background image

Rev:  004  DP 070129

INSTALLATION CHECK LIST

Flue System

1.

The flue height should not be less than 3 metres and no more than 11 metres.

2.

If connecting to an existing chimney, the appliance should be connected to a 125mm (5”) 
diameter continuous, rigid or flexible flue pipe that terminates in excess of 0.6 metres from 
the nearest point on the roof measured vertically, and in excess of 2.3 metres measured 
horizontally.

3.

If using an external flue, the appliance should be connected to a 125mm (5”) diameter rigid 
insulated flue pipe that terminates in excess of 0.6 metres from the nearest point on the 
roof measured vertically and in excess of 2.3 metres measured horizontally.

4.

Any horizontal flue sections should not exceed 300mm (12”).

5.

The chimney serving this appliance should not serve any other appliance.

6.

A suitable flue terminal should be fitted at the flue termination point.

7.

If using an internal flue or chimney, closure-clamping plates should be used to seal the top
& bottom of the chimney.

8.

Access should be provided to the chimney serving the appliance to allow for cleaning.

9.

If the flue passes through a combustible wall, a twin wall insulated connector must be used 
and come flush to the external surface of the wall.

10. The flue should be capable of producing a continuous draught of between 0.06” w.g. during 

normal operation.

Location

1.

Clearance to combustible materials must be adhered to as described in the Clearance to 
Combustibles section.

2.

The stove should be installed as to allow adequate air circulation around the stove and to 
allow access for installation & servicing.

3.

The stove must be installed on a non-combustible insulated floor protector that covers the 
area of 1007mm x 470mm around and under the stove.

Ventilation & Combustion Air Requirements

1.

The room in which the appliance is located should have an air vent of adequate size to 
support correct combustion, including all other air using devices fitted in the same or 
adjacent rooms.  (see Ventilation & Combustion Air Requirement Section for specific details).

Gas Supply

1.

A 8mm rigid gas supply pipe must be used to connect directly from the gas meter to the stove.
In the event of a number of appliances using the same supply pipe, the pipe size may need
to be increased.

2.

A shut off valve must be used to connect the gas supply as close as possible to the stove and
should be accessible at all times.

3.

A soundness test must be conducted to check all joints for gas tightness.

Tick

 

15

Manufactured by

Waterford Stanley Ltd.,

Unit 210, IDA Industrial Estate, Cork Road, 

Waterford, Ireland.

Tel: (051) 302300   Fax (051) 302315

Summary of Contents for MAEVE

Page 1: ...WITH GRILL Country AT BE DK FI FR DE GR IS IE Natural Gas LPG Country IT LU NL NO PT ES SE GB Natural Gas LPG WARNING Do not attempt to burn rubbish in this stove This stove must only be operated with the door secured firmly in position The outer casting of this stove will become hot whilst in operation it is therefore recommended that the appliance be guarded to protect the young and infirm using...

Page 2: ...G30 29MB 6 25 Gross GB PT G31 37MB 5 62 Nett BE FR I3B P G30 29MB 6 25 Gross DK FI IS G31 NL NO SE TECHNICAL SPECIFICATION MEDIUM INJECTOR SIZE NG 400 LPG 170 AERATION SIZE Ø NG 11mm Ø I2L 8mm Ø LPG 15 5 x 2 EFFICIENCY CLASS II FLUE T T B SENSOR 100oC FLUE OUTLET SIZE Ø 127mm INLET CONNECTION SIZE Ø 8mm 150 150 225 1007 127 50 470 1 Fig 1 Fig 2 Fig 3 Fig 4 Fig 5 Fig 6 176 ...

Page 3: ...ING THE STOVE 4 1 Remove the ceramic coals and place on a dry clean surface Remove the front coal ceramic please handle with care 4 2 Clean the flame baffle ceramic piece and burner using a vacuum cleaner with soft brush attachment ensure all debris are removed from the burner ports 4 3 Replace the ceramics by referring to Section 5 5 ARRANGEMENT OF FUEL BED COM PONENTS The major ceramic component...

