Voltage:

Voltage at motor must be not more than 10% above or below motor name-
plate rated voltage or motor may overheat, causing overload tripping and re-
duced component life. If voltage is less than 90% or more than 110% of rated
voltage when motor is running at full load, consult power company.

Values given in tables below are for PUMP MOTOR ONLY. If addi-

tional spa accessories are installed on pump motor circuit (heater,

blower, etc.), include their amperage draw when figuring wire and circuit
breaker sizes.

L2

B

A

L1

Lo

Hi

Timer Motor

Supply

Lo

Hi

Circuit

Protector

Remote

SPDT

Switch

Ground

(Green)

Common

Remote Switching For 2-Speed Pumps

Timer (optional)
Low Speed Only

Minimum switch and timer amp rating must equal Branch Fuse Rating 
given in "Recommended Circuit Breaker Size and Wiring Data" table.

Branch

AWG (mm

2

) Wire Gauge Size

Full

Circuit

Dist in Ft. (M) - Service to Motor

Model

Motor

Load

Breaker

0-100

101-200

201-300

Temp

No.

HP

Volts

Amps

Amp Rating

(0-30)

(31-60)

(61-90)

Deg. C.

Single Speed Pumps:

JSACL-A

1/2

115

7.0

15

14 (2.0)

12 (3.0)

10 (5.5)

75

JSADL-2A

3/4

115

9.0

15

14 (2.0)

14 (2.0)

10 (5.5)

75

JSAEL-2A

115

12.0

15

14 (2.0)

10 (5.5)

8 (8.4)

75

JSAFL-A

1-1/2

115/230

16.4/8.2

25/15

10/14 (5.5/2.0)

8/14 (8.4/2.0)

6/12 (14/3.0)

75

JSAEFL-A

1-1/2 

115/230

14.4/7.2

20/15

12/14 (3.02.0)

8/14 (8.4/2.0)

6/14 (14/2.0)

75

JSADL-230A

3/4

230

4.8

15

14 (2.0)

14 (2.0)

14 (2.0)

75

JSAEL-230A

230

6.1

15

14 (2.0)

14 (2.0)

14 (2.0)

75

Two Speed Pumps:

JSAYDL-A

3/4-1/8

115

9.0/2.7

15

14 (2.0)

12 (3.0)

10 (5.5)

75

JSAYDL-LA

3/4-1/8

115

9.0/2.7

15

14 (2.0)

12 (3.0)

10 (5.5)

75

JSAYEL-A

1-1/6

115

11.7/3.4

15

14 (2.0)

10 (5.5)

8 (8.4)

75

JSAYEL-LA

1-1/6

115

12.0/3.3

15

14 (2.0)

10 (5.5)

8 (8.4)

75

JSAYFL-LA

1

1

- 1/6

115

16.6/3.6

25

10 (5.5)

8 (8.4)

6 (14)

75

JSAYDL-230A

3/4-1/8

230

4.7/1.4

15

14 (2.0)

14 (2.0)

14 (2.0)

75

JSAYEL-230A

1-1/6

230

6.3/1.8

15

14 (2.0)

14 (2.0)

14 (2.0)

75

JSAYFL-230A

1

1

- 1/6

230

8.1/1.7

15

14 (2.0)

14 (2.0)

12 (3.0)

75

JSAYDL-220A

3/4-1/8

220

5.4/1.4

15

14 (2.0)

14 (2.0)

14 (2.0)

75

JSAYEL-220A

1-1/6

220

6.3/1.8

15

14 (2.0)

14 (2.0)

14 (2.0)

75

TABLE I - RECOMMENDED CIRCUIT BREAKER SIZE AND WIRING DATA FOR 60 Hz MOTORS

Summary of Contents for DURA-JET JSACL

Page 1: ...p 293 Wright Street Delavan WI 53115 North America 800 752 0183 FAX 800 582 2217 International 262 728 5551 FAX 262 728 4461 TELEX ITT 4970245 www sta ritepool com Union City TN Delavan WI Mississauga...

Page 2: ...AL CAREFULLY The Sta Rite JS Series Tub Pump Is designed to circulate hot water in spas and hot tubs Is an excellent performer durable reliable Table of Contents Safety Instructions 3 Installation 4 E...

Page 3: ...BE SURE all air is out of system before operating or testing equipment Before pressure testing make the following safety checks Check all clamps bolts lids and system accessories before testing Relea...

Page 4: ...r compartment Piping Use flexible or rigid PVC pipe for connections to pump Suction discharge piping gate valves will allow removal for servicing Use at least 1 1 2 IPS pipe Fittings restrict flow for...

Page 5: ...le I Page 6 gives correct wire and circuit breaker sizes for the pump alone If other lights or appliances are also on the same circuit be sure to add their amp loads to pump amp load before figuring w...

Page 6: ...HP Volts Amps Amp Rating 0 30 31 60 61 90 Deg C Single Speed Pumps JSACL A 1 2 115 7 0 15 14 2 0 12 3 0 10 5 5 75 JSADL 2A 3 4 115 9 0 15 14 2 0 14 2 0 10 5 5 75 JSAEL 2A 1 115 12 0 15 14 2 0 10 5 5...

Page 7: ...ng when system is not in use Failure to do so can allow air to enter system causing pump to lose its prime Keep water temperature at 104 F 40 C or below Age or health conditions may require a lower te...

Page 8: ...e drive ring seats and seals 6 Carefully remove four motor throughbolts from seal plate Figure 3 remove seal plate and use a screwdriver to tap ceramic seat out from the rear Figure 4 Do not damage se...

Page 9: ...f possible store chemicals in another room Allowing pump to freeze will damage pump and void warranty Drain all water from pump and piping when expecting freezing temperatures or when storing pump for...

Page 10: ...the low point of the spa piping to help drain spa system 6 Before restarting replace all plugs and make sure all pipe connections are tightly sealed Startup for Winterized Equipment 1 Remove any tempo...

Page 11: ...use poor flow and poor jet action 2 Consult dealer installer or service representative C EXCESSIVE AIR IN SYSTEM PUMP LOSES PRIME 1 Make sure water level in spa is at least 2 51 mm above top of jets w...

Page 12: ...1 JSAEFL A 11 2 AE910FLL 17301 0101 230 Volt Single Speed JSADL 230A 3 4 AS923DL C105 228PB JSAEL 230A 1 AS923EL C105 228P 230 Volt Two Speed JSAYDL 230A 3 4 AS923DL Y C105 228PB JSAYEL 230A 1 AS923EL...

Page 13: ...13...

Page 14: ...14...

Page 15: ...15...

Page 16: ...pur chaser Purchaser only Sta Rite shall have the option to re pair or replace the defective product at its sole discre tion Purchasers must pay all labor and shipping charges nec essary to replace t...

Reviews: