 Engineering Manual Revision 2.0 -021902 

17

Hood Width:  Island 

REV LOW  

 

The hood width should be equal the depth of the largest appliance from the wall plus allow for an 
additional 12” (305 mm) overhang from the front of the appliance.  Each hood should be a 
minimum 54” (1372mm). 
 

REV LOW

 

Exhaust Volume Vs Exhaust Duct Size 

Exhaust 

Volume 

Duct Collar Size 

Exhaust 

Volume 

Duct Collar Size 

CFM l/s 

W x L 

in x in

 

W x L 

mm x mm

 

CFM l/s 

W x L 

in x in

 

W x L 

mm x mm

 

450 

212 

10 x 4 

254 x 102 

3500  1652  10 x 33.5 

254 x 851 

500 

236 

10 x 4.5 

254 x 114 

3625  1711  10 x 34.5 

254 x 876 

625 

295 

10 x 6.0 

254 x 152 

3750  1770  10 x 36.0 

254 x 914 

750 

354 

10 x 7.0 

254 x 178 

3875  1829  10 x 37.0 

254 x 940 

875 

413 

10 x 8.0 

254 x 203 

4000  1888  14 x 27.0 

356 x 686 

1000  472 

10 x 9.5 

254 x 241 

4125  1947  14 x 28.0 

356 x 711 

1125  531 

10 x 10.5 

254 x 267 

4250  2006  14 x 29.0 

356 x 737 

1250  590 

10 x 12.0 

254 x 305 

4375  2065  14 x 30.0 

356 x 762 

1375  649 

10 x 13.0 

254 x 330 

4500  2124  14 x 30.5 

356 x 775 

1500  708 

10 x 14.0 

254 x 356 

4625  2183  14 x 31.5 

356 x 800 

1625  767 

10 x 15.5 

254 x 394 

4750  2242  14 x 32.5 

356 x 826 

1750  826 

10 x 16.5 

254 x 419 

4875  2301  14 x 33.0 

356 x 838 

1875  885 

10 x 18.0 

254 x 457 

5000  2360  14 x 34.0 

356 x 864 

2000  944 

10 x 19.0 

254 x 483 

5125  2419  14 x 35.0 

356 x 889 

2125  1003  10 x 20. 

254 x 508 

5250  2475  14 x 36.0 

356 x 914 

2250  1062  10 x 21.5 

254 x 546 

5375  2537  14 x 36.5 

356 x 927 

2375  1121  10 x 22.5 

254 x 572 

5500  2596  14 x 37.5 

356 x 953 

2500  1180  10 x 24.0 

254 x 610 

5625  2655  14 x 38.5 

356 x 978 

2625  1239  10 x 25.0 

254 x 635 

5750  2714  14 x 39.0 

356 x 991 

2750  1298  10 x 26.0 

254 x 660 

5875  2773  14 x 40.0 

356 x 1016 

2875  1357  10 x 27.5 

254 x 699 

6000  2832  14 x 41.0 

356 x 1041  

3000  1416  10 x 28.5 

254 x 724 

6125  2891  14 x 42.0 

356 x 1067 

3125  1475  10 x 30.0 

254 x 762 

6250  2950  14 x 42.5 

356 x 1080  

3250  1534  10 x 31.0 

254 x 787 

6375  3008  16 x 38.0 

406 x 965 

3375  1593  10 x 32.0 

254 x 813 

6500  3067  16 x 39.0 

406 x 991 

1. 

If exact exhaust volume is not indicated use duct size closest to required exhaust. 

2. 

Model  B water wash hoods and dry extractors have 1.5” W.C. (0.38kPa) for exhaust 
flow rates from 90 to 450 CFM/ft (140 to 700 l/s/m) 

Chart No. 5 

 

Make Up Air/Supply Air 

Introducing fresh air back into the kitchen is generally recommended as good engineering 
practice.  The amount of make up air should not exceed the total exhaust to maintain a negative 
pressure within the kitchen.  Inadequate amounts of fresh replacement air will result in cold 
drafts, hot spots, poor hood smoke capture and generally uncomfortable working conditions 
within the kitchen and uncomfortable environment in the dining room for the customers. 
 
One excellent method of introducing makeup air is through a make up air plenum built into the 
ventilator.  SPRING AIR SYSTEMS has two optional make up air arrangements; MP and MC.  
Directing the make up air through the exhaust hood ensures the correct quantity of make up air 
and good air distribution. 

Summary of Contents for Rev Low

Page 1: ...REV LOW Engineering Manual ___________________________ Spring Air Systems Inc Oakville Ontario Phone 905 338 2999 Fax 905 338 0179 info springairsystems com www springairsystems com...

Page 2: ...peration 2 Variflow Baffles 3 Model Number Designation 4 Water Wash REV LOW 5 Hood and Damper Assemblies 8 Dry REV LOW 13 REV LOW Exhaust Calculations 14 Exhaust Duct Sizes 17 Make Up Air 18 REV LOW S...

Page 3: ...tor The water wash hood is automatically cleaned in place at the end of each cooking day The REV LOW dry extractor is manually cleaned the dry extractor has inserts that are removed daily and washed i...

