32
TP
Low Ambient Temp.
Protection
Ambient temp
≤
-
30
1 Check the ambient temp
2. When ambient temp
≥
-28
℃
, the fault will
disappear.
P01
Water Inlet Temp.
Sensor Fault
1. Detect the connection.
2. Measure the resistance of sensor, if lower than
100
Ω
or higher than 500k
Ω
, please replace a new
one.
P02
Water Outlet Temp.
Sensor Fault
P04
Ambient Temp.
Sensor Fault
P17
Water Outlet Temp.
Sensor Fault
P032
Hot Water Tank
Temp. Sensor Fault
P42
Room Temp. Sensor
Fault
P101
EVI Inlet Temp.
Sensor Fault
P102
EVI Outlet Temp.
Sensor Fault
P153
Coil Temp. Sensor
Fault
P181
Exhaust Temp.
Sensor Fault
P182
Exhaust Over Temp.
(Exhaust temp.)
≥
C05 default 110
1. Measure the resistance of sensor, if lower than
100
Ω
or higher than 500k
Ω
, please replace a new
one.
2. Check the unit find if it has refrigerant leakage.
P191
Antifreeze Temp.
Sensor Fault
1. Detect the connection
2. Measure the resistance of sensor, if lower than
100
Ω
or higher than 500k
Ω
, please replace a new
one.