Hood Width:  Single Row Wall Mounted 

The hood width should be equal the depth of the largest appliance from the wall plus allow for an 
additional 12” (305 mm) overhang from the front of the appliance.  The hood should be a 
minimum 47” (1194). 
 

Net Exhaust Air (NEV)Volume Chart for All 

RevLow

 

hoods 

Cooking Appliances 

Net Exhaust Volume 

Description 

Length (in)

Electric CFM 

Gas CFM 

Charbroiler 24 

24 

900 

1125 

Charbroiler 30 

30 

1100 

1325 

Charbroiler 34 

34 

1300 

1600 

Charbroiler 36 

36 

1440 

1800 

Charbroiler 48 

48 

1600 

2000 

Charbroiler 60 

60 

1800 

2250 

Charbroiler 72 

72 

2250 

2800 

Chicken broaster 20 

20 

200 

200 

Chicken broaster 30 

30 

300 

300 

Conveyor Oven one deck 90 

90 

325 

430 

Conveyor Oven two deck 90 

90 

430 

575 

Combi Oven  

51 

850 

880 

Comb. Wood/Gas Brick Oven 48 

48 

1200 

Comb. Wood/Gas Brick Oven 48 

48 

1200 

Donut Fryer 32 

32 

285 

430 

Donut Fryer 72 

72 

320 

480 

Fry Top 36 

36 

300 

340 

Fryer Pitco model 14 

17 

150 

Fryer 15 

15 

190 

Fryer 16 

16 

100 

200 

Fryer 18 

18 

125 

250 

Fryer 24 

24 

150 

300 

Griddle 24 

24 

200 

225 

Griddle 36 

36 

250 

275 

Gyro 18 

18 

175 

Hot Top Range 48 

48 

700 

880 

Induction Cookers 

18 

72 

n/a 

Kettle one with stand 28 

28 

130 

130 

Kettle Single 45 

45 

250 

250 

Microwave 24 

24 

30 

-  

Oven 38 

38 

180 

225 

Pasta Cooker 18 

18 

150 

150 

Pizza Oven 60 

60 

260 

325 

Rotisserie Oven 42 

42 

550 

750 

Rotisserie Oven 66 

66 

960 

1250 

Range stock pot 24 

24 

255 

300 

Range two burner regular duty 12 

12 

180 

225 

Range four burner regular duty 24 

24 

275 

315 

Range six burner regular duty 36 

36 

415 

475 

Salamander Broiler 36 

36 

270 

350 

Spreader 12 

12 

10 

10 

Steamer 30 

30 

150 

Solid Fuel 36” 

36 

1800 

Solid Fuel – 60” 

60 

2400 

Tilting Skillet 42 

42 

370 

500 

Toaster 18 

18 

50 

50 

Wok – one hole 30 

30 

500 

Wok – two hole 60 

60 

850 

Wok –three hole 90 

90 

1400 

Woodstone Oven 64 

64 

400 

Upright Broiler 2 shelf 36 

36 

540 

700 

Upright Broiler 3 shelf 36 

36 

810 

1050 

Warming Lamp 18 

18 

30 

30 

Chart No. 4 

Summary of Contents for Rev Low

Page 1: ...REV LOW Engineering Manual ___________________________ Spring Air Systems Inc Oakville Ontario Phone 905 338 2999 Fax 905 338 0179 info springairsystems com www springairsystems com...

Page 2: ...peration 2 Variflow Baffles 3 Model Number Designation 4 Water Wash REV LOW 5 Hood and Damper Assemblies 8 Dry REV LOW 13 REV LOW Exhaust Calculations 14 Exhaust Duct Sizes 17 Make Up Air 18 REV LOW S...

Page 3: ...tor The water wash hood is automatically cleaned in place at the end of each cooking day The REV LOW dry extractor is manually cleaned the dry extractor has inserts that are removed daily and washed i...

Page 4: ...aximumize the amount of the air mixture that enters the slot and minimize the amount of roll back into the canopy as the total amount of the air mixture deviates along the length of the cooking lineup...

Page 5: ...the owners operator of a commercial or institutional restaurant 1 More comfortable kitchen environment 2 Lower annual heating cost with little or no capital cost increase 3 Lower annual air conditioni...

Page 6: ...Single row box canopy hot water wash ventilator with fusible link spring loaded fire damper HT B F Single row box canopy hot water wash ventilator with thermostatic activated spring loaded fire dampe...

Page 7: ...t fan supply unit Spring Air SFA series time wash cycle and fire suppression system Water Wash REV LOW Hoods Automatic Wash Type C and H Ventilators SPRING AIR SYSTEMS ventilators are available with e...

Page 8: ...the spray continuously carries grease dirt and lint down the drain which reduces the daily grease build up The hot water required is approximately 9 gpm ft of ventilator at 40 psig see Chart No 2 The...

Page 9: ...hub drain Water Wash REV LOW Hoods TYPE C Core Extractors Water Wash The SPRING AIR SYSTEMS type C core extractor has the highest grease extraction efficiency available in a water wash ventilator The...

Page 10: ...secondary baffle as the exhaust air gyrates through the secondary chamber After leaving the secondary chamber the exhaust air enters the ventilator fire damper and duct collar and discharges into the...

Page 11: ...INAL BLOCKS BX CONDUIT TO J BOX ON TOP OF VENTILATOR SPRING RETAINING POST SOLENOID IN ENERGIZED POSITION DAMPER RETAINING CLIP IN UP POSITION TERMINAL BLOCK 80 DEGREE PIN ROTATION TO DAMPER CLOSED PO...

Page 12: ...ermostat set at 360F 182C responds quickly to activate the spring in the event of a fire 3 Pushing the fire test button in the control panel can periodically test the fire damper The damper will activ...

Page 13: ...amper assembly system consists of a fusible link damper mounted in the exhaust duct collar In the event of a fire within the grease extractor the fusible link melts closing the fire damper against the...

Page 14: ...fresh air damper All control wiring is 120V 1 60 The water wash hood washes in place at the end of each cooking day For more detail information covering the water wash control panels available please...

Page 15: ...ures the grease trough may require additional cleaning and or scraping to remove baked on solidified grease Type D Grease Extractor Figure 15 TYPE D GREASE EXTRACTOR The SPRING AIR SYSTEMS type D core...

Page 16: ...ce The NET EXHAUST VOLUME NEV decreases and increases proportionally to the length of some appliances These appliances are indicated in Chart No 4 with length dimensions For lengths other than indicat...

Page 17: ...8 1200 Comb Wood Gas Brick Oven 48 48 1200 Donut Fryer 32 32 285 430 Donut Fryer 72 72 320 480 Fry Top 36 36 300 340 Fryer Pitco model 14 17 150 Fryer 15 15 190 Fryer 16 16 100 200 Fryer 18 18 125 250...

Page 18: ...n appliance is not listed It is important to know the dimensions of each appliance The NET EXHAUST VOLUME NEV decreases and increases proportionally to the length of some appliances These appliances a...

Page 19: ...356 x 914 2250 1062 10 x 21 5 254 x 546 5375 2537 14 x 36 5 356 x 927 2375 1121 10 x 22 5 254 x 572 5500 2596 14 x 37 5 356 x 953 2500 1180 10 x 24 0 254 x 610 5625 2655 14 x 38 5 356 x 978 2625 1239...

Page 20: ...nsulation on the interior surfaces for sound attention and insulation A fire damper is located at the supply air inlet on top of the ventilator Model DD B F MP Figure 18 MC The make up air is discharg...

Page 21: ...nted electric or gas heating unit The vertical arrangement requires minimum roof space The roof mounted SFA V is complete with filters supply fan motorized discharge damper and end switch fan motor be...

Page 22: ...OTOR STARTER 120V 1 60 8 8 FLA POWER FROM SFA10 OV MOTOR STARTER TO SFA10 OV POWER FROM RPD20 CONTROLLER TO EXHAUST FAN MOTOR DISCONNECT SWITCH 120V 1 60 8 8 FLA POWER SUPPLY TO RPD11 CONTROLLER 120V...

Page 23: ...BTU hr output Typical SFA IGO Figure 24 Heating Capacity The total heating required is equal to the following Heating Capacity BTU hr Supply Volume CFM x 1 09 x TI TO Where TI Supply discharge tempera...

Page 24: ...management system Spring Air Systems can also supply the motor starters from stock RPD11 Controllers Figure 26 SPRING AIR SYSTEMS MODEL DD B F 6 0 3 92 AND INSTALLED PER NFPA 96 BELOW ROOF JOIST 24 T...

Page 25: ...atives available Refer to the individual specification sheets for SFA models and REV LOW hood controllers available REV LOW Work Sheet Date Job Name Representative Job Location Engineering Food Servic...

Page 26: ...ods Cartridge Hoods Filter Hoods Surface Fire Suppression Commercial Kitchen Exhaust Fans Kitchen Enviro Systems KES 100 Exhaust Commercial Kitchen Supply Units Compensating Hoods Exhaust Fans Supply...

Reviews: