5
Technical data
Marking
Type designation
9162/13-11-a4 (a=1,6)
CE marking
C
0158
Type 9162/13-11-14
Explosion Protection
Global (IECEx)
Gas and dust
IECEx BVS 15.0013X
Ex nA nC [ia Ga] IIC T4 Gc
[Ex ia Da] IIIC
Europe (ATEX)
Gas and dust
BVS 15 ATEX E018X
E
II 3 (1) G Ex nA nC [ia Ga] IIC T4 Gc
E
II (1) D [Ex ia Da] IIIC
Certifications and certificates
Certificates
IECEx, ATEX, Canada (cFM), USA (FM)
Safety data
When connecting
transmitters
When connecting
current sources
2-wire transmitter 3-wire transmitter
max. voltage U
o
27 V
27 V
max. current I
o
87.9 mA
88.3 mA
max. power P
o
574 mW
574 mW
max. connectable capacitance C
o
IIC
90 nF
90 nF
max. connectable inductance L
o
IIC
2.3 mH
2.3 mH
internal capacitance C
i
negligible
negligible
internal inductance L
i
negligible
negligible
Safety-related
maximum voltage
253 V
253 V
max. output voltage U
o
4.1 V
max. output current I
o
~ 0 mA
Max. output power P
o
~ 0 mW
max. connectable voltage U
i
30 V
max. connectable current I
i
100 mA
internal capacitance C
i
negligible
internal inductance L
i