7.3

Failure table

The letter indications comply with the main figure in § 
2.1. An overview of the replacement parts has been 
included in § 8.2.

General

Problem

Possible cause

Correction

Err 3 Syst.temp. too low

There is a risk of freezing.

The temperature of the system fluid is 
< 0 °C.

Provide a temperature of > 0 °C.

Err 4 Syst.temp. too high

There is a risk of boiling.

The temperature of the system fluid is 
> 90 °C.

Provide a temperature of < 90 °C.

Err 5 Entrance flow

The flow in the inlet line has been 
blocked 

1)

.

The solenoid valve (N) in the inlet line 
does not open.

Replace (a part of) the solenoid valve.

A valve in the inlet line is closed.

Open the valve.

The inlet line has been blocked.

Remove the blocking.

The pressure switch (R) is defect.

Replace the pressure switch.

Critical setting adjustment valve inlet 
(J).

Turn adjustment valve ¼ position up 
(from fully open).

Cable to pressure switch (R) 
disconnected or interupted.

Replace the cable. Replace the cable 
lugs.

The adjustment valve (P) inlet has not 
been set correctly.

Turn the adjustment valve outlet to 
the correct position (see § 5.4.1 ).

Err 6 Flow

The flow in the outlet line has been 
blocked 

1)

.

One of the solenoid valves (N) is not 
closing.

Clean valve internally. If necessary, 
replace (a part of) the solenoid valve.

The valve in the outlet line is closed.

Open the valve.

The outlet line has been blocked.

Remove the blocking.

The pump (O) does not run.

Check the pump. Check and replace 
the pump fuse in the control unit.

The pressure switch (R) is defect.

Replace the pressure switch.

The automatic air vent (B) is blocked.

Replace the automatic air vent.

Err 7 Fluid lack vessel

There is a risk of running dry, the fluid 
level in the vessel is at the minimum.

The automatic air vent (B) is defect or 
blocked.

Replace the automatic air vent.

The vessel has not been filled.

Fill the vessel (see § 5.5.4).

The level switch (I) is defect.

Replace the level switch.

Cable to level pin disconnected or 
interrupted.

Check cable connection.

Replace the cable.

OBJ_BUCH-45-001.book  Page 37  Tuesday, June 14, 2011  10:56 AM

Summary of Contents for SpiroVent Superior S6A

Page 1: ...t med tryck fotokopia mikrofilm eller p n got annat s tt utan f reg ende skriftligt tillst nd fr n Spirotech bv Denna handbok r sammanst lld med st rsta omsorg Om handboken nd skulle inneh lla n gon f...

Page 2: ...esm tare I Niv omkopplare i k rlets botten J St llbar intagsventil K Temperaturk nnare L Reservpump f r typS6A R 2P M T mningsanslutning under k rlet N Magnetventil O Huvudpump P St llbar returventil...

Page 3: ...Bokst verna korresponderar med huvudfiguren p f reg ende sida i S6A D K J N A S F R B C I M O P U M TT PS PS LS PI S6A R M TT PS PS LS PT PI FT D K J N N H A S F R B C I M E O P Q U S6A R 2P N N M O P...

Page 4: ...akuumfasen Den kontinuerligt l pande pumpen O skapar ett undertryck i k rlet C Genom undertrycket slipper de l sta gaserna ut ur v tskan och samlas Skall tas bort upptill i k rlet Magnetventilen ppnas...

Page 5: ...Nominell str mstyrka 3 5 A 3 5 A 5 5 A Startstr m 2 6 nominell str mstyrka 2 6 nominell str mstyrka 2 6 nominell str mstyrka S kring 10 A 3 15 A T 10 A 3 15 A T 10 A 3 15 A T Skyddsklass IP X4D IP X4...

Page 6: ...H Byggnads r I Vikt Signal S6A S6A R S6A R 2P Enheten i drift Potentialfri Potentialfri Potentialfri St rning i enheten Potentialfri Potentialfri Potentialfri Frigivning stopp av enheten 24 VAC 24 VA...

Page 7: ...v personer till installationsplatsen Lyft enheten i handtagen C 5 3 Installation och montering VARNING Vinscha inte enheten n r den inte r f rpackad Anv ndning av lyftband kedjor och krokar kan orsaka...

Page 8: ...bla tilloppsslangen C Hos typerna S6A R och S6A R 2P 1 Montera en kran F och en backventil E i p fyllnadsv tskans matningsledning 2 Koppla matningsledningen till enhetens p fyllnadsanslutning G OBS Ko...

Page 9: ...3mm om enheten kopplas direkt till str mf rs rjningen Anv nd matningskablar med r tt dimensioner Byt alltid ut en trasig s kring mot en s kring med samma v rde Se 3 3 A kontakt kontakt stift anslutni...

Page 10: ...um och tid 1 Tryck p ON OFF 2 V lj ett spr k med S och T Tryck p ENTER 3 St ll in datum med S och T Tryck p ENTER 4 St ll in datum med S och T Tryck p ENTER 5 St ll in tiden med S och T Tryck p ENTER...

Page 11: ...ren B 4 S tt tillbaka h ljet C p enheten och s tt fast det med de 2 skruvarna D 5 5 Installation och drift 5 5 1 Installation St ll in anv ndarparametrarna 1 Tryck p MENU V lj Settings med S och S Try...

Page 12: ...6A R och S6A R 2P Minnet kan avl sas s h r 1 Tryck p MENU V lj User menu History med SS och S Tryck p ENTER 2 V lj Fault history eller Operation history med S och T Tryck p ENTER 3 V lj en punkt med S...

Page 13: ...ndens uppst p vissa platser Kondensv tskan t ms ut genom ppningarna i ramen Hos typerna S6A R och S6A R 2P Den tillfogade v tskem ngden B beror p skillnaden A mellan systemtrycket och p fyllnadsvattne...

Page 14: ...G 5 T m enheten genom t mningsanslutningen G 6 ppna avluftningsskruven p huvudpumpen f r att t mma enheten fullst ndigt Se figuren i 5 4 2 VARNING Varsko alltid installat ren vid driftsfel St ng av sp...

Page 15: ...er avbruten Byt ut kabeln Byt ut kabelfl nsarna Justeringsventilens P inlopp har inte st llts in korrekt Vrid justeringsventilen f r utloppet till den korrekta positionen se 5 4 1 Err 6 Flow Fl det i...

Page 16: ...yp S6A R och S6A R 2P S rskilt f r typerna S6A R och S6A R 2P Problem M jlig orsak rg rd Err 1 Psystem too low Systemtrycket r l gre n 1 bar Ett fel i anl ggningen S rj f r ett systemtryck p 1 bar L c...

Page 17: ...en Max refill freq Err 14 Refill time too high P fyllnaden tar f r l ng tid L ckage f religger i anl ggningen Reparera l ckan Kontrollera inst llningen Alarm refill after Err 15 Refill quantity F r my...

Page 18: ...0 Hz 15 511 O Pump typ CR1 9 AAA HQQE 60 Hz R70 675 V H lje 12 023 N Magnetventil exklusive spole 12 022 N Spole f r magnetventil 15 765 N Insats f r magnetventil 12 021 S Tryckm tare R17 889 terfylln...

Page 19: ...ker Initialer Typ av underh ll Inspektionsdatum Tekniker Initialer Typ av underh ll Inspektionsdatum Tekniker Initialer Typ av underh ll Inspektionsdatum Tekniker Initialer Typ av underh ll Inspektion...

Page 20: ...till 2 r efter ink psdatum Garantin f rfaller i fall av felaktig installation okunnigt bruk och eller om obefogad personal f rs ker utf ra reparationer F ljdskada t cks inte av garantin 10 CE F RKLAR...

Page 21: ...eans of printing photocopying microfilm or in any other way without prior written permission from Spirotech bv This manual has been composed with the utmost care Should however this manual contain any...

