
9
installation
Motor Wiring
Wire motor leads as shown on the motor nameplate matching the supply
voltage. Do not deviate from the motor nameplate wiring.
Either of following symbols may be shown on the motor nameplate –
Δ, Δ Δ,
Y
, or
YY
. These symbols represent how the motor is constructed on the inside
and in no way have anything to do with a Delta or Wye electrical distribution
system serving the motor.
When using a starter:
• Set motor overload protection to 110% of motor nameplate amps.
This setting allows the fan motor to operate during cooler weather.
During cooler weather it is common for the motor to draw 6 to 10%
higher than nameplate amps. High amps are common during tower
commissioning when the tower is dry and the ambient air temperature
is cool.
Do not start the motor more than four to five times per hour. Short
cycling the tower will cause fuses, breakers or O.L.s to operate and
will decrease motor life.
When using a two-speed starter:
• Motor rotation must be the same at slow speed and high speed.
• Single winding motor requires a starter with a shorting contactor.
• Two-winding motor requires a starter with out a shorting contactor.
• All two-speed starters must have a 20 second time delay relay when
switching from high speed to low speed.
Do not start the motor more than four to five times per hour (each
low speed start and each high speed start count as one start).
When using a VFD:
Before beginning, ensure that the motor is rated for “Inverter Duty”
per NEMA MG-1, part 31.
• Set the VFD solid state overload protection to 119% of motor name-
plate amps and set “maximum current parameter” in the VFD to motor
nameplate amps. “Maximum current parameter” will reduce fan speed
and limit amp draw to nameplate amps during cold weather opera-
tion. If furnished with a mechanical O.L. set this at 110% over motor
nameplate amps.
Note
Note
Note
➠