Specifications

Specification Value

Marley 

/

 

Sigma Steel 

Cooling Tower 

/

 

Specifications: Options

 

26

 

Low Noise Tower: 

1.1

 

Add  the  following  at  the  end  of  this 

paragraph:

 

The cooling tower shall be 

quiet  operating,  and  shall  produce  an 

overall level of sound no higher than ____ 

dBA at the critical location indicated on 

the Plans.

   Sound produced by a Sigma Steel tower operating in an unobstructed 

environment will meet all but the most restrictive noise limitations – 

and will react favorably to natural attenuation. Where the tower has 

been sized to operate within an enclosure, the enclosure itself will have 

a damping effect on sound. Sound also declines with distance – by 

about 5 or 6 dBA each time the distance doubles. Where noise at a 

critical point is likely to exceed an acceptable limit, you have several 

options – listed below in ascending order of cost impact: 

 

•  Where only a slight reduction in noise will satisfy — and the source 

of concern is in a particular direction — merely turning the tower may 

be the answer. Less sound emanates from the cased face of the tower 

than does from the air intake face.

   •  In many cases, noise concerns are limited to nighttime, when ambi-

ent noise levels are lower and neighbors are trying to sleep. You can 

usually resolve these situations by using two-speed motors in either 

1800/900 or 1800/1200 RPM configuration; and operating the fans at 

reduced speed without cycling “after hours”. (The natural nighttime 

reduction in wet-bulb temperature makes this a very feasible solution 

in most areas of the world, but the need to avoid cycling may cause 

the cold water temperature to vary significantly.) 

   •  Variable speed drives automatically minimize the tower's noise level 

during periods of reduced load and/or reduced ambient without sacri-

ficing the system's ability to maintain a constant cold water tempera-

ture. This is a relatively inexpensive solution, and can pay for itself 

quickly in reduced energy costs.

   •  Where noise is a concern at all times (for example, near a hospital), 

the best solution is to oversize the tower so it can operate continu-

ously at reduced (1200 or 900 RPM) motor speed even at the highest 

design wet-bulb temperature. Typical sound reductions are 7 dBA at 

2/3 fan speed or 10 dBA at 1/2 fan speed, but larger reductions are 

often possible.

   •  Extreme cases may require inlet and discharge sound attenuator 

sections; however, the static pressure loss imposed by attenuators 

may necessitate an increase in tower size. This is the least desirable 

approach because of the significant cost impact – and because of the 

obstruction to normal maintenance procedures.

    Your Marley representative can help you meet your sound require-

ments.

Summary of Contents for Marley Sigma Marley Sigma Steel

Page 1: ...Marley Sigma Steel CoolingTower Engineering Data Specifications...

Page 2: ......

Page 3: ...m 18 Casing 18 Access 18 Cold Water Collection Basin 19 Scope of Work 19 Specifications Options Control Options Control System 20 Basin Heater 21 Fan Motor Variable Speed Drive 21 Marley Premium VFD S...

Page 4: ......

Page 5: ...rt of the continuing better ment of this Marley product line The Sigma Steel is a galvanized steel field erected general purpose crossflow cooling tower designed to serve normal air conditioning and r...

Page 6: ...model indicates number of cells Change as appropriate for your selection Primary engineering data is per cell 3 Height shown is from base of tower columns to top of fan cylinder 4 Pumping head shown i...

Page 7: ...ain at least 2 0 of clear space at tower endwalls for construction purposes Air inlet faces must have unobstructed air supply If obstructions exist nearby consult your Marley sales representative 4 Op...

Page 8: ...r Marley sales representative 4 Minimum basin depth is 1 6 Basin depth may vary to suit your storage requirements 5 All anchor bolts complete with nut and washer must be furnished by others Bolts must...

Page 9: ...required 4 Marley piping terminates at face of a cast iron flat face flange Bolt circle conforms to class 125 lb ANSI B 16 1 specifications 5 Supports on tower for crossover piping are part of the tow...

Page 10: ...esigner must take care to provide generous air inlet paths and the tower s fan cylinder discharge height should not be lower than the elevation of the top of the enclosure Obtain a copy of Marley Tech...

Page 11: ...u money in the long run both on operation and on maintenance Here are two of the more popular options Two Speed Motors Two speed motors improve operating flexibility by increas ing the number of poten...

Page 12: ...ection that fits your space allot ment and whose power usage is acceptable Limitations on physical size and total operating horsepower avoid the introduction of unfore seen operational and site relate...

Page 13: ...ase is incapable of performing as specified then you will not have received full value for your money Bear in mind that the size and cost of a cooling tower varies directly with its true thermal capab...

Page 14: ...wind load and 5 g seismic load Framing joints shall be made with 1 2 diameter and larger Series 300 stainless steel machine bolts nuts and washers 3 4 Towers of more than one cell shall include galvan...

Page 15: ...surance that the tower can withstand long term operation in a hostile environment but that it will accept many years of inspection and maintenance traffic by your operating personnel Fiberglass reinfo...

Page 16: ...s a crossover pipe to deliver water to both sides of the tower 5 6 The mechanical equipment assembly shall be warranted for no less than five 5 years This warranty shall cover the fan s speed reducers...

Page 17: ...parate external louvers used by others permit water to escape the fill and form ice or produce an unsightly situation adjacent to the tower If you plan to use your tower in the wintertime particu larl...

Page 18: ...d steel shall also be provided 9 0 Access 9 1 There shall be a 33 wide by 61 high access door in each endwall casing to provide access to the interior of the tower Access doors shall be hinged and equ...

Page 19: ...be responsible for the design fabrica tion and delivery of materials to the project site and for the erection of the tower over supports provided by others Unless otherwise specified all external pipi...

Page 20: ...20VAC 50VA control power overload trip alarms and remote temperature control devices The temperature controller shall be adjustable for the required cold water temperature If a thermostatic controller...

Page 21: ...drive shafts The VFD shall catch a fan spinning in the reverse direction without tripping The panel shall include a main discon nect with short circuit protection and external operating handle lockabl...

Page 22: ...is no longer required The fluid cooler manu facturer shall supply VFD start up assis tance Tower vibration testing throughout the speed range is required to identify and lockout any natural frequency...

Page 23: ...assure proper gear box lubrication the VFD sys tem shall de energize the motor once 25 motor speed is reached and cool ing is no longer required The VFD shall include de icing logic with auto canceli...

Page 24: ...the ladder attached to the tower casing This extension shall be long enough to rise from the roof grade level to the base of the tower Anchorage and lateral bracing of the ladder extension shall be by...

Page 25: ...r Distribution System Section The distribution basins shall include galvanized steel covers These covers shall be designed for a uniform live load of 40 psf and shall be easily removable for maintenan...

Page 26: ...usually resolve these situations by using two speed motors in either 1800 900 or 1800 1200 RPM configuration and operating the fans at reduced speed without cycling after hours The natural nighttime r...

Page 27: ...n in the tower Refer to our Stainless Steel Sigma Series in which the use of stainless steel has been maximized Except for valve bodies and Geareducer every steel component of that product line is man...

Page 28: ...66213 UNITED STATES 913 664 7400 spxcooling spx com spxcooling com In the interest of technological progress all products are subject to design and or material change without notice 2008 SPX Cooling T...

Reviews: