D7418/4-UL

 

Y04/YL4 INSTALLATION INSTRUCTIONS

 

General  Description:  This  application  should  be  installed  and  used  as  recommended  by  the  National  Fire  Protection 

Association standards and practices. 

The Installer should be familiar with these requirements together with any local codes or special requirements of the local 

Fire Authority having jurisdiction. 

The alarm sounders are intended for connection to the output alarm circuit of a UL listed fire alarm control panel only. All 

alarms are compatible with DC line status monitoring. The alarm sounders are suitable for outdoor use (-35ºC to +66ºC). 

Installation procedures must confirm to appropriate agency requirements including but not limited to the following:- 

 

NFPA72E, NEC ART.760 ET.AL., CAN/ULC-S524-M86, CEC PART 1 SEC 32 

Installation: The sounder or combined sounder strobe units can be affixed to most surfaces using the back box supplied 

separately.    

Supply  input:  Ensure  that  the  supply  is  correct  for  the  voltage  rating  of  the  sounder  or  combined  sounder strobe  being 

installed. Ensure that the supply is OFF before making any connection and wire only in accordance with the terminal label 

detail.  

Sound  selection:  Ensure  the  supply  is  OFF  before  proceeding.  All  dc  and  ac  units  have  selectable  alarm  sounds  (see 

table below for details) and are selectable by means of a 5 way dil switch SW1. A second sound is made available upon 

the  application  of  a  third  wire  connected  to  terminal  TB1/3  as  shown  in  Fig.  1  while  still  connected  to  terminal  TB1/2. 

Alternatively  1st  and  2nd  stage  sound  signals  can  be  generated  by  supply  reversal  (FOR  DC  UNITS ONLY) see Fig. 2.  

Independent second stage sound is available by using SW2 (OPTIONAL- only fitted with orders).  

WARNING - Loud alarm sound. Wear ear defenders when testing, installing and commissioning. 

 

 

 

- HIGH VOLTAGES ARE PRESENT WITHIN THE BEACON WHEN OPERATIONAL 

SOUND SELECTION TABLE

 

 

First Stage Sound  

 

frequency   

rept. 

 

Second 

 

switches   

 

 

 

 

 

 

 

 

Hertz   

 

rate 

 

Stage   

 

1 2 3 4 5 

 

Special Application 

 

1  Alternate two-tone 

 

800-1000   

0.5   

 

 

 

 

1 1 1 1 1 

 

Fire Alarms 

2 Alternate two-tone 

 

2500-3100   

0.5   

 

 

 

 

0 1 1 1 1 

 

Security Alarms 

3 Alternate fast two-tone 

800-1000   

0.25 

 

 

 

 

1 0 1 1 1 

 

Increased urgency   

4 Alternate fast two-tone 

2500-3100   

0.25 

 

 

 

 

0 0 1 1 1 

 

Security deterrent 

5 Alternate two-tone 

 

440-554 

 

0.4/0.1   

14   

 

 

1 1 0 1 1 

 

AFNOR, France 

6 Alternate two-tone 

 

430-470 

 

1.0   

 

14   

 

 

0 1 0 1 1    

7 Alternate v.fast two-tone  800-1000   

0.13 

 

12   

 

 

1 0 0 1 1 

 

 

8 Alternate v.fast two-tone  2500-3200   

0.07 

 

13   

 

 

0 0 0 1 1 

 

 

9 Alternate two-tone 

 

440-554 

 

2.0   

 

10   

 

 

1 1 1 0 1 

 

Turn-out, Sweden 

10 Continuous note  

 

700  

 

 

 

 

 

 

 

0 1 1 0 1 

 

All-clear, Sweden 

11 Continuous note  

 

1000 

 

 

 

 

31   

 

 

1 0 1 0 1 

 

 

12 Continuous note  

 

1000 

 

 

 

 

 

 

 

0 0 1 0 1 

 

 

13 Continuous note  

 

2300 

 

 

 

 

 

 

 

1 1 0 0 1 

 

 

14 Continuous note  

 

440  

 

 

 

 

 

 

 

0 1 0 0 1 

 

 

15 Interrupted tone  

 

1000 

 

 

2.0   

 

31   

 

 

1 0 0 0 1 

 

 

16 Interrupted tone  

 

420  

 

 

1.25 

 

30   

 

 

0 0 0 0 1 

 

AS2220, Australia 

17 Interrupted tone  

 

1000 

 

 

0.5   

 

 

 

 

1 1 1 1 0 

 

 

18 Interrupted tone  

 

2500 

 

 

0.25 

 

 

 

 

0 1 1 1 0 

 

 

19 Interrupted tone  

 

2500 

 

 

0.5   

 

 

 

 

1 0 1 1 0 

 

 

20 Interrupted tone  

 

700  

 

 

6/12 

 

10   

 

 

0 0 1 1 0 

 

Pre-vital mess, Sweden 

21 Interrupted tone  

 

1000 

 

 

1.0   

 

32   

 

 

1 1 0 1 0 

 

 

22 Interrupted tone  

 

700  

 

 

4.0   

 

10   

 

 

0 1 0 1 0 

 

Air-raid, Sweden 

23 Interrupted tone  

 

700  

 

 

0.25 

 

10   

 

 

1 0 0 1 0 

 

Local warning, Sweden 

24 Interrupted tone  

 

720  

 

 

0.7/0.3   

10   

 

 

0 0 0 1 0 

 

Industrial alarm, Germany 

25 Int,fast,rising volume 

1400 

 

 

0.25 

 

26   

 

 

1 1 1 0 0    

 

26 Fast siren 

 

 

 

250-1200   

0.085   

11   

 

 

0 1 1 0 0 

 

 

27 Rising constant, fall   

1000 

 

 

10/40/10 

17   

 

 

1 0 1 0 0 

 

Industrial alarm, Germany 

28 ISO 8201 Evacuation 

800-1000   

as std   

11   

 

 

0 0 1 0 0 

 

Int’l evacuation alarm 

29 Fast whoop   

 

 

500-1000   

0.15 

 

32   

 

 

1 1 0 0 0 

 

 

30 Slow whoop  

 

 

500-1200   

4.5   

 

12   

 

 

0 1 0 0 0 

 

Evacuation, The Netherlands 

31 Reverse sweep   

 

1200-500   

 

 

11   

 

 

1 0 0 0 0 

 

Evacuation, Germany 

32 Siren 

 

 

 

 

500-1200   

3.0   

 

26   

 

 

0 0 0 0 0 

 

 

Switch settings: ON=1 and OFF=0 

MOUNTING: The Y04/YL4 series alarm units are supplied separate from the back box. The back box should be mounted 

to a suitable surface or to a standard wiring box using any of the mounting holes. 20mm cable entries are provided on all 

sides and in the base. To maintain the integrity of the weather seal, the cable entry must be via a suitable sealed gland. 

 