Inlet Water Bypass—provision for total water bypass directly into the tower collection basin during cold  

  weather operation.

 

Hoistable Steel Grillage—allows assembling tower at grade on temporary supports and hoisting    

  into final location.

 

Fire Retardant FRP—flame spread rating of 25 or less per ASTM E-84.

 

Control Systems—ranging in sophistication from standard fan starters and disconnects to  

 

  Programmable Logic Controllers that work in conjunction with your building or process system.

 

Variable Speed Drive—the ultimate in temperature control, energy management, and  

 

 

  mechanical equipment longevity

 

 Electric Basin Heater Package—maintains collection basin water temperatures between 40°F  

 

  and 45°F during tower shutdown.

 

Vibration Limit Switch—shuts down the fan motor if excessive vibration occurs. 

 

Solid State Water Level Control Package—monitor basin water level with solenoid-valve water  

 

  makeup. Configurations include makeup along with high and low water level alarm and cutoff  

 

  and electric basin heater cutoff.

 

Magnetrol

®

 Electric Float Switch—monitor basin water level with solenoid-valve water makeup. 

/  Available Options /

W

H

W

TOWER MODELS

TONS

W

H

21120

129-183

12'-8"

7'-2"

21220

186-211

12'-8"

8'-5"

21320

204-256

12'-8"

9'-9"

22120

243-304

14'-1"

8'-6"

22220

312-425

14'-1"

9'-11"

23120

390-475

16'-8"

9'-11"

23220

419-546

16'-8"

11'-3"

24120*

531-836

24'-6"

12'-9"

24220*

796-1047

24'-6"

16'-1"

*Models in this box size require a taller fan cylinder