Installation
10
149915 / 8562606300
2012-08-16·BA00·III·en·06
Residual current circuit-breaker with
integral overcurrent protection
8562/5
8
Installation
8.1 Main Connection
8.2 Rated connection cross-section
Solid, stranded or finely stranded copper wires can be used. 1 or 2 wires of the same
cross-section can be fitted under one terminal. Both wires must be made of the same
material. No preparation is necessary prior to connecting the wires.
Connect the cables with particular care.
Choose suitable cables and route them accordingly to ensure that the maximum
permissible conductor temperatures are not exceeded.
To ensure that creepage distances are maintained remove precisely 10, 17 or 21 mm of
insulation (see chapter “Rated connection cross-section“).
The conductor must not be damaged (scored) when stripping the insulation!
Only heat-resistant cables must be used, if connected directly.
When terminal sleeves are fitted, they must be applied with a suitable tool.
Conductor
Main contact terminals
Auxiliary contact terminals
single-wire
2 x 1.5 ... 10 mm
2
*
04935T00
2 x 0.75 ... 2.5 mm
2
04937T00
1 x 10 mm
2
(bend the end of the
conductor)
04938T00
04939T00
stranded or
flexible-stranded
2 x 1.5 ... 6 mm
2
04940T00
2 x 0.75 ... 1.5 mm
2
04941T00
Permissible tightening
torques for the options
mentioned*
1.8 ... 2.0 Nm
1.0 ... 1.2 Nm
*Permissible tightening
torques for 10 mm
2
single-wire cable
2.5 Nm