDELINES TROUBLE SHOOTING Please check guidelines below For your safety water heater service should be performed only by a qualified service technician Read the GENERAL SAFETY INFORMATION section first ...

Page 29: ...29 ...

Page 30: ...d be utilized by a qualified service agent When calling for service notify the service agent that this is a Flammable Vapor Ignition Resistant Product TROUBLESHOOTING GUIDELINES TROUBLESHOOTING GUIDELINES Figure 1 and 15 Page 9 ...

Page 31: ...m or any attempt to repair tank leaks or parts will void this warranty SERVICE AND LABOR RESPONSIBILITY UNDER THIS LIMITED WARRANTY THE WARRANTOR WILL PROVIDE ONLY A REPLACEMENT WATER HEATER OR PART THEREOF THE OWNER IS RESPONSIBLE FOR ALL OTHER COSTS Such costs may include but are not limited to a Labor charges for service removal or reinstallation of the water heater or part thereof b Shipping a...

Page 32: ...32 500 Tennessee Waltz Parkway Ashland City TN 37015 www statewaterheaters com ...

Reviews: