ENGINEERING DATA
MODEL
HPR25
HPR35
HPR50
SPECIFICATIONS
Rated Capacitya
- (scfm)
25
35
50
Inlet /Outlet Connections - (inches)
3/4
3/4
3/4
Dimensions
Height - (inches)
22.2
22.2
22.2
Length - (inches)
15.5
15.5
19.7
Width - (inches)
14.5
14.5
19.7
Power Supply - (V/Ph/Hz)
115/1/60
115/1/60
115/1/60
Refrigerant Compressor Rating - (hp)
1/4
1/4
1/3
Input Power - (kW)
0.47
0.47
0.63
Refrigerant Type
b
R-134a
R-134a
R-134a
a Rating c
onditions are 100°F inlet temperature, 100 psig inlet pressure, 100% inlet relative humidity, 100°F ambient temperature @ 60Hz. Per CAGI ADF-100.
b
Refer to dryer data plate for refrigerant charge.
MODEL
HPR25, HPR35, HPR50
MINIMUM - MAXIMUM OPERATING CONDITIONS
Min.-Max. Inlet Air Pressure (compressed air at inlet to dryer)
30 - 250 psig
Min.-Max. Inlet Air Temperature (compressed air at inlet to dryer)
40°F - 120°F
Min.-Max. Ambient Temperature
40°F - 110°F
NOTE: Continuous operation in the above maximum and minimum operation conditions is not allowable.