17
17
If the system is in Prime mode, the following will occur:
•
Output 9 will be energized (lubrication on)
•
Output 10 will output a 120 cycle per minute pulse train to rapidly cycle the piston pumps
•
The Blue LED indicator on the control panel door will strobe in sync with Output 10
•
The Red LED indicator on the PRIME pushbutton located on the PCB will be illuminated, indicating that the
system is in Prime mode
•
HVPS will be disabled
•
Nozzle 1 & 2 Pressure Low and Pressure High inputs will be disabled
To exit Prime mode, one
of the following must occur:
•
The system is put into Lubrication Mode (Input 3 is energized). This automatically terminates Prime mode
•
Press the Reset button on the control panel door
•
Press the Prime pushbutton located on the printed circuit board
•
Momentarily energize Input 1 (Customer Prime mode input)
•
The Prime mode cycle timer expires (60 minutes)
•
A fault condition (Low air pressure or Low reservoir level)
TEST MODE
Terminal Block J9
-
INPUT 2
-
Connection 3 & 4 and/or PCB Mounted Pushbutton
Test mode will be active for 15 minutes and should be used to check the system operation anytime when the system
is in Standby Mode. This means that the system
cannot
be in Lubrication mode, Burst mode, Prime mode, or under
any fault condition.
Block J9, Input 2 is intended for a
customer
-
installed
normally
-
open momentary pushbutton (Optional). The PCB
mounted button will be fully functional whether or not the input is connected.
If the system is in Test mode, the following will occur:
•
Output 9 will be energized (lubrication on)
•
Output 10 will output a low frequency pulse train (adjustable by the PUMP ADJ potentiometer) to cycle the
piston pumps
•
The Blue LED indicator on the control panel door will strobe in sync with Output 10
•
The Red LED indicator on the TEST pushbutton located on the PCB will be illuminated indicating that the
system is in Test mode
•
HVPS will be enabled
To exit Test mode, one of the following must occur:
•
The system is put into Lubrication mode (Input 3 energized). This automatically terminates Test mode
•
Press the Reset button on the control panel door
•
Press the TEST pushbutton located on the printed circuit board
•
Momentarily energize Input 2 (Customer Test mode input)
•
Test mode 15 minute cycle timer expires
•
A fault condition
Figure 4.7
-
2
PCB TEST