Page 4: ...aximumize the amount of the air mixture that enters the slot and minimize the amount of roll back into the canopy as the total amount of the air mixture deviates along the length of the cooking lineup...

Page 5: ...the owners operator of a commercial or institutional restaurant 1 More comfortable kitchen environment 2 Lower annual heating cost with little or no capital cost increase 3 Lower annual air conditioni...

Page 6: ...Single row box canopy hot water wash ventilator with fusible link spring loaded fire damper HT B F Single row box canopy hot water wash ventilator with thermostatic activated spring loaded fire dampe...

Page 7: ...t fan supply unit Spring Air SFA series time wash cycle and fire suppression system Water Wash REV LOW Hoods Automatic Wash Type C and H Ventilators SPRING AIR SYSTEMS ventilators are available with e...

Page 8: ...the spray continuously carries grease dirt and lint down the drain which reduces the daily grease build up The hot water required is approximately 9 gpm ft of ventilator at 40 psig see Chart No 2 The...

Page 9: ...hub drain Water Wash REV LOW Hoods TYPE C Core Extractors Water Wash The SPRING AIR SYSTEMS type C core extractor has the highest grease extraction efficiency available in a water wash ventilator The...

Page 10: ...secondary baffle as the exhaust air gyrates through the secondary chamber After leaving the secondary chamber the exhaust air enters the ventilator fire damper and duct collar and discharges into the...

Page 11: ...INAL BLOCKS BX CONDUIT TO J BOX ON TOP OF VENTILATOR SPRING RETAINING POST SOLENOID IN ENERGIZED POSITION DAMPER RETAINING CLIP IN UP POSITION TERMINAL BLOCK 80 DEGREE PIN ROTATION TO DAMPER CLOSED PO...

Page 12: ...ermostat set at 360F 182C responds quickly to activate the spring in the event of a fire 3 Pushing the fire test button in the control panel can periodically test the fire damper The damper will activ...

Page 13: ...amper assembly system consists of a fusible link damper mounted in the exhaust duct collar In the event of a fire within the grease extractor the fusible link melts closing the fire damper against the...

Page 14: ...fresh air damper All control wiring is 120V 1 60 The water wash hood washes in place at the end of each cooking day For more detail information covering the water wash control panels available please...

Page 15: ...ures the grease trough may require additional cleaning and or scraping to remove baked on solidified grease Type D Grease Extractor Figure 15 TYPE D GREASE EXTRACTOR The SPRING AIR SYSTEMS type D core...

Page 16: ...ce The NET EXHAUST VOLUME NEV decreases and increases proportionally to the length of some appliances These appliances are indicated in Chart No 4 with length dimensions For lengths other than indicat...

Page 17: ...8 1200 Comb Wood Gas Brick Oven 48 48 1200 Donut Fryer 32 32 285 430 Donut Fryer 72 72 320 480 Fry Top 36 36 300 340 Fryer Pitco model 14 17 150 Fryer 15 15 190 Fryer 16 16 100 200 Fryer 18 18 125 250...

Page 18: ...n appliance is not listed It is important to know the dimensions of each appliance The NET EXHAUST VOLUME NEV decreases and increases proportionally to the length of some appliances These appliances a...

Page 19: ...356 x 914 2250 1062 10 x 21 5 254 x 546 5375 2537 14 x 36 5 356 x 927 2375 1121 10 x 22 5 254 x 572 5500 2596 14 x 37 5 356 x 953 2500 1180 10 x 24 0 254 x 610 5625 2655 14 x 38 5 356 x 978 2625 1239...

Page 20: ...nsulation on the interior surfaces for sound attention and insulation A fire damper is located at the supply air inlet on top of the ventilator Model DD B F MP Figure 18 MC The make up air is discharg...

Page 21: ...nted electric or gas heating unit The vertical arrangement requires minimum roof space The roof mounted SFA V is complete with filters supply fan motorized discharge damper and end switch fan motor be...

Page 22: ...OTOR STARTER 120V 1 60 8 8 FLA POWER FROM SFA10 OV MOTOR STARTER TO SFA10 OV POWER FROM RPD20 CONTROLLER TO EXHAUST FAN MOTOR DISCONNECT SWITCH 120V 1 60 8 8 FLA POWER SUPPLY TO RPD11 CONTROLLER 120V...

Page 23: ...BTU hr output Typical SFA IGO Figure 24 Heating Capacity The total heating required is equal to the following Heating Capacity BTU hr Supply Volume CFM x 1 09 x TI TO Where TI Supply discharge tempera...

Page 24: ...management system Spring Air Systems can also supply the motor starters from stock RPD11 Controllers Figure 26 SPRING AIR SYSTEMS MODEL DD B F 6 0 3 92 AND INSTALLED PER NFPA 96 BELOW ROOF JOIST 24 T...

Page 25: ...atives available Refer to the individual specification sheets for SFA models and REV LOW hood controllers available REV LOW Work Sheet Date Job Name Representative Job Location Engineering Food Servic...

Page 26: ...ods Cartridge Hoods Filter Hoods Surface Fire Suppression Commercial Kitchen Exhaust Fans Kitchen Enviro Systems KES 100 Exhaust Commercial Kitchen Supply Units Compensating Hoods Exhaust Fans Supply...

Reviews: