Floodlight

Series 6521/5

For further technical data, see r-stahl.com.

Technical Data
Electrical data

Rated operational 

voltage

220 to 240 V AC, 50 Hz

Inrush current

Power factor

High-pressure lamps compensated cos 

p

 > 0.9

Protection class

I (with internal and external PE connection)

Ambient conditions

Ambient temperature

Mechanical data

Degree of protection IP66 to EN 60529
Impact strength  

(IK code)

IK10 (IEC 62262)

Material

Enclosure

Window

Safety glass; resistant to thermal shocks

Seal

Silicone

Reflector

Aluminium, anodised

Luminaire locking

Allen screws, M6, stainless steel

Hinged enclosure cover

Mounting / Installation

Operating position

Horizontal luminaire axis

Cable entry

Standard

1 x M20 x 1.5 cable gland, clamping area Ø 6 to 13 mm

1 x M20 x 1.5 stopping plug

1 x M20 x 1.5 cable gland (with blind plugs)

Special

specific costumer order possible

Connection

3-pole (L1, N, PE)

Spring clamp terminals

0.5 to 2.5 mm

2

 (solid)

0.75 to 2.5 mm

2

 (finely stranded)

(2 free clamping units per pole available)

Mounting

U-shaped holding bracket made of stainless steel, continuously swivelable 

around the rotary axis of the flood lights.

Size

HST (High-pressure sodium vapour lamp)
Power

I

N

3

250 W

400 W

3.0 A

4.45 A

Size

Lamp

Power

Ambient temperature

3

HST

250 W

-40 to +55 °C

400 W

-40 to +55 °C

6521/5...-...-...-1-...-..

Sheet steel powder coated RAL 7032 (pebble-grey)

6521/5...-...-...-3-...-..

Stainless steel 1.4301 (V2A)

6521/5...-...-...-4-...-..

Stainless steel 1.4404 (V4A)

Summary of Contents for 6521/5 Series

Page 1: ...EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN Operating instructions Additional languages r stahl com EN Floodlight Series 6521 5...

Page 2: ...vice 5 3 Safety notes 5 3 1 Operating instructions storage 5 3 2 Safe use 5 3 3 Intended Use 6 3 4 Modifications and alterations 6 4 Function and device design 6 4 1 Function 6 4 2 Device design 7 5 T...

Page 3: ...stahl com 1 4 Conformity with standards and regulations See certificates and EU Declaration of Conformity r stahl com The device has IECEx approval For certificate please refer to the IECEx homepage...

Page 4: ...rce of danger damage Consequences of danger Taking countermeasures to avoid the danger or damage Symbol Meaning Tips and recommendations on the use of the device Danger due to explosive atmosphere Dan...

Page 5: ...al data We cannot be held liable for damage to the device caused by incorrect or unauthorised use or non compliance with these operating instructions For assembly and installation Observe national ass...

Page 6: ...ge The floodlight 6521 5 is equipment used for lighting areas work equipment and objects It can be used indoors and outdoors DANGER Explosion hazard due to modifications and alterations to the device...

Page 7: ...and device design 7 EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN EN Floodlight Series 6521 5 4 2 Device design 17215E00 1 Luminaire enclosure 4 Mounting bracket 2 Cable gla...

Page 8: ...II 3G Ex nAc IIC T1 Dust T V 12 ATEX 7174 E II 2D Ex tb IIIC T1 C IP66 1 HST High pressure sodium lamps Notice Only lamps of the type OSRAM VIALOX T SUPER can be used Certifications and certificates...

Page 9: ...locking Allen screws M6 stainless steel Hinged enclosure cover Mounting Installation Operating position Horizontal luminaire axis Cable entry Standard 1 x M20 x 1 5 cable gland clamping area 6 to 13...

Page 10: ...and national safety and accident prevention regulations to maintain the explosion protection Select and install the electrical device so that explosion protection is not affected due to external infl...

Page 11: ...mounting attachment DANGER Explosion hazard due to inadmissible heating Non compliance results in severe or fatal injuries Avoid external heat sources and or direct sunlight risk of change of temperat...

Page 12: ...Do not clamp any part of the conductor insulation Do not mix up the conductors Observe the technical regulations when connecting the conductor Clamp the conductor firmly Connection terminals DANGER R...

Page 13: ...Loop in loop out wiring with max 12 A possible 21967E00 Insert the cable 17217E00 Connect the conductor to the spring clamp terminal Check that the cable is clamped properly The unit must be connecte...

Page 14: ...type of protection the required temperature resistance the IP degree of protection according to the rating plate the operating instructions of the cable entries and stopping plugs the required tighten...

Page 15: ...entries and stopping plugs have been tightened firmly Check if all conductors have been clamped firmly Check if the line voltage and the rated operational voltage are consistent Check if the permissi...

Page 16: ...mp was incorrectly inserted Insert the lamp correctly The lamp is defective Replace the lamp The control gear is defective Replace the control gear DANGER Explosion hazard due to hot built in componen...

Page 17: ...damage Whether the seal shows signs of ageing or damage completely replace enclosure components with damaged foamed seal Whether the device is clean inside and out Whether the permissible temperatures...

Page 18: ...er te GmbH refer to chapter 1 1 for the address 11 Cleaning To avoid electrostatic charging the devices located in potentially explosive areas may only be cleaned using a damp cloth When cleaning with...