Page 4: ...pondence always quote the appli ance type and the serial number which may be found on the data badge 9 ENAMEL CLEANING General cleaning must be carried out when the stove is cool If this stove is finished in a high gloss vitreous enamel to keep the enamel in the best condition observe the following tips 9 1 Wipe over daily with a soapy damp cloth followed by a polish with a clean dry duster 9 2 Fo...

Page 5: ... that the local distribution conditions identification of the type of gas and pressure and the adjustment of the appliance are compati ble IMPORTANT ENSURE THAT THE APPLI ANCE IS CORRECTLY ADJUSTED FOR THE GAS TYPE AND CATEGORY APPLICABLE IN THE COUNTRY OF USE REFER TO DATA BADGE AND TECHNI CAL SPECIFICATIONS AT THE FRONT OF THE BOOKLET FOR DETAILS OF CHANGING BETWEEN GAS TYPES REFER TO SECTION 18...

Page 6: ... expel any debris that may block the gas controls Connect the gas supply to the 8mm compression elbow at the right hand rear corner of the stove see Fig 10 6 4 Check the pull of the flue system by apply ing a lighted smoke pellet to the flue sys tem opening If there is a definite flow into the chimney proceed with the installation if not warm the chimney for a few minutes IF THERE IS STILL NO DEFI...

Page 7: ...e isolation 6 device remove the door and place to one side carefully remove the ceramic fuelbed components 10 2 Undo the pilot compression nut remove the ignition lead from the electrode by gen tly pulling downwards and undo the ther mocouple from the back of the gas valve see Fig 19 Undo the main injector compression nut and pull pipe clear of the injector see Fig 23 10 3 Remove the two pozidriv ...

Page 8: ...d in a restric tive location it may be necessary to remove the stove from its location 16 1 Locate the sensor in the draught diverter opening and gently pull the two wires off the terminals Undo the two taptite screws and remove the sensor and the two plastic spacers see Fig 24 16 2 Refit a new sensor ensuring that the spac ers are located between the sensor and the bracket replace the two leads 7...

Page 9: ...has entered the stove pipework Blocked gas filter Replace filter refer to Section 12 Insufficient gas pressure Check the gas pressure and correct if necessary Empty supply tank or LPG only ensure adequate clylinder supply of gas in cylinders Short pilot flame length see Insufficient gas Check the gas pressure and diagram 26 pressure correct if necessary Blocked pilot flame Replace Unit refer to se...

Page 10: ...ES YES YES NO NO NO NO YES YES YES YES NO FLAME FAILURE FUNCTIONAL CHECK PILOT WILL NOT STAY LIT OR FIRE GOES OUT IN USE If the appliance goes out in use continually this may mean that the Waterford Flue T T B System has been activated The appliance should not be used until the cause has been found and rectified Ensure there is no debris around the pilot assembly e g coal soot etc which could shor...

Page 11: ...A B Medium 1007 470 A 225mm B 150mm A 50mm B 150mm 10 DIAGRAMS Fig 7 Fig 8 Fig 9 ...

Page 12: ...11 Fig 10 Fig 11 Fig 12 Fig 13 Fig 15 Fig 14 COAL LAYOUT ...

Page 13: ...12 Fig 16 Fig 17 Fig 18 ...

Page 14: ...13 Fig 19 Fig 21 Fig 20 ...

Page 15: ...14 Fig 22 Fig 23 Fig 24 Fig 26 Fig 25 ...

Page 16: ...he external surface of the wall 10 The flue should be capable of producing a continuous draught of between 0 06 w g during normal operation Location 1 Clearance to combustible materials must be adhered to as described in the Clearance to Combustibles section 2 The stove should be installed as to allow adequate air circulation around the stove and to allow access for installation servicing 3 The st...

Reviews: