Read all the instructions before using and installing this product.
•
Do not use this product if power cable or charging cable have any damage.
•
Do not use this product if the enclosure or charging connector are broken or
open or if there is damage.
•
Do not put any tool, material, finger or other body part into the charging connec
-
tor or EV connector.
•
Do not twist, swing, bend, drop or crush the charging cable. Never drive over it
with a vehicle.
•
Power feed must be 3 Phase Wye configuration with TN(-S)/ TT grounding sys
-
tems.
•
In the installation of TN(-S) system: the neutral (N) and the PE of the power dis-
tribution are directly connected to the earth. The PE of the charger equipment is
directly connected to the PE of power distribution and separate conductor for PE
and neutral (N).
•
In the installation of TT system: the neutral (N) and the PE of the power distribu-
tion are directly connected to the earth. The PE of the charger equipment is iso-
lated to the PE of power distribution to the earth.
•
The capacity of power supply should be higher than 67kVA in order to function
correctly.
•
The product should be installed in free air area and keep at least 30cm (12 inch-
es) clearance distance to all air vent of the product.
•
Recommend to keep not less than 100cm (3 ft. 6 in.) clearance distance from all
around the product following NEC table 110.26 condition 2, 151-600V.
3. Installation Instruction
3.1 Before Installation
Warning: The product should be installed only by a licensed contractor
and/or licensed technician in accordance with all building codes, elec-
trical codes and safety standards.
Warning: The product should be inspected by a qualified installer prior
to initial use. Under no circumstances will compliance with the infor-
mation in this manual relieve user of his /her responsibilities to comply
with all applicable codes and safety standards.
9