Mounting and Installation
11
SolConeX Wall-Mounted Socket, 16 A
Series 7570/11
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
7.3
Installation
WARNING
Danger due to live components!
Risk of severe injuries!
• Disconnect all connectors and wires from the power supply.
• Secure the connections against unauthorized switching.
DANGER
Risk of explosion!
Risk of injuries and material damage!
• Select suitable conductors to ensure that the maximum
permissible conductor temperatures are not exceeded.
• When using core end sleeves, attach them using a suitable tool.
• Observe the insulation capability and separation distances
between intrinsically safe and non-intrinsically safe circuits
according to EN 60079-14, section 12.
• Use only separately tested cable glands and stopping plugs with
EC Type Examination Certificate.
• The conductor insulation must reach to the terminal.
• Do not damage the conductor (e.g. nicking) when stripping it.
• Always connect the protective conductor.
Two conductors can be installed under one connection terminal. The material
and conductor cross-section of both conductors must be identical.
The conductors can be connected without any special preparations.