background image

145290 / 8491602300

2020-04-21·BA00·III·en·04

Maintenance, Overhaul, Repair  

13

EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN

Signal Horn 105 dB(A)

Series 8491/2

9.1

Troubleshooting

If the error cannot be eliminated using the mentioned procedures:

• Contact R. STAHL Schaltgeräte GmbH.

For fast processing, have the following information ready: 

• Type and serial number of the device

• Purchase information 

• Error description 

• Intended use (in particular input / output wiring)

10

Maintenance, Overhaul, Repair

10.1 Maintenance

• Consult the relevant national regulations to determine the type and extent of  

inspections.

• Adapt inspection intervals to the operating conditions.

• Perform maintenance and repair work in accordance with IEC 60079-17 and  

IEC 60079-19.

At a minimum, check the following points during maintenance on the device:

• Whether the clamping screws holding the electrical lines are fitted securely

• Whether the device enclosure and/or protective enclosure has/have cracks or other 

visible signs of damage 

• Whether the seals have aged or been damaged 

• Compliance with the permissible temperatures (according to EN 60079)

• Whether the device is used as intended and functions properly

Error

Cause of error

Troubleshooting

Signal horn does  

not work

Signal horn element is  

broken

Return signal horn to R. STAHL

Signal horn connected  

incorrectly

Have the signal horn connected  

by qualified personnel

No power supply

Ensure that there is a power supply

Signal horn volume 

too low

Insufficient power supply

Ensure sufficient power supply

CAUTION

Risk of electric shock or malfunction of the device due to unauthorized work!

Non-compliance can result in light injuries!

• Before carrying out work on the device, switch off voltage supply.

• Work performed on the device must only be carried out by authorized 

and appropriately trained qualified electricians.

Observe the relevant national regulations in the country of use.

Summary of Contents for 8491/2 Series

Page 1: ...EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN Operating instructions Additional languages r stahl com EN Signal Horn 105 dB A Series 8491 2...

Page 2: ...ls on the device 5 3 Safety notes 5 3 1 Operating instructions storage 5 3 2 Personnel qualification 5 3 3 Safe use 6 3 4 Modifications and alterations 6 4 Function and device design 7 4 1 Function 7...

Page 3: ...Further documents Data sheet For documents in additional languages see r stahl com 1 4 Conformity with standards and regulations See certificates and EU Declaration of Conformity r stahl com Further n...

Page 4: ...d source of danger damage Consequences of danger Taking countermeasures to avoid the danger or damage Symbol Meaning Tips and recommendations on the use of the device Danger due to explosive atmospher...

Page 5: ...stallation Commissioning Maintenance repair cleaning Specialists who perform these tasks must have a level of knowledge that meets applicable national standards and regulations Additional knowledge is...

Page 6: ...nting and installation performed only by qualified and authorised persons see chapter Qualification of the personnel The device is only to be installed in areas for which it is suited based on its mar...

Page 7: ...ersons are present Gas explosion protection is achieved using an mb encapsulation and through eb increased safety in the area of the electrical connection Dust explosion protection is provided by the...

Page 8: ...able Back up fuse to be installed in an enclosure with Increased safety e g type 8118 113 303 Duty cycle 70 ED Acoustic data Volume max 105 dB A 1 m Ambient conditions Ambient temperature 40 to 50 C M...

Page 9: ...ore the device in a dry place no condensation and vibration free Do not drop the device 7 Mounting and installation 7 1 Dimensions fastening dimensions 7 2 Mounting dismounting operating position 7 2...

Page 10: ...rical line 7 2 3 Mounting the horn The cable entry is included 11097E00 Cut the cable electrical line to a suitable length to ensure a correct connection Insert cable electrical line through the cable...

Page 11: ...the seal Remove the cable sheath over a length of approx 35 mm Strip wires over a length of approx 7 mm Lead the cable through the provided passage into the connection chamber Unlock the screwless ter...

Page 12: ...onductors have been clamped firmly Monitor if all cable entries and stopping plugs have been tightened securely Observe the line voltage Use only in a completely installed state 9 Operation DANGER Exp...

Page 13: ...screws holding the electrical lines are fitted securely Whether the device enclosure and or protective enclosure has have cracks or other visible signs of damage Whether the seals have aged or been da...

Page 14: ...l Please print this file off Send the device along with the RMA form in the packaging to R STAHL Schaltger te GmbH refer to chapter 1 1 for the address 11 Cleaning Clean the device only with a cloth b...