Page 22: ...vel switch in bottom of vessel J Adjustable inlet valve K Temperature sensor L Back up pump for type S6A R 2P M Drain connection under the vessel N Solenoid valve O Main pump P Adjustable outlet valve...

Page 23: ...r indications comply with the main figure on the previous page i S6A D K J N A S F R B C I M O P U M TT PS PS LS PI S6A R M TT PS PS LS PT PI FT D K J N N H A S F R B C I M E O P Q U S6A R 2P N N M O...

Page 24: ...ntinuously running pump O provides underpressure in the vessel C The underpressure causes the release of the gases dissolved in the fluid which are collected at the top of the vessel The solenoid valv...

Page 25: ...1300 W Nominal power consumption 3 5 A 3 5 A 5 5 A Starting current 2 6 nominal current 2 6 nominal current 2 6 nominal current Protection 10 A 3 15 A T 10 A 3 15 A T 10 A 3 15 A T Protection class I...

Page 26: ...ial number H Year of construction I Weight Signal S6A S6A R S6A R 2P Unit in operation Potential free Potential free Potential free Unit failure Potential free Potential free Potential free Unit relea...

Page 27: ...ith two persons to the place of installation Lift the unit using the handles C 5 3 Installation and mounting WARNING Do not hoist the unit when unpacked The use of webbing slings chains and hooks can...

Page 28: ...ble inlet hose C With the types S6A R and S6A R 2P 1 Insert a valve F and a non return protection E in the refill fluid supply line 2 Connect the supply line to the refill connection G of the unit CAU...

Page 29: ...tact opening 3mm if the unit is directly connected to the power supply Use supply cables with the correct dimensions Always replace a defect fuse by a fuse of the same value See 3 3 A connector contac...

Page 30: ...1 Press ON OFF 2 Select a language using S and T Press ENTER 3 Set the date using S and T Press ENTER 4 Set the day using S and T Press ENTER 5 Set the time using S and T Press ENTER System pressure...

Page 31: ...the pressure gauge B 4 Put back the cover C on the unit and fasten it with the 2 screws D 5 5 Install and operate 5 5 1 Install Set the user parameters 1 Press MENU Select Settings using S and T Pres...

Page 32: ...A R and S6A R 2P The memory can be read in the following way 1 Press MENU Select User menu History using S and T Press ENTER 2 Select Fault history or Operation history using S and T Press ENTER 3 Sel...

Page 33: ...rough the openings in the frame With the types S6A R and S6A R 2P The amount of fluid that is added B depends on the difference A between the system pressure and the refill water pressure A System pre...

Page 34: ...unit through the drain connection G 6 Open the air vent screw on the main pump to completely empty the unit See the figure in 5 4 2 WARNING In case of failure always warn the installer Remove the volt...

Page 35: ...nterupted Replace the cable Replace the cable lugs The adjustment valve P inlet has not been set correctly Turn the adjustment valve outlet to the correct position see 5 4 1 Err 6 Flow The flow in the...

Page 36: ...2P Problem Possible cause Correction Err 1 Psystem too low The system pressure is below 1 bar A failure in the installation Provide a system pressure of 1 bar There is a leak in the installation Repa...

Page 37: ...ck the setting Max refill freq Err 14 Refill time too high Refilling takes too long There is a leak in the installation Repair the leak Check the setting Alarm refill after Err 15 Refill quantity Too...

Page 38: ...50 Hz 15 511 O Pump type CR1 9 AAA HQQE 60 Hz R70 675 V Cover 12 023 N Solenoid valve excluding coil 12 022 N Coil for solenoid valve 15 765 N Interior for solenoid valve 12 021 S Pressure gauge R17...

Page 39: ...aintenance Inspection date Technician Initials Nature of the maintenance Inspection date Technician Initials Nature of the maintenance Inspection date Technician Initials Nature of the maintenance Ins...

Page 40: ...ars following the purchasing date The guarantee lapses in cases of faulty installation incompetent use and or non authorised personnel trying to make repairs Consequential damage is not covered by the...

Reviews: