Change-of-state output: Execute this command once the data buffer changes
Polling output: The command is put in the polling list and executed periodically
Initialization output: Execute the command once, when power is on
Disable output: The command will not be sent.
Memory starting address of sending data
: Set the start address in data buffer of output data of this command
and the range is 3000~4999;
Modbus register starting address of sending data
: This parameter is automatically calculated and used for
register addressing;
Sending data length (BYTE)
: Set the length of output data of this command;
Sending data length (WORD)
: This parameter is automatically calculated. 1 word=2 byte;
Memory starting address of receiving data
: Set the start address in data buffer of input data of this command
and the range is 0~2999;
Modbus register starting address of receiving data
: This parameter is automatically calculated and used for
register addressing;
Receiving data length (BYTE)
: Set the length of input data of this command;
Receiving data length (WORD)
: This parameter is automatically calculated. 1 word=2 byte;
Command index
: This parameter is automatically calculated and it indicates the index of this command in the
configured command list.
5.2.2.5 Delete Command
Select the command you want to deleteand, right click on it and select "Delete Command". You can also do this through
the menu bar or tool bar.
5.2.2.6 Delete Node
Select the node you want to delete, right click on it and select "Delete Node". You can also do this through the menu bar
or tool bar. When a node is deleted, all commands under this node will be also deleted.