/  Freeze Prevention  /

When the ambient air temperature falls below 0°C, the 

water in a cooling tower can freeze. 

Marley Technical Report  

#H-003

 

“Operating Cooling Towers in Freezing Weather”

 

describes how to prevent freezing during operation. Ask your 
Marley sales representative for a copy or download from our 
website.

Water collects in the cold water basin during shutdowns, 

and may freeze solid. You can prevent freezing by adding 
heat to the water left in the tower. Or, you can drain the tower 
and all exposed piping at shutdown.

 

Electric Basin Heaters

Provide an electric immersion heater for each cell of the 

tower to prevent freezing of water in the collection basin 
during periods of shutdown. The rod type heater is installed 
in the side of the cold water basin.

 

Each heater will include an integral thermostat, set 

point nominally 4°C but adjustable to suit local operating 
requirements.

Any exposed piping that is still filled with water at 

shutdown —including the makeup water line—should be 
electrically traced and insulated (by others).

1.   Required kw is the amount of heat needed to ma4.5°C basin 

water temperature at the indicated ambient air temperature.

2.  Tank heaters shown are 220 volts, single-phase.

3.   Component  heaters  shown  are  400  volts,  three-phase.  

Options  or  special  heater  selections  may  add  several  weeks  to  

delivery.

4.   Heaters  do  not  operate  continuously.  Heaters  cycle  on  and  off 

automatically as basin water temperature dictates.

5.   Contact your Marley sales representative for selections appropriate 

for other ambient conditions than those shown here.

 

Indoor Tank Method

In this type of system, water flows from an indoor tank, 

through the load system, and back to the tower, where it is 
cooled. The cooled water flows by gravity from the tower to 
the tank located in a heated space. At shutdown, all exposed 
water drains into the tank, where it is safe from freezing.

The table on page 9 lists typical drain-down capacities 

for all Aquatower models. Although we do not produce 
tanks, many of our representatives offer tanks supplied by 
reputable manufacturers.

The amount of water needed to successfully operate 

the system depends on the tower size, flow and the volume 
of water contained in the piping system to and from the 
tower. You must select a tank large enough to contain those 
combined volumes—plus a level sufficient to maintain 
a flooded suction on your pump. Control makeup water 
according to the level where the tank stabilizes during 
operation.

You should always use a bottom outlet for this type of 

piping system. The following table lists the flow capacities for 
bottom outlets.

Basin Heater Selection

Tower 

Model

-12°C Ambient

-25°C Ambient

Tank Heater

Component 

Heater

Tank Heater

Component 

Heater

490A

2 kW

3 kW

2 kW

3 kW

490B

2 kW

3 kW

2 kW

3 kW

492A

2 kW

3 kW

2 kW

3 kW

492B

2 kW

3 kW

2 kW

3 kW

493A

2 kW

3 kW

3 kW

3 kW

493B

2 kW

3 kW

3 kW

3 kW

494A

2 kW

3 kW

4 kW

3 kW

494B

2 kW

3 kW

4 kW

3 kW

494C

2 kW

3 kW

4 kW

3 kW

495A

3 kW

3 kW

6 kW

4.5 kW

495B

3 kW

3 kW

6 kW

4.5 kW

496A

3 kW

4.5 kW

6 kW

6 kW

496B

3 kW

4.5 kW

6 kW

6 kW

Summary of Contents for Marley Aquatower

Page 1: ...MarleyAquatower CoolingTower...

Page 2: ...e all year long Proven Corrosion Protection Thousands of users over more than 40 years confirm the value of heavy galvanizing And Marley s Z 600 is the most effective galvanizing used in the industry...

Page 3: ...r of local distributors can draw from that stock Contact your local distributor or Marley representative They ll be glad to help you choose the proper model for your needs They can also help you with...

Page 4: ...et Install the desired connection and seal the unused opening with the cover plate provided Pump suction should use side outlet See page 9 for size and flow capacities of bottom outlets 7 Overflow is...

Page 5: ...TION BASIN 16mm DIAMETER HOLES TOWER COLLECTION BASIN B NORMAL GAUGE MIN BEARING WIDTH AT EACH ANCHOR BOLT 51 SUPPORT BY OTHERS TOWER COLLECTION BASIN SUPPORTING STEEL PLAN OPTION ONE VIEW B SECTION A...

Page 6: ...irborne trash out of the collection basin and fill area Hot water distribution basin covers are provided as standard equipment to keep the distribution basin free from airborne debris and to reduce th...

Page 7: ...onsist of welded heavy gauge steel wire hoops and spokes hot dip galvanized after fabrication The galvanized steel belt guard encloses both belts and pulleys Guards are easily removed for servicing Co...

Page 8: ...temperature dictates 5 Contact your Marley sales representative for selections appropriate for other ambient conditions than those shown here Indoor Tank Method In this type of system water flows from...

Page 9: ...2 494A 494B 494C 13 6 32 507 32 3 51 5 549 51 7 85 4 613 85 6 127 8 674 495A 495B 18 6 43 6 689 43 8 61 3 727 61 5 116 5 829 116 7 173 3 912 496A 496B 23 6 44 5 863 44 7 64 9 920 65 1 112 8 1026 113 1...

Page 10: ...stainless steel structure Or you can choose a galvanized tower with a stainless steel cold water collection basin Your Marley sales representative can help you choose the amount of corrosion resistanc...

Page 11: ...housing with externally accessible remote oil reservoir for easy maintenance Fill Louvers and Drift Eliminator Fill shall be film type thermoformed PVC with louvers and drift eliminator formed as par...

Page 12: ...BANK WORCESTER WR3 8AB UNITED KINGDOM 44 0 1905 720 200 info uk spx com spxcooling com In the interest of technological progress all products are subject to design and or material change without noti...

Reviews: