SPT WA-S7000E Owner'S Manual & Installation Manual Download Page 9

Safety 

Precautions

 Page 9

Do not apply any permanent inductive or capacitance loads to the circuit without ensuring that this will 

not exceed the permissible voltage and current permitted for the equipment in use. Intrinsically safe 

components are the only types that can be worked on while live in the presence of a flammable 

atmosphere. The test apparatus shall be at the correct rating. Replace components only with parts 

specified by the manufacturer. Other parts may result in the ignition of refrigerant in the atmosphere 

from a leak.

8.Repair to intrinsically safe components 

 

and shall be calibrated to the refrigerant employed and the appropriate percentage of gas (25 % 

maximum) is confirmed. Leak detection fluids are suitable for use with most refrigerants but the use of 

detergents containing chlorine shall be avoided as the chlorine may react with the refrigerant and 

corrode the copper pipe-work. If a leak is suspected, all naked flames shall be removed/ extinguished. 

If a leakage of refrigerant is found which requires brazing, all of the refrigerant shall be recovered from 

the system, or isolated (by means of shut off valves) in a part of the system remote from the leak. 

Oxygen free nitrogen (OFN) shall then be purged through the system both before and during the 

brazing process.  

When breaking into the refrigerant circuit to make repairs or for any other purpose conventional 

procedures shall be used. However, it is important that best practice is followed since flammability is a 

consideration. The following procedure shall be adhered to:

Remove refrigerant; Purge the circuit with inert gas; Evacuate; Purge again with inert gas; Open the 

circuit by cutting or brazing.   

The refrigerant charge shall be recovered into the correct recovery cylinders. The system shall be flushed 

with OFN to render the unit safe. This process may need to be repeated several times. Compressed air or 

10.Detection of flammable refrigerants

The following leak detection methods are deemed acceptable for systems containing flammable 

refrigerants. Electronic leak detectors shall be used to detect flammable refrigerants, but the sensitivity 

may not be adequate, or may need re-calibration. (Detection equipment shall be calibrated in a 

refrigerant-free area.) Ensure that the detector is not a potential source of ignition and is suitable for 

the refrigerant used. Leak detection equipment shall be set at a percentage of the LFL of the refrigerant 

11.Leak detection methods

Check that cabling will not be subject to wear, corrosion, excessive pressure, vibration, sharp edges or 

any other adverse environmental effects. The check shall also take into account the effects of aging or 

continual vibration from sources such as compressors or fans.

9.Cabling

12.Removal and evacuation

Under no circumstances shall potential sources of ignition be used in the searching for or detection 

of refrigerant leaks. A halide torch (or any other detector using a naked flame) shall not be used.

 

being worked upon prior to any removal of sealed covers, etc. If it is absolutely necessary to have an 

electrical supply to equipment during servicing, then a permanently operating form of leak detection 

shall be located at the most critical point to warn of a potentially hazardous situation. 

2)Particular attention shall be paid to the following to ensure that by working on electrical components, 

the casing is not altered in such a way that the level of protection is affected. This shall include damage 

to cables, excessive number of connections, terminals not made to original specification, damage to 

seals, incorrect fitting of glands, etc.  Ensure that apparatus is mounted securely. Ensure that seals or 

sealing materials have not degraded such that they no longer serve the purpose of preventing the 

ingress of flammable atmospheres. Replacement parts shall be in accordance with the manufacturer's 

specifications.

NOTE: The use of silicon sealant may inhibit the effectiveness of some types of leak detection 

equipment. Intrinsically safe components do not have to be isolated prior to working on them.

Summary of Contents for WA-S7000E

Page 1: ...on Manual IMPORTANT NOTE Read this manual carefully before installing or operating your new air conditioning unit Make sure to save this manual for future reference PORTABLE AIR CONDITIONER WA S7000E...

Page 2: ...ation Design Notice Energy Rating Information Ambient Temperature Range For Unit Operating Exhaust Hose Installation Choosing The Right Location Tools Needed Accessories Window Installation Kit Instal...

Page 3: ...is grounded and has the appropriate voltage The power cord is equipped with a three prong grounding plug to protect against shock Voltage information can be found on the nameplate of the unit Your un...

Page 4: ...ould be supervised to ensure that they do not play with the appliance Children must be supervised around the unit at all times be applicable for other countries except the European Countries If the su...

Page 5: ...capes endangers your health when hazar do us substances leak into the ground water and find their way into the food chain Do not use hazardous chemicals to clean or come into contact with the unit Do...

Page 6: ...reil au gaz en marche ou radiateur lectrique en marche Ne pas percer ni bruler Attention les frigorig nes peuvent tre inodores Please follow the instruction carefully to handle install clear service t...

Page 7: ...side the package will not cause a leak of the refrigerant charge The maximum number of pieces of equipment permitted to be stored together will be determined by local regulations 3 General work area A...

Page 8: ...uit is being used the secondary circuit shall be checked for the presence of refrigerant Marking to the equipment continues to be visible and legible Markings and signs that are illegible shall be cor...

Page 9: ...e following leak detection methods are deemed acceptable for systems containing flammable refrigerants Electronic leak detectors shall be used to detect flammable refrigerants but the sensitivity may...

Page 10: ...Isolate system electrically c Before attempting the procedure ensure that Mechanical handling equipment is available if required for handling refrigerant cylinders All personal protective equipment i...

Page 11: ...ted weighing scales shall be available and in good working order Hoses shall be complete with leak free disconnect couplings and in good condition Before using the recovery machine check that it is in...

Page 12: ...The unit with 3 meters extended exhaust duct is running by using 2 exhaust ducts Diameter 5 9inch Length 59inch Diameter 5 12inch Length 59inch The Energy rating and noise information for unit with 3...

Page 13: ...square footage of the room you want to cool by multiplying the room length by its width You also need to know the air conditioner s BTU British Thermal Unit rating which indicates the amount of heat...

Page 14: ...Hose Drain Hose 1 pc Window Slider Adaptor O N O F F T E M P S H O R T C U T T IM E R O N T IM E R O F F M O D E FA N S LE E P S W IN G LE D 1 set 1 pc Window Slider B Remote Controller and Battery on...

Page 15: ...ders once they are adjusted to the Proper length Window slider A Window slider B Bolt Window slider A Window slider B Window slider C Bolts Step Two Install the Exhaust hose assembly to the unit MODEL...

Page 16: ...sash and frame as shown Foam seal B Adhesive type shorter Foam seal A Adhesive type Or Or Window slider A Window slider B if required Foam seal C Non adhesive type 3 Cut the non adhesive foam seal C...

Page 17: ...actual shape shall prevail NOTE Cover the hole using the adaptor cap when not in use max 120cm or 47 inch min 30cm or 12 inch Expansion anchor position Adaptor cap Wall Exhaust Adaptor B Or 5 Insert t...

Page 18: ...error select models only E4 Display panel communication error EC Refrigerant leakage detection malfunction select models only Shows protection code P1 Bottom tray is full Connect the drain hose and d...

Page 19: ...nd UP buttons at the same time for 3 seconds to turn off Wireless function and the LED DISPLAY shows OF for 3 seconds press MODE button and UP to turn on Wireless function and the LED DISPLAY shows On...

Page 20: ...sure the hose is secure so there are no leaks Direct the hose toward the drain making sure that there are no kinks that will stop the warter flowing Place the end of the hose into the drain andmake su...

Page 21: ...e unit using a damp lint free cloth and mild detergent Dry the unit with a dry lint free cloth Drain the unit s water collection tray according to the instructions in the following section Run the app...

Page 22: ...urn off the unit and clean the filter according to instructions Call a service technician to inspect the unit and top off refrigerant Decrease the set temperature Make sure all windows and doors are c...

Page 23: ...TANT NOTE REMOTE CONTROLLER Thank you for purchasing our air conditioner Please read this manual carefully before operating your new air conditioning unit Make sure to save this manual for future refe...

Page 24: ...d Functions sections of this manual for a detailed description of how to use your air conditioner SPECIAL NOTE Button designs on your unit may differ slightly from the example shown If the indoor unit...

Page 25: ...FCC Rules Operation is subject to the following two conditions 1 This device may not cause harmful interference and 2 this device must accept any interference received including interference that may...

Page 26: ...SPEED Selects fan speeds in the following order AUTO LOW HIGH TEMP Decreases temperate in 1 F increments Min temperature is 62 F TIMER ON Sets timer to turn unit on see How to Use Basic Functions for...

Page 27: ...Displayed when remote controller is ON Low speed NO display Medium speed some units High speed Auto fan speed Displayed when TIMER ON time is set Displayed when TIMER OFF time is set Indicated all th...

Page 28: ...OFF Select DRY mode Set your desired temperature Turn on the air conditioner FAN Mode MODE ON OFF Select FAN mode Turn on the air conditioner Select COOL HEAT mode Set the temperature Turn on the air...

Page 29: ...2 Cancel either function by setting its timer to 0 0h Point remote to unit and wait 1sec the TIMER ON will be activated Press TIMER OFF button to initiate the OFF time sequence Point remote to unit a...

Page 30: ...is used to decrease energy use while you sleep and don t need the same temperature settings to stay comfortable This function can only be activated via remote control The sleep function is not availab...

Page 31: ...The design and specifications are subject to change without prior notice for product improvement Consult with the sales agency or manufacturer for details CR2712 RG51F H 1...

Page 32: ...t parts will be new or reconditioned Parts which are replaced become the property of Sunpentown The warranty applies for the use of the product in the USA only What is NOT COVERED Warranty does not in...

Reviews: