background image

BARAT LED Ex           

USER INSTRUCTION OF LUMINAIRE

 

 

 

NORTHCLIFFE LIGHTING                  

 

     2015-12-14            No. BARLEDEX-151214 

 

Subject to change without notice 

    BARAT LED EX 

Raudondvario pl. 101, Kaunas, Lithuania.  

www.northcliffe.org

 

 

Explosion Proof IP66 
Luminaire for 
Hazardous Zones 2, 22 

 

 
 
 
 
 

 

 

 

 

Type: 

Explosion proof IP66 luminaire designed for illumination of hazardous areas where an explosive atmosphere persists 

for a short period. Hazardous zones: 2, 22. 

Specification: 

Opal (LED) UV stabilized polycarbonate diffuser. White powder coated gear tray. 

Injection molded polycarbonate canopy, grey finished. Stainless steel diffuser retaining clips. 
Explosion group: gas: IIC, IIB, IIA  dust: IIIC, IIIB, IIIA 

Protection degree: IP66 
ATEX cable gland: 2xM20, 1xblanking plug 

Cable diameter: 

7-13mm 

Ta: -25ºC to 40ºC (Ta with emergency kit: +0ºC to 35ºC) 

Luminaire is plastic-wrapped and boxed individually. 

Installation: 

Surface luminaire is designed to be fixed to ceilings of any type or suspended. Supplied with two fixing brackets for 

easy  installation,  sealing  washer  and  accessories  for  chain  and  wire  suspension.  Installed  luminaires  has  to  be 
protected from mechanical damage. 

Application: 

Suitable for industrial areas and facilities with a danger of flammable gas, dust and vapour explosion. Marking of 

explosion-protection: II 3G Ex nA IIC T6 Gc;  II 3D Ex tc IIIC T85

o

C Dc 

 

 

 

 

 

 If EM3   

 

 

 

 

Summary of Contents for Barat LED1x1300 C101 T840 PC/PC OP IC Ex

Page 1: ...d Stainless steel diffuser retaining clips Explosion group gas IIC IIB IIA dust IIIC IIIB IIIA Protection degree IP66 ATEX cable gland 2xM20 1xblanking plug Cable diameter 7 13mm Ta 25ºC to 40ºC Ta with emergency kit 0ºC to 35ºC Luminaire is plastic wrapped and boxed individually Installation Surface luminaire is designed to be fixed to ceilings of any type or suspended Supplied with two fixing br...

Page 2: ...x111 50000 3759 31 80 4000 2 10 Barat LED2x2600 C110 T840 PC PC OP IC Ex 1272x146x111 50000 5117 46 80 4000 2 80 Barat LED2x3800 C111 T840 PC PC OP IC Ex 1272x146x111 50000 7518 62 80 4000 2 80 Barat LED1x3200 C113 T840 PC PC OP IC Ex 1572x96x111 50000 3198 29 80 4000 2 60 Barat LED1x4700 C114 T840 PC PC OP IC Ex 1572x96x111 50000 4699 39 80 4000 2 60 Barat LED2x3200 C116 T840 PC PC OP IC Ex 1572x...

Page 3: ...nas Lithuania www northcliffe org Type Examination Certificate Number OBAC 16 ATEX II 3G Ex nA IIC T6 Gc II 3D Ex tc IIIC T85o C Dc Type Barat LED1x Ex Light source LED module Type of power source LED driver Temperature class T6 T max surface 850 C Type Barat LED2x Ex Light source LED module Type of power source LED driver Temperature class T6 T max surface 850 C ...

Page 4: ...ьник должен быть установлен в соответствии со всеми требованиями безопасности Внимание Точная модель прибора указаны на этикетке внутри него Ettevaatusabinõud EST Paigaldamise võib teostada ainult volitatud elektrik Lülitage välja toide enne paigaldustööde alustamist Valgusti peab olema paigaldatud vastavalt kõigile ohutusnõuetele Tähelepanu Toote täpne mudel on toote etiketil Piesardzības pasākum...

Page 5: ...ARAT LED EX Raudondvario pl 101 Kaunas Lithuania www northcliffe org 6 7 If option ThroughWiring 8 If Emergency If Through Wiring 3LIN 1LIN 9 L L1 or L2 or L3 10 11 Closing sequence Exploitation If the lens is dirty clean it with a damp cloth only Electrostatic sensitive devides Do not enter without proper static control devices ...

Page 6: ...vario pl 101 Kaunas Lithuania www northcliffe org USER TO REPLACE BATTERIES Accu NiCd 4A 55 Nickel cadmium cells NiCd Batteries technical information Connection blade terminal Number of cells 4 Capacity 4 5Ah 1 2 3 4 USE ONLY NiCd Batteries 5 6 Red positive Black negative WARNING DO NOT CHANGE THE BATERRY WHEN THE EXPLOSIVE ATMOSPHERE IS POSSIBLE ...

Reviews: