It will be possible to display one of the following variables on the screen:
LEVEL / DENSITY (PV)
CURRENT (TV)
PERCENTAGE (SV)
SENSOR TEMPERATURE (FV)
4.5
K
EYBOARD
C
ONFIGURATION
The electronic transmitters have some configuration functions available via keyboard and LCD
display, provided with the transmitters themselves.
Press the [MENU] button to enter the password entering dialog (the default password is
0000). Confirm by [OK] to enter the configuration menu.
The display will allow to choose from the different functions described in the table below.
Use the
and
buttons to show the sequence of the available functions and press [OK] to
confirm the selected function.
When the display is in numerical entering mode, the cursor will blink.
To move the cursor press the
button; to raise the value of the digit press the
button.
Press the [OK] button to confirm; use instead the [MENU] button to cancel the modifications
and to go back to the standard display.
Function
Display name
Use
Choice span
Zero setting
LRV
Indicates and allows you
to manually enter the
initial value of the
interval
(the
value
corresponding to the 4
mA output). The unit of
measurement
is
displayed at the bottom
right of the screen.
Between the
sensor limits
24.2
°C
34.73
▁▂▃
%
4.220
▁▂▃
mA
1220
▁▂▃
mm