Switching Repeater Type 9170/*2       

Maintenance and repair 

It is recommended that all repairs to our devices be carried out by R. STAHL. 
In exceptional cases, repair may be performed by approved third-parties. 
The devices are maintenance-free. 
 
Troubleshooting chart: 

 

Error detection 

Malfunction cause(s) 

Corrective action 

“PWR” LED does not lit 

Power supply failure  
Device fuse is defective 
 
Polarity reversal 

Check power supply. 
If device fuse is defective, send device in for 
repair. 
Connect the power acc. to operating guide 

“LF” LED lights all the time 

Switching element is not connected 
correctly – short circuit or disruption 
Switching element does not work in 
compliance with NAMUR 

Please verify that the connection is established 
correctly.  
Please apply the mode of connection for volt-
free contacts as described in 7.2 .  

LED “OUT” lights but the 
state of operation at the 
output does not change 

The exchangeable terminals are 
mixed up. 

Please connect the terminals to the predefined 
socket. 

High switching frequencies 
are not transmitted 

The electronic output is optimized for 
the application along with active I/O 
cards. In case of passive I/O cards 
the potential for the generation of 
High Level is missing. 

The High Level can be generated if an resistor 
is connected externally to the supply voltage 
(e.g. +5V).  

 

Self test 
In  order  to  check  basic  functions  of  the  device,  you  may  apply  the  following  test  steps. 
Please disconnect the exchangeable terminals first. (see 6.3) 

 

Connect the device to the power supply (directly via terminals 7 and 9) 

 

Deactivate the  line  fault  detection my means  of the  DIP switches  at  the  front  of 
the device. 

 

Establish  an  electrical  connection  between  terminal  11  and  12  (in  case  of  dual 
channel devices additionally between terminal 14 and 15) 

 

The LED ”OUT” (yellow) lights up. It indicates that the output has switched. If you 
disconnect the connection between the terminals the LED turns dark. The result 
of this test indicates that input signals are processed. 

 

Activate  the  line  fault  detection.  The  LED  “LF”  lights  up  no  matter  if  the 
connection between the terminal is established or not.     

 
If  the  procedure  described  above  does  not  obtain  the  desired  result,  please  contact  your 
local R.STAHL sales and service representative. In order to quickly process your request, 
please provide us with the following information: 

  Type and serial number 

  Purchase date 

  Description of malfunction 

  Application description (particularly the configuration of the input/output circuitry) 

 
 

10  Accessories and spare parts 

Use only original spare parts from R. STAHL Schaltgeräte GmbH. 

Summary of Contents for 9170/12-12-13

Page 1: ...Type 9170 Switching Repeater 1 1 1 Operating Instructions Type 9170 2 Switching Repeater...

Page 2: ...Engineering of the power dissipation in cabinets 6 6 Arrangement and fitting 7 6 1 Dimensions 7 6 2 Installation 7 6 3 Mounting and dismounting 7 7 Commissioning 8 7 1 Connections 8 7 2 Engineering 8...

Page 3: ...lly recognised technical regulations Safety guidelines in these operating instructions Any damage can compromise and even neutralise the explosion protection The following requirements apply if used i...

Page 4: ...ternal capacitance Ci Internal inductance Li Max connectable capacitance Co IIC IIB I Max connectable inductance Lo IIC IIB I Insulation voltage Um 9 6 V 9 6 V 10 mA 20 mA 24 mW 48 mW 2 42 nF 4 84 nF...

Page 5: ...F 149 F 9170 22 12 23 131 F 149 F Ventilation With ventilation Installation Single unit DIN rail Orientation any vertical horizontal Channels Type 1 9170 12 12 13 158 F 158 F 158 F 9170 12 12 23 158...

Page 6: ...e lower and upper ends of the cabinet the air flow path must be kept free from obstacles Result Depending on the engineering the improvement can reach a two times higher power dissipation as with a c...

Page 7: ...napping onto the pac Bus Note In order to prevent pole reversal during installation the pac Bus elements have been equipped with a keyed connection plug see photo The module is fitted with a matching...

Page 8: ...t identification volt free contacts at the input Open circuit identification 22 k or 33 k in parallel Short circuit identification 2 7 k in series The loading has to carry out in direct proximity of t...

Page 9: ...ized Electronic output activated Relay not energized Electronic output deactivated Line fault detection LF activated Open circuit IE 0 05 0 35mA Relay not energized Electronic output deactivated Relay...

Page 10: ...neration of High Level is missing The High Level can be generated if an resistor is connected externally to the supply voltage e g 5V Self test In order to check basic functions of the device you may...

Page 11: ...11 EC Declaration of Conformity...

Page 12: ...12 EC Type Examination Certificate...

Page 13: ......

Page 14: ......

Page 15: ......

Page 16: ...R STAHL Schaltger te GmbH Am Bahnhof 30 74638 Waldenburg W rtt Germany www stahl de ID Nr 9170611310 S BA 9170 2 001 en 06 2009...

Reviews: