Freezing Weather Operation

During operation in subfreezing weather, the opportunity exists for ice to form 
in the colder regions of the fluid cooler. Primary concerns are to protect the 
heat transfer coil from freezing and prevent the formation of destructive ice 
on the fluid cooler air inlet and louvers. Your understanding of cold weather 
operation will be enhanced if you read 

Marley Technical Report H-003

 

“Cool-

ing Towers and Freezing Weather”

.

It is the operator's responsibility to prevent the formation of destruc-
tive (hard) ice on the fluid cooler air inlet louvers. Certain guidelines 
should be followed:

 1.  Do not allow the fluid cooler’s leaving process fluid temperature to drop 

below 50°F. If low temperature operation is necessary or beneficial to 
your process, establish the minimum allowable level as follows:

    During the first coldest days of operation, observe whether any ice is 

forming on the louver face, particularly near the bottom part of the louver 
face. If hard ice is present on the louvers, you must increase the allowable 
cold water temperature.

2.    As cold air enters the louvers, it causes the water flowing over the coil(s) 

to be drawn inward toward the center of the fluid cooler. Thus, under fan 
operation, the louvers and lower periphery of the fluid cooler structure 
remain partly dry, seeing only random splashing from within the fluid 
cooler — plus normal atmospheric moisture from the entering air. Such 
lightly wetted areas are most subject to freezing.

    Therefore, if excessive ice forms on the louvers, stop the fan for a few 

minutes. With the fan off, the water flow will increase in the vicinity of the 
louvers and reduce the ice buildup. 

Intermittent Freezing Weather Operation:

If periods of shutdown (nights, weekends, etc.) occur during freezing weather, 
measures must be taken to prevent the water in the cold water basin and all 
exposed pipework from freezing. Several methods are used to combat this, 
including Marley automatic basin heater systems and pump freeze protection 
systems.

Note

operation

Summary of Contents for Marley LW032 B Series

Page 1: ...LW fluid cooler INSTALLATION OPERATION MAINTENANCE Z1047819_C ISSUED 4 2019 READ AND UNDERSTAND THIS MANUAL PRIOR TO OPERATING OR SERVICING THIS PRODUCT user manual...

Page 2: ...er installation and operation of your fluid cooler Carefully read the manual before installation or operation of the fluid cooler and follow all instruc tions Save this manual for future reference Not...

Page 3: ...If you have questions about the operation and or maintenance of this fluid cooler and you don t find the answers in this manual please contact your sales representative When writing for information o...

Page 4: ...tance and direction to avoid the possibility of contaminated discharge air being drawn into building fresh air intake ducts The purchaser should obtain the servicesofaLicensedProfessionalEngineerorReg...

Page 5: ...assemblies only during factory assembly If a forklift is used to lift from the base of the equipment ensure forks extend completely underneath the unit and past the basin flange on the opposite side R...

Page 6: ...ion flat washers between the bolt head and the fluid cooler basin flange 3 Attach makeup water supply piping to appropriately sized float valve connection Attach the drain and overflow piping accordin...

Page 7: ...on the motor and mechanical equipment Electrical savings can be large dur ing periods of low ambient temperature when the cooling requirement can be satisfied at reduced speeds LW fluid coolers use El...

Page 8: ...designed for synchronous variable speed operation of all fans 1 Spin the fan s manually to assure that all fan blades properly clear the inside of the fan cylinder s 2 Momentarily bump energize the mo...

Page 9: ...initial pump down may be insufficient to open the float valve However its operation can be checked by pressing down on the operating lever to which the stem of the float valve is attached The float v...

Page 10: ...ll rise If the heat load reduces the cold process fluid temperature will reduce Note that the number of degrees range through which the fluid cooler cools the process fluid is established by the syste...

Page 11: ...to premature scaling of the coil surface Motor cycling limits apply Dampers If equipped the positive closure damper system is designed to help prevent heat loss from the coil due to air movement caus...

Page 12: ...face particularly near the bottom part of the louver face If hard ice is present on the louvers you must increase the allowable cold water temperature 2 As cold air enters the louvers it causes the w...

Page 13: ...industrial antifreeze solutions is not possible the system must be operated to meet both of the following conditions at all times 1 Maintain sufficient flow rate through the coil 2 Maintain sufficien...

Page 14: ...0 with hardness and alkalinity levels between 100 and 300 ppm expressed as CaCO3 Chlorine if used shall be added intermittently with a free residual not to exceed 1 ppm maintained for short periods E...

Page 15: ...with various cooling ranges Range Difference between hot water temperature coming to the fluid cooler and cold water temperature leaving the fluid cooler EXAMPLE 530gpmrecirculatingwaterrate 18 Fcooli...

Page 16: ...equipment PPE as directed by their facility safety officer Fluid coolers must be visually inspected regularly to assess signs of bacte rial growth appearance of debris and scale on drift eliminators a...

Page 17: ...over frame and slide downward until door seats in trough Replace doors prior to operation Heat Transfer Fill Media Removal and Replacement Fill edges can be very sharp and can cut skin if proper prot...

Page 18: ...to fluid cooler operation Incorrect installation may result in excessive drift rates and fan inefficiency To ensure packs are reinstalled in the correct orientation it is recommended that one pack is...

Page 19: ...ne 12 for specific frequency recommendations Consult a knowledgeable water treatment professional to maintain fluid cooler hygiene If equipped the damper actuator and assembly should be cycled open an...

Page 20: ...xtended period of time it is rec ommended that the recirculating water system be drained Leave the basin and pump drains open During shutdown follow recommendations in the Fluid Cooler Inspection and...

Page 21: ...Damper actuators should be removed and stored in a dry location to prevent condensation buildup inside the actuator Internal Protection of Coil All of the coil inlet and outlet connections should be s...

Page 22: ...be shipped within 24 hours by air freight if necessary However you would obviously benefit from anticipating your need in advance thus avoiding the cost of special handling Be sure to mention your fl...

Page 23: ...your product ever reaches the limit of its service life we recommend that you investigate the cost of rebuilding before you routinely order a new replacement fluid cooler Numerous technical reports ar...

Page 24: ...ESERVED In the interest of technological progress all products are subject to design and or material change without notice LW fluid cooler US E R MAN UAL SPX COOLING TECHNOLOGIES INC 7401 WEST 129 STR...

Reviews: