Commissioning
19
Linear Luminaire with LED
Series EXLUX 6402/2
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
Luminaires with approved cable glands and stopping plugs; not supplied by
R. STAHL Schaltgeräte GmbH
Please note:
• the required dust resistance!
• the required type of protection!
• the required temperature resistance!
• the IP degree of protection according to the rating plate!
• the operating instructions of the cable glands and stopping plugs!
• the required tightening torques!
• the range of the permissible cable diameter!
8
Commissioning
Before commissioning, ensure that
• the device has been installed according to regulations.
• the power supply voltage and the rated operational voltage are identical.
• the required cable diameter for cable glands has been used.
• the cable entries and stopping plugs have been securely tightened.
• the cables are correctly connected.
• the connection has been performed correctly.
• all screws and nuts are tightened according to regulations.
• the connection chamber is clean.
• the device is not damaged.
• no foreign bodies are inside the device.
• the device is sealed according to regulations.
• the LED assembly and the diffusor are clean.
M25 x 1.5
1.5 Nm
WARNING
Cable glands and stopping plugs which are not approved.
Explosion protection is impaired!
• Only use separately certified cable glands and stopping plugs.
DANGER
Explosion hazard due to incorrect installation!
Non-compliance results in severe or fatal injuries.
• Check the device for proper installation and function before
commissioning.
• Comply with the national regulations.
NOTE
Condensation
due to specific environmental and operating conditions condensation cannot be avoided
completely.
• operate the luminaire continuously or periodically over extended periods of time!
• avoid thermal bridges!