169070 / 9193603310
2019-0
7
-
16
·BA00·III·en·0
1
Parameterization and Commissioning
11
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
Supply Module
Type 9193/21-11-11
6.2
Installation
6.2.1 Electrical Connections / Schematic Diagram
See device labelling.
For the connection cross-sections of the wiring to be connected,
refer to chapter "Technical data".
If there is only one auxiliary power supply, connect the power supply to the terminals 1 +
and 3 -.
7
Parameterization and Commissioning
Before commissioning, carry out the following checks:
• Mounting and installation of the device according to regulations.
• Correct, secure connection of the cables.
• No damage to the device or the cables.
• The screws are securely fastened to the terminals.
Correct tightening torque: 0.5 to 0.6 Nm.
Do not commission the device until it has been successfully tested.
7.1
Replacement of the Device
• If replacing this device with a device with an identical design, readjust the DIP switch if
necessary.
7.2
Parameterisations and Error Messages
If the primary auxiliary power supply ("PWR1") fails, an error message is always issued
regardless of whether or not a redundant supply has been connected. If there is a malfunction
of the interchangeable fuse, an error message is always issued as well.
Operation under difficult conditions, in particular on ships, requires additional
measures to be taken for correct installation, depending on the operating location.
Further information and instructions on this can be obtained from your regional sales
contact upon request.
DANGER! Explosion hazard from operating the DIP switches in Zone 2
while they are live!
Non-compliance may result in serious or even fatal injury.
Adjust the DIP switches exclusively in a de-energised state.
20304E00
DIP 4
Non-functional
DIP 3
Collective error message for 92xx series modules
• I: Message activated
• II: Message deactivated
DIP 2
Collective error message for 91xx series modules
• I: Message activated
• II: Message deactivated
DIP 1
Error message for "PWR2"
• I: Message activated
• II: Message deactivated
I II
4
3
2
1
Summary of Contents for ISpac 9193/21-11-11
Page 41: ......