6.3 Connection of the cables to
the base
CAUTION! The electrical system to which the
unit is connected must be equipped with a
15A max automatic bipolar circuit breaker.
The minimum distance between the circuit
breaker contacts must be 3mm (0.1in).
The circuit breaker must be provided
with protection against the fault current
towards the ground (differential) and the
overcurrent (magnetothermal).
A power disconnect device must be
included in the electrical installation, and
it must be very quickly recognizable and
operated if needed.
Before doing any technical work on the
device make sure that the power supply is
disconnected.
The device can only be considered to be
switched off when the power supply has
been disconnected and the connection
cables to other devices have been removed.
Be careful not to use cables that seem worn
or old.
Use adequate cable for higher temperature
than 80°C. And if installed in an external
ambient below –10°C the cable suitable for
the minimum ambient temperature at point
installation.
The connection compartment lid can
be opened only for cabling the device.
The other lids must be opened by the
manufacturer only.
A connection compartment for cable entry with a
3/4” NPT threaded hole is located on the base of the
unit.
A threaded cap gives access to a connection board
with removable connectors that help the installer to
connect the cables.
The safety grub screws are used to prevent
the unscrewing of the threaded lid from the
connection compartment. Remove both
safety grub screws before unscrewing the
threaded lid.
Carry out the connections removing the safety grub
screws (01), the threaded lid (02) and the plastic cap
(03).
The plastic cap is only used during transportation and
cannot be used when operating the device.
02
01
03
Fig.
12
Summary of Contents for EC-940-DUA Series
Page 2: ......
Page 4: ......
Page 87: ......
Page 88: ...MNTCMPXT_1824_EN R Stahl HMI Systems GmbH Adolf Grimme Allee 8 50829 K ln Germany...
Page 90: ......
Page 173: ......
Page 174: ...MNTCMPXT_1824_IT R Stahl HMI Systems GmbH Adolf Grimme Allee 8 50829 K ln Germany...
Page 176: ......
Page 259: ......
Page 260: ...MNTCMPXT_1824_FR R Stahl HMI Systems GmbH Adolf Grimme Allee 8 50829 K ln Germany...
Page 262: ......
Page 345: ......
Page 346: ...MNTCMPXT_1824_DE R Stahl HMI Systems GmbH Adolf Grimme Allee 8 50829 K ln Germany...
Page 347: ...RU EC 940 PTZ A EC 940 DUA PTZ...
Page 348: ......
Page 353: ...RU 7 MNTCMPXT_1824_RU 1 1 1 INFO 2 3 J1 6 5 19 1...
Page 354: ...RU 8 MNTCMPXT_1824_RU 40 C 60 C IEC EN60079 14 4 4 2 10...
Page 357: ...RU 11 MNTCMPXT_1824_RU 5 5 1 15A max 3mm 5 2...
Page 358: ...RU 12 MNTCMPXT_1824_RU 5 3 1 PTZ 1 2 1 1 2 2 IP 1 PTZ 1 2 1 1 2 2 1 CD 1 PTZ 1 2 1 3 6 2 2 5 4...
Page 363: ...RU 17 MNTCMPXT_1824_RU 6 3 15A max 3mm 80 C 10 C 3 4 NPT 01 02 03 02 01 03 12...
Page 376: ...RU 30 MNTCMPXT_1824_RU 6 21 STAHL 46 47 30mm 48 49...
Page 377: ...RU 31 MNTCMPXT_1824_RU 7 7 1 7 1 1 STAHL 7 1 2 7 1 3...
Page 378: ...RU 32 MNTCMPXT_1824_RU 8 De Ice 0 C 60 120 8 1...
Page 426: ...RU 80 MNTCMPXT_1824_RU 15 336 336 232 232 N 4 M10 N 4 M10 138 138 398 398 128 EC 940 PTZ A...
Page 427: ...RU 81 MNTCMPXT_1824_RU 453 453 232 232 N 4 M10 N 4 M10 138 138 398 398 129 EC 940 DUA...
Page 431: ......
Page 432: ...MNTCMPXT_1824_RU R Stahl HMI Systems GmbH Adolf Grimme Allee 8 50829 K ln...
Page 434: ......
Page 517: ......
Page 518: ...MNTCMPXT_1824_PT R Stahl HMI Systems GmbH Adolf Grimme Allee 8 50829 K ln Germany...
Page 519: ...KO EC 940 PTZ A EC 940 DUA PTZ...
Page 520: ......
Page 525: ...KO 7 MNTCMPXT_1824_KO 1 1 1 INFO 2 3 J1 6 5 19 1...
Page 526: ...KO 8 MNTCMPXT_1824_KO 40 C 60 C 40 F 140 F IEC EN60079 14 4 4 2 10 A UPS...
Page 529: ...KO 11 MNTCMPXT_1824_KO 5 5 1 15A 3mm 0 1 5 2...
Page 530: ...KO 12 MNTCMPXT_1824_KO 5 3 1 PTZ 1 2 1 1 2 2 IP 1 PTZ 1 2 1 1 2 2 1 CD 1 PTZ 1 2 1 3 6 2 2 5 4...
Page 535: ...KO 17 MNTCMPXT_1824_KO 6 3 15A 3mm 0 1 80 10 C 3 4 NPT 01 02 03 02 01 03 12...
Page 548: ...KO 30 MNTCMPXT_1824_KO 6 21 OR OR STAHL O 46 OR 47 30mm 48 49...
Page 549: ...KO 31 MNTCMPXT_1824_KO 7 7 1 7 1 1 STAHL 7 1 2 7 1 3...
Page 550: ...KO 32 MNTCMPXT_1824_KO 8 De Ice 0 C 60 120 8 1...
Page 579: ...KO 61 MNTCMPXT_1824_KO PC 117 118 9 7 2 1 WAN Setting IP IP 192 168 0 101 30 192 168 0 101 119...
Page 598: ...KO 80 MNTCMPXT_1824_KO 15 336 336 232 232 N 4 M10 N 4 M10 138 138 398 398 128 EC 940 PTZ A...
Page 599: ...KO 81 MNTCMPXT_1824_KO 453 453 232 232 N 4 M10 N 4 M10 138 138 398 398 129 EC 940 DUA...
Page 603: ......
Page 604: ...MNTCMPXT_1824_KO R Stahl HMI Systems GmbH Adolf Grimme Allee 8 50829 K ln Germany...
Page 605: ......
Page 606: ...MNTCMPXT_1824 MNTCMPXT_1824 R Stahl HMI Systems GmbH Adolf Grimme Allee 8 50829 K ln Germany...