I.S. Relay Module
Type 9172/**-11-00
91 726 01 31 1
none
FM
01
13.12.11
Reistle
Kaiser
02
22.10.12
Reistle
Type 9172/*0-11-00
Type 9172/*1-11-00
Type 9172/*2-11-00
Hazardous area:
Class I, II, III; DIV 1; Group A-G or Class I; Zone 0; Group IIC/IIB Hazardous Locations
Safe area:
Non-hazardous; Division 2 or Zone 2 Hazardous (Classified) Locations
The Relay Module Type 9172 is an associated apparatus as well as a nonincendive apparatus for installation in non-hazardous or Class I,
Division 2 or Zone 2 Hazardous (Classified) Locations and provides intrinsically safe connections for one (or two) field devices located in
Class I, II, III, Division 1, Group A-G or Class I, Zone 0 [AEx ia] Group IIC, hazardous locations according to NEC Article 504/505 as listed
below.
Relay Module Type 9172/ab-11-00
a = numeral 1 or 2 for number of channels
b = numeral 0, 1 or 2 for direction of action (relay)
Entity parameters are as follows:
V
OC
I
SC
P
O
V
max
I
max
P
i
L
i
C
i
Type 9172/*0-11-00
Type 9172/*2-11-00
0
0
0
30 V
150 mA
1.3 W
0
0
Nominal values for the output circuits:
U
n
I
n
P
n
Type 9172/*0-11-00 250 V AC
220 V DC
125 V AC
125 V DC
60 V DC
30 V DC
4.0 A
0.1 A
4.0 A
0.25 A
0.3 A
4.0 A
100 VA
100 VA
100 W
Limits for I.S. circuits connected to output contacts:
V
max
I
max
L
i
C
i
Type 9172/*1-11-00
Type 9172/*2-11-00
125 V AC
125 V DC
60 V DC
30 V DC
4.0 A
0.25 A
0.3 A
4.0 A
0
0
Notes:
1. For Connections refer to chapter Commissioning of Operating Instruction ID-No. 91 726 01 31 0.
2. Intrinsically safe apparatus may be switches, thermocouples, LEDs, RTDs or an FM Approved System or
Entity device connected in accordance with the manufacturer´s installation instructions.
3. For Entity concept use the appropriate parameters to ensure the following:
V
t
or V
OC
V
max
C
o
, C
a
C
i
+ C
leads
P
o
≤ P
I
I
t
or I
SC
I
max
.
L
o
,
L
a
L
i
+ L
leads
4. Electrical apparatus connected to an intrinsically safe system should not use or generate voltages > 250 V (U
max
).
5. Installation should be in accordance with Article 504/505 of the National Electrical Code ANSI/NFPA 70 and
ANSI/ISA RP 12.06.01.
6. Installation in Canada should be in accordance with the Canadian Electrical Code, CSA C22.1, Part 1, Appendix F.
7. Use a general purpose enclosure meeting the requirements of IEC 61010-1 for use in non-hazardous or
Class I, Division 2, Hazardous (Classified) Locations.
8. Use an FM Approved Dust-ignition proof enclosure appropriate for environmental protection
in Class II, Division 1, Groups E, F and G; and Class III, Hazardous (Classified) Locations.
9. These modules are to be mounted on DIN rail, DIN rail with pac-Bus (type 9194) or pac-Carrier (type 9195).
The I.S. field wiring in any case is connected to the ISpac device terminals.
10. Ambient temperature:
-20°C
… +70°C (any mounting position)
WARNING:
Do not disconnect equipment when a flammable or combustable atmosphere is present.
AVERTISSEMENT:
Ne pas débrancher l’équipement en présence d’atmosphère inflammable ou combustible.
(only at
9172/20)
(only at
9172/22)
(only at
9172/21)
Summary of Contents for 9172 Series
Page 33: ......