Floodlight LED
Series 6525/2
Technical Data
Electrical data
Control gear
Rated voltage
6525/21..:
AC: 110 to 277 V ±10%; 50 to 60 Hz
DC: 127 to 250 V
6525/22..:
without DALI
AC: 110 to 277 V ±10%; 50 to 60 Hz
DC: 175 to 275 V
with DALI
AC: 100 to 277 V ±10%; 50 to 60 Hz
DC: 99 to 275 V
Rated current
Inrush current
6525/21..:
6525/22..:
Variant 100 W
Variant 160 W
Variant 225 W
110 V AC
≤ 1.05 A
≤ 1.61 A
≤ 2.38 A
230 V AC
≤ 0.50 A
≤ 0.74 A
≤ 1.10 A
277 V AC
≤ 0.42 A
≤ 0.63 A
≤ 0.91 A
Inrush current
light fittings per circuit breaker
Variant Voltage
I
peak
Δt
B10 B16 B20 B25 C10 C16 C20 C25
100 W,
160 W
110 V AC 32 A
560
m
s
3
5
6
7
3
5
9
9
230 V AC 57 A
500
m
s
2
4
5
6
4
7
9
11
277 V AC 75.5 A 550
m
s
1
2
3
4
2
4
7
7
225 W
110 V AC 36 A
500
m
s
2
4
5
6
3
4
7
7
230 V AC 64 A
500
m
s
2
3
4
6
4
6
8
10
277 V AC 78.5 A 550
m
s
1
3
3
4
3
5
8
8
Inrush current
light fittings per circuit breaker
Variant Voltage
I
peak
Δt
B10 B16 B20 B25 C10 C16 C20 C25
100 W
110 V AC 0 A
> 100
m
s 6
10 13 16 7
11 14 17
230 V AC 0 A
> 100
m
s 15 24 30 37 16 25 31 38
277 V AC 0 A
> 100
m
s 19 31 39 49 20 32 40 50
160 W
110 V AC 0 A
> 100
m
s 4
7
8
11 5
8
9
12
230 V AC 0 A
> 100
m
s 10 16 20 25 11 17 21 26
277 V AC 0 A
> 100
m
s 13 21 26 32 14 22 27 33
225 W
110 V AC 0 A
> 100
m
s 3
5
6
8
4
6
7
9
230 V AC 0 A
> 100
m
s 7
11 14 17 8
12 15 18
277 V AC 0 A
> 100
m
s 9
15 18 23 10 16 19 24