MPG-1 Advanced Settings (cont)

Bi-Directional Energy Flow (Signed Mode)
If you have energy flowing in both directions in the case of distributed energy resourses (solar, wind, etc), the MPG-1 can
provide both positive and negative pulses.  This is known as the 

Signed

 mode, meaning that "kWh Delivered" (

from

 the

utility 

to

 the customer) is positive or forward flow, and "kWh Received" (

from

 the customer 

to

 the utility) is negative or

reverse flow.
The Pulse Value Setting (set by dip switches S1.1-S1.3) is the same for both positive and negative values.

To enter the functional or operational mode into the MPG-1, use the S and N commands.  Press N <Enter> to set the
MPG-1 in the Normal mode.  Press S <Enter> to set the MPG-1 in the Signed mode.  The serial link to the MPG-1 will
return "Output Mode: Signed".  To read what mode the MPG-1 is currently in, press R <Enter>.  The serial link will return
the mode stored in the MPG-1.  For example, "Output Mode: Normal" will be returned. Case does not matter.

Form C Signed mode - A positive energy value received from the meter is added to the positive Accumulated Energy
ReAER). Negative energy values received are ignored.  Only Form C toggle pulses are generated on the KYZ
output for Positive energy flow.  See Figure 3 below.

Form A Signed mode - A positive energy value received is added to the positive Accumulated Energy ReAER).
A negative energy value received is added to the negative Accumulated Energy Register(-AER).  When either register
equals or exceeds the Pulse Value setting, a pulse of the corresponding sign is outputted on the correct line. Pulses in
this mode are Form A (2-wire) "Fixed" only.  K-Y pulses are Positive pulses and K-Z pulses are negative pulses.  They
share a common K terminal on the output.  Set the pulse value with dip switches S1.1 thru S1.3.  Set the pulse width
using dip switches S1.5 and S1.6. See Figure 4 below.

T1

Figure 4: 2-Wire (FORM A) FIXED Output Operation

K-Y Out

Open

Closed

Open

Closed

K-Z Out

KY closure time

In Signed mode, with a Form A output mode selected, the K-Y output pulse represents
positive (or kWh delivered) energy; K-Z output pulse represents negative (or kWh received)
energy.

(Positive)

(Negative)

Figure 3: 3-Wire (FORM C) TOGGLE Output Operation

K-Z Out

K-Y Out

Open

Open

Closed

Closed

Positive Energy Pulse Outputs Only

Positive and Negative Energy Pulse Outputs

In Signed mode, with a Form C output mode selected, the K-Y and K-Z output pulses
represent positive (or kWh delivered) energy; Negative (or kWh received) energy is ignored.

Positive Flow

Positive Flow

Negative Flow

Positive Flow

Positive Flow

Negative Flow

Summary of Contents for MPG-1

Page 1: ...s hot wire to the L2 terminal Connect the NEU terminal to the AC supply s neutral wire Connect GND to electrical system Ground METER INPUT The MPG 1 receives data from a Zigbee equipped AMI electric m...

Page 2: ...tate Instruments div 6230 Aviation Circle Loveland CO 80538 970 461 9600 970 461 9205 fax www solidstateinstruments com MPG 1WiringDiagram vsd AMI Electric Meter w Zigbee Radio K1 Z1 Y1 K2 Z2 Y2 Out 1...

Page 3: ...pulse output mode that emulates the standard KYZ 3 Wire electric meter output It toggles back and forth to the opposite state each time a pulse is generated by the MPG 1 Even though there are three w...

Page 4: ...the calculation by the MPG 1 s processor is for pulse output timing that exceeds 15 pulses per second the MPG 1 will light the RED comm LED indicating an overflow error and that the pulse value is to...

Page 5: ...factory for technical support at 970 461 9600 In the Fixed output mode shown in Figure 2 below an output pulse K Y closure only is a fixed width T1 each time the output is triggered The pulse width cl...

Page 6: ...decimal A0 If the multiplier is one 1 you then know that either this is a self contained meter and a multiplier of 1 is correct OR that this is an instrument rated meter and the utility does NOT send...

Page 7: ...currently programmed into the MPG 1 press R and Enter The serial link will return the following Multiplier 1 Pulse Value 10 Watt hours Output Mode Normal Output Form C Dongle Mode Normal Reset Time 1...

Page 8: ...output for Positive energy flow See Figure 3 below Form A Signed mode A positive energy value received is added to the positive Accumulated Energy Register AER A negative energy value received is add...

Page 9: ...MPG 1 will return the following Filter Setting 5 XML Dongle Reset V2 11 Firmware implements a XML Dongle reset feature that will reset the dongle if the dongle received a pre defined number of transm...

Reviews: