Technical Data
8
149909 / 8562604300
S-BA-8562-03-en-20/11/2008
Miniature Circuit Breaker
8562/5
Auxiliary switch
The switch indicates the status of the protective device (ON/OFF), whether it is switched manually
or automatically.
Remote trip
This opens the connected protective device when triggered.
Undervoltage trip
The undervoltage trip triggers the circuit breaker if the voltage drops below 50% of the rated
voltage (0.5 x Ue).
)
Please contact the manufacturer if operating conditions are non-standard.
Further technical data is given in the STAHL catalogue or is available upon request.
)
The temperature class depends upon where the protective enclosure is installed.
)
Change the Miniature Circuit-Breaker at the end of its service-life to guarantee ongoing
protection!
)
Upstream fuse/downstream Miniatur Circuit-Breaker for back-up protection I
cc max
: 100
kA (80 kA, 400 V with fuse)
Rated operating current
Rated current
[A]
AC 14
240 V AC
5 A
DC 12
60 V DC
1 A
DC 12
48 V DC
2 A
DC 12
214 V DC
4 A
Min. switching voltage
AC
24 V
DC
24 V
Min. switching current
AC
10 mA
DC
200 mA
Rated short-circuit limit current:
back-up protection via fusible link
6 A gG
1 kA
Rated voltage
AC
110/415 V
DC
110/125 V
AC
24/60 V
DC
24/48 V
Tripping time
< 10 ms
Rated voltage
AC
230 V
AC/DC
12 V
AC/DC
24 V
AC/DC
48 V
Tripping time
< 150 ms