Page | 17
SECTION 7
Maintenance
There are no wear items in the Parallel Output Redundant Cabinet that require periodic
replacement. However, regular care will assure maximum availability of power.
Keep the ventilation openings in the cabinet free of dust and debris.
Wipe the cabinet exterior with a soft cloth, slightly dampened with water, to remove dust.
Consider performing periodic infrared temperature measurements on the circuit breaker
terminations. This will require access to the cabinet interior. There are hazardous voltages
present and any work must be performed using caution. Only trained service personnel
should perform this work. Elevated temperatures of the terminations usually are the sign of
a loose connection, but can also signal that a breaker is failing. Loose connections should
only be serviced after removal of power.
If the system is powered down, consider removing accumulated dust from the cabinet
interior using a vacuum cleaner.
SECTION 8
Parallel Output Redundant Cabinet Technical Specifications
Table 6 - Technical Specifications
Environmental
Altitude
De-rate load capability above 1000 meters 1% per 100
meters.
Operating Temperature
40
o
C Maximum
Humidity
Maximum 95%RH, Non-condensing
Rated Input voltage
480/277
Rated Input Current
18A
Input Breaker Rating
25A
Rated Output voltage
208/120
Rated Output Current
40A
Output Breaker Rating
50A
Minimum Wire
Size INPUT
#12 AWG
OUTPUT
#8 AWG